T4031A,B,P; T6031A,B REFRIGERATION TEMPERATURE CONTROLLERS

60-2177—3

Fig. 2. 107324A bulb holder.

To install duct:

1. Make a hole in duct wall to admit sensing bulb into

holder.

2. Using holder as template, mark and drill mounting holes.
3. Break off bulb holder to required length. (Be sure holder

is long enough to hold sensing bulb away from duct wall
and in freely circulating air.)

4. Place capillary tubing in bulb holder channel, with bulb at

inner end of holder. Pinch together top edges of channel
segments.

5. Insert assembled bulb and holder into duct, and fasten to

duct wall with screws supplied.

Tank Installation

The sensing bulb can be inserted directly into a tank using a
compression fitting; or the bulb can be inserted into an immer-
sion well (order separately), which is screwed into a tank or
boiler.

Select a location where liquid of average temperature can
circulate freely around the sensing bulb.

Using Compression Fitting (Fig. 3)

1. Drain system. Screw boiler plug into properly sized and

threaded boiler or pipe tapping.

2. Place packing nut on capillary tubing.
3. Slide sensing bulb completely through boiler plug.
4. Place composition disc and the four slotted brass

washers on capillary tubing.

5. Slide assembly into boiler plug and tighten packing nut.
6. Refill system and check for leaks. Neatly coil excess

capillary tubing.

Using Immersion Well (Fig. 4)

1. Drain system. Screw the well into threaded fitting.
2. Refill system and check for leaks.
3. Insert sensing bulb into well until it bottoms.
4. Fit bulb retaining clamp over immersion well flange and

capillary tubing, and tighten screw.

M8970

Fig. 4. Immersion well installation.

Cold Room Installation

Locate the bulb in freely circulating air in the controlled area or
on the suction side of a refrigerant line, and secure the bulb in
position.

Wiring (Fig. 5)

All wiring must comply with local electrical codes and ordi-
nances.

Two knockouts are provided, one at the top and one at the
bottom of the case for 1/2 in. conduit. Follow the wiring
instructions furnished with the heating or cooling system. For
replacement, make sure the new control is wired into the
system to operate the same as the old control.

M4494

1

2

1

2

B TERMINAL ON T6031 CONTROLLERS ONLY.

AT SETPOINT MINUS DIFFERENTIAL SETTING.

TEMPERATURE FALL
B-R MAKES

TEMPERATURE RISE
R-W MAKES

B

R

W

Fig. 5. Wiring terminals on T4031 and T6031 temperature

controllers.

COMPOSITION 
PACKING
(SLIT)

BOILER PLUG

THREAD

SLOTTED WASHERS 
ASSEMBLED 
IN PAIRS:

PACKING NUT

M4492

SENSING 
BULB

Fig. 3. Compression fitting installation.

BULB RETAINING 
CLAMP

IMMERSION WELL

WELL SPUD

CAPILLARY

M4493

Содержание T4031A

Страница 1: ...es and defrost termination Universal mounting bracket is available for easy replacement of other controllers Models are available with various control ranges Control setpoint is dial knob adjustable Models are available with fixed or adjustable tempera ture differentials Capillary lengths are 5 8 or 20 ft 1 5 2 4 6 1m depending on model Reliable snap acting spst or spdt switch Ambient temperature ...

Страница 2: ...trol Sales office check white pages of your phone directory 2 Home and Building Control Customer Relations Honeywell 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 International Sales and Service Offices in all principal cities of the world Capillary Lengths and Temperature Ranges Capillary Length...

Страница 3: ...ed The ambient temperature must not exceed 125 F 52 C in the area where the controller is installed Install the sensing element where it can sense the average temperature Avoid sharp bends or kinks in the capillary tubing that can affect the accuracy of the controller Carefully coil the excess capillary tubing and leave it directly beneath the controller The 130883 Mounting Plate furnished with TR...

Страница 4: ... tubing 5 Slide assembly into boiler plug and tighten packing nut 6 Refill system and check for leaks Neatly coil excess capillary tubing Using Immersion Well Fig 4 1 Drain system Screw the well into threaded fitting 2 Refill system and check for leaks 3 Insert sensing bulb into well until it bottoms 4 Fit bulb retaining clamp over immersion well flange and capillary tubing and tighten screw M8970...

Страница 5: ...All controllers are carefully tested and calibrated at the factory under controlled conditions If the controller is not operating at a temperature corresponding to the scale and differential setting verify that the bulb senses the average temperature of the medium If the temperature of the controlled medium is changing rapidly the differential will appear wider than its setting M4497 TERMINAL SCRE...

Страница 6: ...6 T4031A B P T6031A B REFRIGERATION TEMPERATURE CONTROLLERS 60 2177 3 ...

Страница 7: ...7 T4031A B P T6031A B REFRIGERATION TEMPERATURE CONTROLLERS 60 2177 3 ...

Страница 8: ... World Home and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 60 2177 3 J H Rev 5 95 Printed in U S A QUALITY IS KEY www honeywell com building components ...

Отзывы: