T4398A,B PRECISION ELECTRIC HEATING THERMOSTAT

3

69-1604

INSTALLATION

WARNING

120-277 Volt Line Voltage Hazard. 

Can cause serious injury or death.

Do not install thermostat unless you are a trained, 

experienced electrical service technician.

CAUTION

Electrical Shock Hazard. 

Can cause personal injury and equipment 

damage.

Disconnect power supply before connecting wiring.

Use a limit control when wiring the thermostat.

MERCURY NOTICE

If this control is replacing a control that contains 

mercury in a sealed tube, do not place your old control 

in the trash. Dispose of properly.

Contact your local waste management authority for 

instructions regarding recycling and the proper 
disposal of an old control.

When Installing This Product . . .

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-
tion.

2.

Check the rating given in the instructions and on the 

product to make sure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

5.

Follow local codes for installation and application.

Selecting Location

— Mount the thermostat on an approved electrical junction 

box. 

— Locate the thermostat 4 to 5 ft (1.5m) above the floor on an 

inside wall where the thermostat can be exposed to 

average room temperature.

— Locate the thermostat away from concealed warm or cold 

water pipes, light switches and dimmers, and refrigerators.

— Locate the thermostat away from drafts of hallways, 

fireplaces, stairways, and fans.

Mounting 

 When replacing an old line voltage thermostat:

— Carefully remove the old thermostat to avoid damaging the 

wiring insulation. 

— Check the old insulation for cracks, chips, or fraying and 

apply approved electrical tape, where necessary, to ensure 

adequate insulation.

NOTE: Make line voltage wiring connections directly to the 

leadwires installed on the thermostat, using wire con-

nectors approved for the number and size of conduc-

tors.

IMPORTANT 

When using aluminum conductors, all wiring connec-
tions to the thermostat must be made to the factory-

installed lead wire, using approved CO/ALR solder-

less connectors.

1.

Connect all wires with the thermostat cover in place. Be 

sure that all wire connectors are tight. Install any secu-
rity features. See Fig. 2 and 3.

2.

Pre-bend the solid conductors and push them into the 

electrical box.

3.

Remove the thermostat cover by grasping both the top 

and bottom of the cover and pulling out..

IMPORTANT

Carefully handle the thermostat. Excessive pressure 

can damage the control knob or sensing element.

4.

Turn the dial so the setpoint indicator is at the 12 o’clock 

position. (This prevents accidental damage to the dial- 
stop during mounting.)

5.

Using the screwdriver, secure the thermostat to the 

electrical box by tightening the two mounting screws. 
See Fig. 4.

6.

Level the thermostat only for appearance.

7.

Tighten the screws and replace the cover.

Fig. 2. T4398A typical hookup.

M5791B

L1 
(HOT)

L2

L1

T1

1

2

4

3

SOLDERLESS
CONNECTORS

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.

USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS 
WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE
HAZARD MAY RESULT.

USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.

BREAKS AND REMAKES BELOW -31

°

F (-35

°

C); NORMALLY

THERMAL ACTIVATED. BREAKS ON TEMPERATURE RISE; 
MAKES ON TEMPERATURE FALL. 

1

2

3

4

T4398A

ELECTRIC 
HEATER

Содержание T4398A

Страница 1: ...lement provides high temperature sensitivity with minimum droop Canadian Standards Association CSA Performance Certified up to 20A CSA Certified UL Listed up to 5 kW at 277 Vac Long life industrial grade Micro Switch mechanism Rugged engineered plastic mounting base with captive mounting screw Color coded flyleads compatible with aluminum wire for quick installation Replaces any standard wall moun...

Страница 2: ...nd thermal non adjust able Switch Type Enclosed industrial grade Micro Switch snap switch T4398A Single line break single pole single throw T4398B Double pole single throw with double line break double pole single throw in Off position Wiring Connections Six inch 150 mm stranded copper leadwires suitable for con necting to aluminum wiring if approved special service CO ALR connectors are used Elec...

Страница 3: ...n old line voltage thermostat Carefully remove the old thermostat to avoid damaging the wiring insulation Check the old insulation for cracks chips or fraying and apply approved electrical tape where necessary to ensure adequate insulation NOTE Make line voltage wiring connections directly to the leadwires installed on the thermostat using wire con nectors approved for the number and size of condu...

Страница 4: ...R A FIRE HAZARD MAY RESULT BREAKS AT POSITIVE OFF AND REMAKES UNDER 31 F 35 C NORMALLY THERMALLY ACTIVATED BREAKS ON TEMPERATURE RISE MAKES ON TEMPERATURE FALL USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE BREAKS AT POSITIVE OFF ONLY NOT THERMALLY ACTIVATED DO NOT CONNECT GROUNDED CONDUCTOR NEUTRAL ON 120 OR 227V CIRCUITS INSULATE AND TAPE OR CUT OFF RED WIRES IF UNUSED 1 2 3 4 5 6 5 L2 T2...

Страница 5: ...r is affected by barometric pressure and altitude Deviations up to 1 F 1 2 C are within normal operation The control point drops 2 F every 1000 ft 1 C 300m above sea level See Fig 5 and 6 Fig 5 T4398 altitude correction in ft Fig 6 T4398 altitude correction in m To calibrate see Fig 7 1 Remove cover and place it in a location that allows it to sense the room temperature NOTE Allow several minutes ...

Страница 6: ...lock cover drive Allen screw into thermostat base until screw body clears cover Fig 8 Installing locking cover To install the range stops select models Fig 9 1 Set thermostat to desired setpoint and remove the cover 2 Install plastic dowels supplied into minimum and or maximum range stop holes on the back of the cover 3 Reinstall the cover and check range stop operation Fig 9 Installing range stop...

Страница 7: ... the diaphragm changes into liquid The diaphragm collapse to a fraction its original thickness turning on the heat regardless of setpoint This feature guarantees minimum yet reliable operation of heaters in spaces near freezing NOTE To prevent heat from turning on below 40 F 4 C turn off the circuit at the breaker panel or install a T4398B ...

Страница 8: ... RQWURO 6ROXWLRQV RQH ZHOO RQH ZHOO LPLWHG RQH ZHOO LPLWpH RXJODV ULYH 1RUWK QDPLF ULYH ROGHQ 9DOOH 01 6FDUERURXJK 2QWDULR 0 9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers T4398A B PRECISION ELECTRIC HEATING THERMOSTAT ...

Отзывы: