Honeywell Super Tradeline Q674F Скачать руководство пользователя страница 2

60-1147-4

2

Fig. 1—Installation of Q674 Subbase on outlet box.

M925

VERTICAL 
OUTLET
BOX

ADAPTER
RING

SUBBASE

COVER 
PLATE

MOUNTING
SCREWS (2)

MOUNTING
SCREWS (2)

1

SUBBASE

MOUNTING
SCREWS (2)

HORIZONTAL
OUTLET
BOX

1

2

2

1   NOT INCLUDED WITH UNIT.

2   ACCESSORY PARTS AVAILABLE (193121A).

Fig. 2—Installation of Q674 Subbase on wall.

WIRES THROUGH
WALL OPENING

WALL 

WALL
ANCHORS
(2)

SUBBASE

MOUNTING
HOLES

MOUNTING
SCREWS (2)

M926

Fig. 3—Subbase components and leveling
procedure.

SPIRIT LEVEL

MOUNTING HOLES (2)

M927

TOP MOUNTING HOLES (2)

WIRING
TERMINAL

THERMOSTAT
CABLE OPENING

TO SPRING FINGER CONTACTS 
ON THE THERMOSTAT
(UP TO 12)

POST (2) FOR
MOUNTING
THERMOSTAT

LOCATION

Install the thermostat about 5 ft [1.5 m] above the floor in

an area with good air circulation at average temperature.

Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

MOUNTING THE SUBBASE

The thermostat subbase can be mounted on a vertical

outlet box, horizontal outlet box or directly on the wall.

1. If you must mount the subbase on a vertical outlet box,

order 193121A Adapter Assembly (Fig. 1). The as-sembly
includes an adapter ring, two screws and a cover plate to cover
marks on the wall. Install the ring and cover plate on the
vertical outlet box.

For a wall installation, hold subbase in position and mark

holes for anchors (Fig. 2). Obtain wall anchors locally. Take
care that the wires do not fall back into the wall opening. Set
aside subbase. Drill four 3/16 in. [4.8 mm] holes and gently
tap anchors into the holes until flush with the wall.

2. Pull wires through the cover plate (if used) and subbase

cable opening (Fig. 3).

3. Secure the cover plate (if used) and subbase with the

screws provided. Do not fully tighten the subbase screws.

4. Level the subbase using a spirit level, as shown in  Fig.

3, and firmly tighten the subbase mounting screws. The
subbase mounting holes provide for minor out-of-level ad-
justments.

IMPORTANT: An incorrectly leveled subbase will cause

the temperature control to deviate from set point.

WIRING THE SUBBASE

IMPORTANT: Use 18-gauge color-coded thermostat cable

for proper wiring.

Disconnect power supply before beginning installation to

prevent electrical shock or equipment damage.

All wiring must comply with local electrical codes and

ordinances. Follow equipment manufacturer wiring instruc-
tions when available. To wire subbase, proceed as follows:

1. Connect the system wires to the subbase as shown in

Figs. 5-7. A letter code located near each terminal is for
identification. The terminal barrier permits straight or con-
ventional wraparound wiring connection (Fig. 4).

2. Firmly tighten each terminal screw.
3. Fit wires as close as possible to the subbase. Push

excess wire back into the hole.

4. Plug hole with nonflammable insulation to prevent

drafts from affecting the thermostat.

MOUNTING THE THERMOSTAT

1. Remove the thermostat cover by pulling the bottom

edge of the cover outward and away from the base until it
snaps free of the mounting slots.

NOTE: The cover is hinged at the top and must be re-moved

by pulling outward at the bottom.

Содержание Super Tradeline Q674F

Страница 1: ...sedamagetosubbasethreads may result 4 Do not short across coil terminals on the relay This may burn out the thermostat heat anticipator IMPORTANT Thermostats are calibrated at the factory using subbases mounted at true level An inaccurately leveled subbase will cause thermostat control devia tion Operation On a two heat thermostat the two stages of heat make sequentially as the temperature drops M...

Страница 2: ...tain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill four 3 16 in 4 8 mm holes and gently tap anchors into the holes until flush with the wall 2 Pullwiresthroughthecoverplate ifused andsubbase cable opening Fig 3 3 Secure the cover plate if used and subbase with the screws provided Do not fully tighten the subbase screws 4 Levelthesubbas...

Страница 3: ...nsert is com pletelyseatedinrecessedarea Letsetpointscalepopback and set levers to desired positions FOR STRAIGHT INSERTION STRIP 5 16 in 8 mm FOR WRAPAROUND STRIP 7 16 in 11 mm SUBBASE TERMINAL SCREW M928 BARRIER Fig 5 Internal schematic and typical wiring diagram for T874N and Q674C M1860 G R W2 X L1 HOT L2 AUTO SYSTEM SWITCH AUTO ON FAN SWITCH 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOA...

Страница 4: ...ITCH EM HT HEAT OFF COOL H1 ANTICIPATOR H1 H2 H2 ANTICIPATOR 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M3686 FALL R RISE L C1 HEAT RELAY 3 EM HT RELAY CONTACT OUTDOOR THERMOSTAT AUTO ON FAN SWITCH X W3 OPTIONAL COMPRESSOR FAILURE DEVICE DEFROST RELAY REVERSING VALVE EM HT RELAY CONTACT HIGH PRESSURE SWITCH HEAT RELAY 1 HEAT RELAY 2 AUTO FALL C0 C1 ANTICIPATOR ...

Страница 5: ...rmostat base and note the spring fingers that engage the subbase contacts Make sure the spring fingersarenotbentflat Flatfingerspreventproperelectrical contact with the subbase 5 Set the second stage heat anticipation indicator to match the current rating of the controlled equipment See Heat Anticipator Setting section The first stage heat antici pator and the cooling anticipator are nonadjustable...

Страница 6: ... COOLING SET POINT LEVER THERMOMETER WHEN PROVIDED FAN SWITCH SYSTEM SWITCH OPTIONAL LED ENUNCIATION XXX XXXX XXXX XXXX XXX XXXX The T874N has separate heating and cooling set point levers the T874R has one set point lever for heating and cooling Move the heating and cooling set point levers Fig 10 to the desired comfort positions The minimum differen tialbetweenheatingandcoolingsetpointis3 F 2 C ...

Страница 7: ...h to AUTO In this position fan operation is controlled by the heating or cooling system control circuit Calibration THERMOSTAT T874Thermostatsareaccuratelycalibratedatthefactory They do not have provision for field calibration THERMOMETER The thermometer in your thermostat has been accurately calibrated at the factory The thermometer should need adjustment only if it has been dropped or shifted du...

Страница 8: ...ited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 1147 4 S M Rev 5 93 Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 www honeywell com yourhome ...

Отзывы: