Honeywell T641A Скачать руководство пользователя страница 4

4

Settings

TEMPERATURE SETTING

Move the heating and cooling set point levers to the

desired comfort positions. See Fig. 3.

SWITCH SETTING

T641B—momentary system override switch that in the

ON position will energize a relay that can be used in
building management systems or other application.
The momentary override switch will output a 24 Vac
signal as long as the switch in held in the ON position.
In the OFF position, no output signal will be present.
For use in building management systems, the system
that the T641B interfaces with must be capable of
detecting a contact closure and respond accordingly to
perform a desired action.

T641C—manual heat/cool changeover switch. With this

switch set in the cool position, wire to damper actuator
as shown in Fig. 5. Be sure to determine direction of
damper opening for correct wiring between the T641
and ML6161. See Fig. 7. The changeover switch can
be placed in the heat position to reverse action at
terminals Y and W.

Fig. 7—Determining direction of damper opening
for correct wiring of ML6162 to T641.

IMPORTANT:  An incorrectly leveled thermostat will

cause the temperature control to deviate from set
point. It is not a calibration problem.

6. Install two screws in top mounting holes and tighten.
7. Replace the thermostat cover.

WARNING

Because the cooling anticipator operates continu-
ously in the floating band, the T641 incorporates a
factory offset that calibrates the thermostat. The
offset causes the T641 to appear to be switching
10.5

°

  F lower when not powered compared to

actual operation. The cooling anticipator is needed
to provide proper thermostat cycling by matching
the current draw of the ML6161 Actuator. To
ensure proper thermostat calibration and operation,
the C terminal must be used.

Fig. 5—ML6161 used with T641 for Type 

B

damper applications. Y terminal will energize
counterclockwise winding on call for cooling,
driving motor open.

120 
VAC

SYSTEM
TRANSFORMER

24 VAC

T641A THERMOSTAT

R

C

Y

W

PHASE SHIFT CAP.

DRIVE
CCW
WINDING

DRIVE
CW
WINDING

MOTOR ML6161

COMMON

M2257A

COM

CCW

CW

Fig. 6—T641B showing terminals X and C
energizing external relay when momentary
system override switch is pressed to ON
position.

120 
VAC

SYSTEM
TRANSFORMER

24 
VAC

T641B THERMOSTAT

R

C

Y

W

PHASE SHIFT CAP.

DRIVE
CCW
WINDING

DRIVE
CW
WINDING

MOTOR ML6161

COMMON

M2268

COM

CCW

CW

X

EXTERNAL
RELAY

NOTE:  The ML6161 is designed to open a damper by

driving the damper shaft in either the clockwise

                     (cw)

or counterclockwis

e      

(ccw) direction. To wi

re the

T641 correctly to the ML6161, see Figs. 5 and 7.

Cooling
Air Flow

CW TO OPEN, CCW TO CLOSE

CCW TO OPEN, CW TO CLOSE

M2067A

Cooling
Air Flow

TYPE A  DAMPER

TYPE B  DAMPER

Содержание T641A

Страница 1: ... is sized to handle an average peak load notthesumoftheindividualpeaks Aseachzonepeaks at a different time of day extra air is borrowed from the off peak zones This transfer from low load to high load zones occurs only in true VAV systems Pressure dependent systems do not incorporate an indi vidual zone air flow sensor and depend on a stable system pressure to maintain flow These systems require s...

Страница 2: ... and ordinances The T641 utilizes a four wire opera tion so an additional transformer common wire must be present for correct wiring and operation See Fig 2 for functional schematic of T641 Screw terminals are on the back of the thermostat See Fig 3 Thepartno 221618CoverPlateisavailablewhenreplac ing a competitive device that has left marks on the wall See Fig 4 1 Grasp the thermostat cover at the...

Страница 3: ...NG SCREWS 4 THERMOSTAT COVER M6111 EXTERNAL SET POINT LEVER Fig 4 Mounting T641 using the accessory wallplate Y C X W R 80 70 60 50 OFF ON SYSTEM OVERRIDE SPIRIT LEVEL WALLPLATE HEATING CONTACT MOUNTING HOLES 4 COOLING CONTACT INTERNAL SET POINT LEVER MOUNTING HOLES 4 WIRING TERMINAL UP TO 5 M 965 FRONT OF THERMOSTAT COVER REMOVED BACK OF THERMOSTAT ...

Страница 4: ...les and tighten 7 Replace the thermostat cover WARNING Because the cooling anticipator operates continu ously in the floating band the T641 incorporates a factory offset that calibrates the thermostat The offset causes the T641 to appear to be switching 10 5 F lower when not powered compared to actual operation The cooling anticipator is needed to provide proper thermostat cycling by matching the ...

Страница 5: ...o close Replace the ML6161 if the motor does not run in either direction With the T641 controlling the ML6161 or equivalent actuator lower the set point of the thermostat to call for cooling Observe the operation of the motor If the damper is closed it should begin to open If not adjust the set point of the T641 higher to determine if the wiring is correct If no movement is observed check for the ...

Страница 6: ...6 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 6 ...

Отзывы: