OPERATOR MANUAL // SECTION 1 

TECHNICAL DESCRIPTION 

 

HONEYWELL 

Other Specifications: 

Housing: 

Explosion-Proof, Copper-free Aluminum (< 0.4%) with powder 
coated finish, or Optional 316 Stainless Steel, NEMA type 3 and 
type 4, tamper-resistant with integral dual ¾ inch NPT conduit 
openings.

 

Marking: 

Class I, Div. 1 & 2, Groups B, C, & D 
Class II, Div. 1 & 2, Groups E, F, & G 
Class III  

Class I Zone 1 AEx d IIC 

 

 

Ex d IIC; Ex tb IIIC

 

Temperature:

  Operation: 

-40 to +85

°

C (-40 to +185º F)  

Storage

:

 

-55 to 105

°

C

 

Humidity range: 

10% to 90% (RH), non-condensing 

 

NOTE

: The supply connection wiring shall be rated at least  

10°C above the rated service temperature (95°C for T4 applications  
and 85°C for T5 applications).  See Figures 8 and 9 on Page 17 of this 
Insruction Manual.  
 

Weight:

 

Aluminum housing is approximately 3.8 lbs.   
Stainless Steel is approximately 8.9 lbs 

Dimensions:

  4.81 inches diameter by 4.40 inches high 

LED Visual Indicators: 

 

Powered Detector: 

Dual LEDs blink every 10 seconds 

 

Fault Declared: 

One LED turns ON solid until the fault is cured 

 

Re-calibrate when: 

Both LEDs flash ON and OFF rapidly 

 

Fire Declared: 

Both LEDs ON solid (one LED blinks during first  
few seconds) 

Содержание SS4-A HART

Страница 1: ...nd Operating Manual Multi Spectrum Digital Electro Optical Fire Detector Model SS4 AS AS2 For Special Applications Optimized for Hydrogen Silane Methanol Ethanol and Methane Stand Alone Relay Mode or 4 20 mA Output Option ...

Страница 2: ...ptical Path Integrity CM1 CM1 A DartLogic FireLogic Fire Signature Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Fire Sentry Corporation Fire Sentry Corp FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5X FS6 FS6X FS7 FS7X FS8 FS8X FS9 FS9X FS10X FS10X FS11 FS11X FS12 FS12X FS14 FS14X FS15 FS15X FS16 FS16X FS17 FS17X FS18 FS18X FS19 F...

Страница 3: ...this bookset REFERENCE INTERNAL Identifies an additional source of information within this bookset Indicates a situation which if not avoided may result in equipment or work data on the system being damaged or lost or may result in the inability to properly operate the process CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may als...

Страница 4: ... Supply Considerations 16 2 2 Installation Procedure 16 2 2 1 Configuring and Wiring Detectors 16 2 2 2 Removing Detector From Its Enclosure 16 2 2 3 Configuring the Detector Module 16 2 2 4 Wiring the Detector Module 17 2 2 5 Wiring the SS4 AS AS2 Detector for 4 or 20 mA Current Mode Operation Optional 18 2 2 6 Wiring the Detector Relays 19 2 2 7 Replacing the Detector Module in the Enclosure 19 ...

Страница 5: ...ed Environment Part No DASA1 P 27 5 2 PC Software Kit 2029 INTERFACE KIT 27 5 3 4 20 mA Option MA420 4 27 5 4 Detector Mounts SM2 or SM4 27 5 5 Test Lamp FT2045 or FT 2145 27 SECTION 6 DETECTOR LABEL DRAWINGS 28 INDEX 29 Read and understand this manual before installing or operating equipment ...

Страница 6: ...etectors have been manufactured in compliance with the requirements of the ISO 9002 standard and have been approved by California State Fire Marshal CSFM Factory Mutual FM Canadian Standards CSA CENELEC approval by FM Approvals Ltd Certification Service in compliance with the ATEX Directive ...

Страница 7: ...e sensors and lens These UV IR and VIS Fire Detectors have false alarm immunity and alarm range between 15 and 60 feet for a one square foot heptane gasoline kerosene or isopropyl alcohol pan flame with a 120 degree 60 degrees from the axis conical field of view Additional optimization for hydrogen assures a less than 5 second response to a 10 inch hydrogen flame at 15 ft Their microprocessor base...

Страница 8: ...5 C Humidity range 10 to 90 RH non condensing NOTE The supply connection wiring shall be rated at least 10 C above the rated service temperature 95 C for T4 applications and 85 C for T5 applications See Figures 8 and 9 on Page 17 of this Insruction Manual Weight Aluminum housing is approximately 3 8 lbs Stainless Steel is approximately 8 9 lbs Dimensions 4 81 inches diameter by 4 40 inches high LE...

Страница 9: ...tural Gas and Hydrogen gas among others 1 1 3 Detector Locations For unobstructed performance considering Detector locations in application areas avoid sources other than fire which may cause false alarms such as operations utilizing welding or gas torch equipment high power sources of EMI or RFI or artificial lighting pointed directly at the Detector Locations experiencing strong mechanical or ac...

Страница 10: ...d Alone mode compared to FS2000 System operation NOTE The Fault relay is not available when the Detector is wired to the FS2000 System 1 3 FS2000 System Operation For FS2000 System operation the Model SS4 AS AS2 Fire and Fault signals are sent digitally to the FS2000 System Controller using the four wire FS2000 FireBus The FireBus provides 24 Volt DC power for the Detector and RS 485 digital commu...

Страница 11: ...nt Once the FirePic data is stored the second LED will remain on For this version the fire alarm LEDs turn on and remain on until power to the unit is cycled turned off and on again If the Detector has a Fault it de energizes the Fault relay and turns one 1 LED on the LED will not light if the Fault is a No Power Fault If the Fault condition such as a Low Voltage Fault is eliminated the Detector w...

Страница 12: ... sensitivity setting for these types of fires Hydrogen 10 ten inch fire height at a distance of 15 ft with the Detector sensitivity setting of 15 ft Ethanol One square foot pan fire at a distance of 15 ft with the Detector sensitivity setting of 15 ft Methane Natural Gas 30 Thirty inch fire height using a 3 8 orifice at a distance of 15 ft with the Detector sensitivity setting of 15 ft Methanol On...

Страница 13: ... for special applications The configuration of the Detector is set from a DIP switches located on the middle circuit board of the Detector Module The DIP switch settings for each configuration are listed in Table 2 These configurable options include 1 Fire Verify Relay The Verify Relay may be disabled or enabled with several Verify Time settings It also may be set to act as another Fire Relay The ...

Страница 14: ... Red LEDs will turn off after 10 seconds 3 Test Period This setting pertains to the Through the Lens test period which may be set to 6 or to 30 minutes The 6 minute period may be required in applications where the lens is frequently obscured The Factory setting is 30 minutes NOTE Utilization of the 6 minute period may adversely affect the source tube service life 4 IR Only Enable Disable The IR on...

Страница 15: ... the protective Self test grill or when removing the enclosure cover 1 6 3 Manual Testing For manual testing the SS4 AS AS2 Detector may be exposed to an actual industry standard open flame or to a Test Lamp simulating a fire It is mandatory to use the Honeywell Analytics handheld UV IR Test Lamp Model No FT 2045 or FT 2145 with SS4 Fire Detectors The FT 2045 and FT 2145 Test Lamps are housed in a...

Страница 16: ...g all necessary measures to prevent the effect of electrostatic discharge ESD 2 1 2 Conduit Installation When planning the conduit follow these recommendations 1 If only one of the two 3 4 inch NPT conduit openings on the Model SS4 AS AS2 Detector enclosure is used seal the unused opening with a threaded plug and approved sealing material 2 In areas where moisture may accumulate install an approve...

Страница 17: ...e enclosure After the configuration settings and wiring connections have been completed the module should soon be re installed in the enclosure to avoid contamination from the environment NOTE Avoid touching the Detector sensors at the front of the Detector module If touched accidentally they should be cleaned per instructions of Section 3 2 2 2 2 Removing Detector From Its Enclosure a With electr...

Страница 18: ...nterface used only for downloading the FirePic from the Detector s non volatile memory or for viewing the Tri Mode Plot It is recommended to wire pins 2 and 3 to a separate junction box and properly identify them for future use A color coded multi connector shielded UL rated cable with 18 to 24 gauge wire is recommended for connecting to J1 or J2 The following color coding is suggested as a guidel...

Страница 19: ... the analog output of an SS4 AS AS2 make the following connections 24 V DC J2 pin 4 24 V DC RTN J2 pin 1 4 20 mA output J5 pin 4 4 20 mA RTN J1 pin 1 The fire Alarm and fault relays of the Detector equipped with the MA420 4 Module are not usable However the Detector s Verify Relay may still be used as a separate Fire Alarm output Refer to Table 2 Configuration DIP Switch Settings to set DIP switch...

Страница 20: ...Detector sensors and windowed cover per instructions of Section 3 2 c Securely screw down the metal enclosure top windowed cover and tighten the Allen head tamper proof screw 2 3 Enclosure Installation optional 2 3 1 Installing the Detector on the Swivel Mount SM2 or SS Extra Duty SM4 Swivel Mount a Select fasteners for the swivel mounting such that they will secure it to the type of material at t...

Страница 21: ...OPERATOR MANUAL SECTION 2 INSTALLATION HONEYWELL 20 4 86 4 26 2 95 2 00 0 295 Dia 4 7 approx Figure 4 Model SM2 Swivel Mount Figure 5 Model SM4 Stainless Steel Swivel Mount ...

Страница 22: ...PERATOR MANUAL SECTION 2 INSTALLATION HONEYWELL 21 2 09 4 66 1 10 0 67 4 38 2 40 3 4 NPT 1 50 Figure 6 Model SS4 AS AS2 Detector Enclosure Side View Figure 7 Model SS4 AS AS2 Detector Enclosure Rear View ...

Страница 23: ...d measure the voltage between Pins 1 and 4 of the power connector J1 or J2 If none or very low voltage is measured the user should check the wiring and the power supply e Detector Fault The Detector faults if its Optical Sensors fail the automatic built in through the lens test In this case one LED is on until the fault is corrected The user should first clean both inside and outside of the lens t...

Страница 24: ... to clean the enclosure window Oil degrades the performance of UV Detectors Occasionally the use of a solvent such as alcohol is acceptable No disassembly of the Detector is required DO NOT USE SILICONE BASED OR COMMERCIAL WINDOW CLEANING PRODUCTS THESE WILL DEGRADE THE MODEL SS4 AS AS2 DETECTOR PERFORMANCE 3 3 Personnel Training Troubleshooting of the Model SS4 AS AS2 Detector should be performed...

Страница 25: ...ule If the Model SS4 AS AS2 Module must be shipped back to the factory for repair it MUST be packed in static protective material If not available the Module should be carefully wrapped with aluminum foil An RMA Return Material Authorization is required for all returns to the factory Contact Honeywell Analytics Customer Service or your Distributor for an RMA number before shipping a unit back to t...

Страница 26: ... 4 Power 24 Volts DC J2 DETECTOR POWER OUT PIN 1 DC Return 2 RS 485 Connection to an optional interface unit for viewing FirePic and TriMode Plot 3 RS 485 Connection to an optional interface unit for viewing FirePic and TriMode Plot 4 Power 24 Volts DC J4 FIRE RELAY PIN 1 Fire Relay Common 2 Fire Relay Normally Closed 3 Fire Relay Common 4 Fire Relay Normally Open J5 FAULT RELAY Energized J6 FIRE ...

Страница 27: ...sabled then the Fire Relay s will de energize approximately 10 seconds after it energizes The SS4 A2 Factory setting is Non Latching closed Latching mode If Verify is enabled then when the Verify Relay energizes it will remain energized until the Detector is reset If Verify is disabled then when the Fire Relay energizes it will remain energized until the Detector is reset The SS4 A Factory setting...

Страница 28: ...e 4 20 mA module is by Factory Mutual FM recognized device to be used with all approved SS4 type Detectors Honeywell Analytics is required by FM to install this device at the factory and certifies this option along with the Detector Refer to Section 2 2 5 for system wiring details NOTE Converting Field units of the SS4 Stand alone relay type to the 4 20 mA version requires the unit be returned to ...

Страница 29: ...mA T4 T5 T6 LB 6093 045 SS4 0 020 Al 1100 Hl4 Black White 75 40C to 85C 40C to 75C 40C to 60C LB 6093 046 SS4 0 020 316 Stainless Steel Polished Black 75 40C to 85C 40C to 75C 40C to 60C LB 6093 047 SS4 0 020 Al 1100 Hl4 Black White 75 40C to 85C 40C to 75C 40C to 60C LB 6093 048 SS4 0 020 316 Stainless Steel Polished Black 75 40C to 85C 40C to 75C 40C to 60C ...

Страница 30: ...lf Checking 22 Detector Repair 24 ESD 15 FireBus 9 FireBus Wiring 15 Grounding 15 Installation 15 Conduit 15 Detector 16 Enclosure 19 Precautions 15 Procedure 16 Static Damage 15 Junction Box 15 Layout Planning 15 Maintenance 22 Optional Accessories 27 Personnel Qualified 23 Power 16 Relay Fault 25 Fire 25 Removing Modules 16 Stand Alone 9 Static Damage 15 Swivel Mount 19 Test Lamp 27 Test Source ...

Страница 31: ...e commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such product to the full extent such may be disclaimed by law THIS WARRANTY DOES NOT COVER 1 Defects or damage resulting from use of the Product s in other than its normal and customary manner 2 Defects or damage from misuse accident or neg...

Страница 32: ...ience Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Email analytics ap honeywell com Internet These Honeywell websites may be of interest to Industry Solution customers Honeywell Organization URL Corporate www honeywell com Honeywell Analytics www honeywellanalytics com Telephone Contact us by telephone at these numbers Organization Phone Number Americas Honeywell Analytics Inc 1 800 5...

Страница 33: ...1998M0912 Rev A July 2014 2014 Honeywell International Inc ...

Отзывы: