STT850
Temperature Transmitter User’s Manual
Page 29
S1 Cal Lo
Corr
(HART only)
<Return>
Do S1 Cal Lo
Executing this selection corrects the Input 1
Calibration Low Point based on the input
measurement.
The current live value of the Input 1 Sensor is
shown on this display so the user can easily
see the effect of the correction.
Press
to enter
menu selection
Scroll to Do Cal
Press
to initiate
S1 Cal Hi
Corr
(HART only)
<Return>
Do S1 Cal Hi
Executing this selection corrects the Input 1
Calibration High Point based on the input
measurement.
The current live value of the Input 1 Sensor is
shown on this display so the user can easily
see the effect of the correction.
Press
to enter
menu selection
Scroll to Do Cal
Press
to initiate
S2 Cal Lo
Corr
(Dual Inputs
only)
(HART only)
<Return>
Do S2 Cal Lo
Executing this selection corrects the Input 2
Calibration Low Point based on the input
measurement.
The current live value of the Input 2 sensor is
shown on this display so the user can easily
see the effect of the correction.
Press
to enter
menu selection
Scroll to Do Cal
Press
to initiate
S2 Cal Hi
Corr
(Dual Inputs
only)
(HART only)
<Return>
Do S2 Cal Hi
Executing this selection corrects the Input 2
Calibration High Point based on the input
measurement.
The current live value of the Input 2 sensor is
shown on this display so the user can easily
see the effect of the correction.
Press
to enter
menu selection
Scroll to Do Cal
Press
to initiate
Reset Cal 1
Corr
(HART only)
<Return>
Reset S1
Corr
Executing this selection resets the Sensor 1 and
calibrations back to Factory values.
Press
to enter
menu selection
Scroll to Reset
Cals
Press
to initiate
Reset Cal 2
Corr
(Dual Inputs
only)
(HART only)
<Return>
Reset S2
Corr
Executing this selection resets the Sensor 2
calibrations back to Factory values.
Press
to enter
menu selection
Scroll to Reset
Corrects
Press
to initiate
LRV Correct
(DE only)
<Return>
Do LRV
Correct
Executing this selection corrects the LRV based
on the input pressure.
The current live value of the primary pressure
input is shown on this display so the user can
easily see the effect of the LRV correction.
Press
to enter
menu selection
Scroll to Do LRV
Correct
Press
to initiate
URV Correct
(DE only)
<Return>
Do URV
Correct
Executing this selection corrects the URV based
on the input pressure.
The current live value of the primary pressure
input is shown on this display so the user can
easily see the effect of the URV correction.
Press
to enter
menu selection
Scroll to Do URV
Correct
Press
to initiate
Содержание STT850 SMARTLINE
Страница 65: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 55 This page is left blank intentionally ...
Страница 75: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 65 ...
Страница 76: ...Page 66 STT850 Temperature Transmitter User s Manual Revision 3 ...
Страница 77: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 67 ...
Страница 84: ...Page 74 STT850 Temperature Transmitter User s Manual Revision 3 A 6 Control Drawing ...
Страница 85: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 75 ...
Страница 86: ...Page 76 STT850 Temperature Transmitter User s Manual Revision 3 ...
Страница 87: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 77 ...
Страница 88: ...Page 78 STT850 Temperature Transmitter User s Manual Revision 3 ...
Страница 89: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 79 ...