Chapter 3 - Installation
1. Connect the video and network interface cables.
WARNING
AC power cords from all computing nodes mounted in a given cabinet must be distributed
across the two power entries as equally as possible. Failure to do so may result in tripping
the circuit breakers.
2. Connect the Honeywell AC power cords.
3. Perform any one of the following, as necessary.
l
If you are not using Fault Tolerant Ethernet (FTE), connect the Ethernet cable to the on-board
RJ-45 connector.
l
If you are using an Intel dual NIC card for FTE, connect the FTE cable to the NIC card in the
expansion slot.
l
If you are using the on-board NICs for FTE, connect the FTE cable to the onboard RJ-45
connector.
4. Secure any loose cables, and verify that all cables have proper strain relief.
5. If necessary, refer to the section
Install air duct baffles and blank panel front covers in cabinet
.
ATTENTION
Any unused rack mount space must have an air duct baffle and blank front panel
installed.
6. To complete the installation, turn on the server.
3.4.5
Install air duct baffles and blank panel front covers in cabinet
Air duct baffles and blank panel front covers ensure that the airflow within the cabinet allows proper
cooling for the servers. The following image illustrates the air duct baffles and blank panel front covers
used in cabinet.
Figure 3.1 Air Duct Baffle and Blank Panel Front Cover
- 38 -