background image

 

OPERATOR MANUAL // SECTION 1:  FAMILIARIZATION 

 

HONEYWELL 

 

1.3 FS2000 

System 

Operation 

For FS2000 System operation, the Detector’s Fire and Fault signals are 
sent digitally to the FS2000 System Controller using the four wire FS2000 
FireBus. The FireBus provides the 24 Volts DC power for the Detector and 
RS-485 digital communication (Refer to Honeywell Analytics document 
MN0003: "FS2000 FIRE EARLY WARNING SYSTEM - INSTALLATION and 
OPERATIONS GUIDE"). For special remote alarm applications, users may 
also connect directly to the Detector’s Fire alarm relay.  

 

NOTE

:  When the Model SS2 Detector is connected to the FS2000 

System using FireBus communication, the Controller 

automatically

 

de-energizes the Detector’s Fault relay. 

1.4 Overview 

1.4.1 

Model SS2 Detector Status Indications 

The Model SS2 Multi-Spectrum Optical Fire/Flame Detectors are 
microprocessor-based devices, which see ultraviolet (UV), visible (VIS), 
and infrared (IR) spectral regions. The Detector's logic processor is 
capable of quick response to fires while virtually eliminating false alarms. 
The Model SS2 Detector has a 120° field-of-view. 

There are two (2) LEDs on the Model SS2 Detector for indication of the 
Detector status. During Normal Operation both LEDs will blink every 10 
seconds. 

If a Model SS2 Detector has a Fault, it 

de-energizes

 the Fault relay and 

turns one (1) LED on. (The LED will not light if the Fault is a “No Power 
Fault”). If the Fault condition, such as a “Low Voltage Fault”, is eliminated, 
the Detector will automatically return to Normal Operation. 

Faults caused by Excessive Input Voltage or temperatures outside the 
operating temperature range require factory re-certification. Both LEDs 
rapidly blinking (with frequency about 2 Hz) indicate faults requiring re-
certification.  

If a Model SS2 Detector alarms to a fire, it 

energizes

 the Fire relay and 

turns on both LEDs in the following sequence. One LED is turned on 
immediately and the second LED will rapidly blink for several seconds 
indicating that the Detector's FirePic is being permanently stored in the 
Detector's solid-state memory. (FirePic is the several seconds of Detector 
data, which precede an alarm event.) 

1.4.2 Detection 

Range 

The detection range of the detector is 60 feet to an industrial standard of 
one square foot gasoline pan fire within 5 seconds.  

1.4.3 Field-of-View 

The Detector incorporates a minimum 120-degree conical Field of View. 
The fire emissions received by the Detector diminish at extreme edges of 

Содержание SS2-A

Страница 1: ...Installation Guide and Operating Manual Multi Spectrum Digital Electro Optical Fire Detectors Models SS2 A SS2 AN SS2 AH and SS2 AM Stand Alone Mode ...

Страница 2: ...ptical Path Integrity CM1 CM1 A DartLogic FireLogic Fire Signature Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Fire Sentry Corporation Fire Sentry Corp FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5X FS6 FS6X FS7 FS7X FS8 FS8X FS9 FS9X FS10X FS10X FS11 FS11X FS12 FS12X FS14 FS14X FS15 FS15X FS16 FS16X FS17 FS17X FS18 FS18X FS19 F...

Страница 3: ...d or lo to properly o ON Indicates n which if no r moderate in ainst unsafe ON Symbol o the product m tion The sym d information OR MANUAL S his documen fies informat n n which if no or work dat ost or may r operate the s a potential ot avoided m njury It may practices on the equip manual for a mbol appear n in the manu SYMBOL DEFINI nt to denote tion that requ ot avoided m a on the sys result in ...

Страница 4: ...9 2 1 4 Power Supply Considerations 9 2 2 Enclosure Installation Optional 10 2 2 1 Swivel Mount SM2 10 2 2 2 Install Conduit If not already installed 10 Figure 2 Model SS2 Detector with SM2 Swivel Mount 10 2 3 Wiring Detectors 11 Figure 3 Model SS2 Detector Enclosure Side View 11 Figure 4 Model SS2 Detector Enclosure Back View 12 Figure 5 Models SS2 A SS2 AN SS2 AH and SS2 AM 13 SECTION 3 MAINTENA...

Страница 5: ...one d IIC Ex tb Read and operating al Fire Detec equirements te Fire Mars al FM ndards CSA proval by FM e with the AT Div 1 2 roups E F 1 AEx d IIC IIIC T135 C d understan g equipmen O tors have be of the ISO 9 shal CSFM A M Approvals TEX Directiv Groups A B G C nd this manu t OPERATOR MA een manufac 9001 standar s Ltd Certif ve B C D ual before in ANUAL APPRO tured in rd and have ication Serv nst...

Страница 6: ...g UV and IR energy for munitions and air bag industries The Detector is housed in a Class I Div 1 Explosion Proof enclosure For more information refer to corresponding specification sheets There are operational advantages when the Detector is connected to an FS2000 Controller and FireBus The Detector also has flexibility to be re configured in the field It is simple to install and operate due to b...

Страница 7: ...del SS2 Detector for indication of the Detector status During Normal Operation both LEDs will blink every 10 seconds If a Model SS2 Detector has a Fault it de energizes the Fault relay and turns one 1 LED on The LED will not light if the Fault is a No Power Fault If the Fault condition such as a Low Voltage Fault is eliminated the Detector will automatically return to Normal Operation Faults cause...

Страница 8: ...t after periodic maintenance or after lens contamination has been identified 1 5 2 Automatic Testing The Model SS2 Detectors contain an internal source for self testing For testing the Model SS2 Detectors end to end for both optical path and window cleanliness use a Honeywell Analytics Model FT 2045 Test Lamp 1 5 3 Manual Testing For manual testing the Detector may be exposed to an actual industry...

Страница 9: ...5 Test Lamps are housed in an Explosion proof enclosure powered by internal rechargeable batteries and designed for indoor and outdoor use For additional information on the Test Lamp refer to Honeywell Analytics Specification SP0242 for the FT 2045 or 1505 008A for the FT 2145 ...

Страница 10: ...n approved conduit trap or drain 3 For applications requiring a Class I Div 1 Explosion Proof rating install a seal within 6 inches of the enclosure 4 Consult the manufacturer for dimensional information on the flameproof joint specifications 2 1 3 Wiring Recommendations Install a junction box near each Detector location Wire each Detector to the junction box Use screw down terminal strips inside ...

Страница 11: ...outside contours of the mounting ears on the Detector enclosure and the ends of the bracket will match The large diameter of the threaded insert should face the enclosure d Screw the enclosure bracket assembly onto the ball or swivel stud Turn the Detector until the stud bottoms against the enclosure Do not tighten While holding the enclosure tighten the jam nut against the bracket e While holding...

Страница 12: ...ed wrist s pply connect d service tem plications S ual ot touch the tector modul of Section 3 9 4 6 osure Side V OPERATOR MA move its mod odule in the rds while han trap tion wiring sh mperature 9 See Figures detector ele es If touche 2 6 6 1 5 View ANUAL SECTI dule from the enclosure ndling Model hall be rated 95 C for T4 a 6 and 7 on P ements on th ed accidenta 1 1 0 5 0 ON 2 INSTALL e enclosure...

Страница 13: ...OPERATOR MANUAL SECTION 2 INSTALLATION HONEYWELL 12 Figure 4 Model SS2 Detector Enclosure Back View ...

Страница 14: ...OPERATOR MANUAL SECTION 2 INSTALLATION HONEYWELL 13 Figure 5 Models SS2 A SS2 AN SS2 AH and SS2 AM ...

Страница 15: ... Connect the 24 volt D C Power Supply wires to the J1 connector and firmly tighten down the two slotted screws with a small screwdriver DO NOT CONNECT ANY WIRES TO J1 Pin 2 or J1 Pin 3 Do NOT over tighten to prevent stripping or breaking See Figure 4 above Pin 1 Pin 2 Pin 3 Pin 4 Black Green or Blue White or Yellow Red Ground NOT USED NOT USED Power 3 WIRE THE DETECTOR FIRE RELAY All Models a Inse...

Страница 16: ... module back over the three metal standoffs and screw it down with the three chrome plated screws into the standoffs b If necessary clean the detectors and windowed cover according to the instructions in Section 3 2 c Screw down the metal enclosure top windowed cover until secure and tighten the allen head tamper proof screw ...

Страница 17: ...del SS2 Dete permanent d e a module w Module must cked in static available ca ATOR MANUAL OUBLESH ntenance mu serving stand erate on safe er supply ma tages may b or death ma s ector module damage due without adeq be shipped c protected m arefully wrap SECTION 3 HOOTING st be perform dard safety p e 24 Volts D y operate on e present du ay result if pe es and their to electrosta quate ground back t...

Страница 18: ...d off g Fault The r self checkin ATOR MANUAL sures and 2 Detector sh e schedule cient For ex truck filling eaning sched S2 Detectors or the Dete or each time ment l free cloth to ance of UV D s acceptable ILICONE BA NING PROD MODEL SS E rostatic haza Detectors Fault or Trou ollowing are D Detector will on is above ation to corre ll Fault if one rrected Retu ltage Fault T it is too high ect Both LE...

Страница 19: ...er Ser e shipping a ATOR MANUAL Detector M AN AH an eptible to pe SD DO NOT Allen head s wed cover o NOT blink f cover and s ree slot head odels use ca t board e sliding it a from the fem sure to note t connect the orrectly align offs Re insta touch the s n as instructe losure top w en head tam the factory f eable parts ipped back t ve material le with alum for all return rvice Departm unit back t...

Страница 20: ...USED Do not connect anything to this Pin 4 Power 24 Volts D C J2 FAULT RELAY J2 FIRE RELAY 2 SS2 A AN AM AML AH SS2 AMD AMDL AHD PIN PIN 1 Fault Relay Common 1 Fire Relay 2 Common 2 Fault Relay Normally Closed 2 Fire Relay 2 Normally Open 3 Fault Relay Common 3 Fire Relay 2 Common 4 Fault Relay Normally Open 4 Fire Relay 2 Normally Closed J3 FIRE RELAY PIN 1 Fire Relay Common 2 Fire Relay Normally...

Страница 21: ...d IIC Hazardous Locations ATEX IECEx CertificationClass I Zone 1 Ex db IIC T4 T6 and Ex tb IIIC T4 T6 ATEX Certification FM14ATEX0058X IECEx Certification FMG 14 0027X Ex db IIC T6 T4 Gb Ex tb IIIC T135 C Db IP66 II 2 G Ex db IIC T6 T4 Gb II 2 Ex tb IIIC T135 C IP66 IEC 60067 0 2011 IEC 60079 1 2014 IEC 60079 31 2013 IEC 60529 2013 EN 60079 0 2012 EN 60079 1 2014 EN 60079 31 2014 EN 60529 A2 2013 ...

Страница 22: ...f View 6 FireBus 6 FireBus Wiring 9 FireLogic 6 Flame Detector See Detector 6 Grounding 9 Installation 9 Conduit 9 Detector 11 Enclosure 10 Precautions 9 Static Damage 9 Layout Planning 9 Maintenance 15 Multi Spectrum See Detector 6 Optical Fire Detector See Detector 6 Personnel Qualified 15 Power 9 Relay FAULT 13 18 FIRE 13 18 Removing Modules 13 SS2 See Detector 6 SS2 A 13 SS2 AH 13 SS2 AM 13 SS...

Страница 23: ...e commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such product to the full extent such may be disclaimed by law THIS WARRANTY DOES NOT COVER 1 Defects or damage resulting from use of the Product s in other than its normal and customary manner 2 Defects or damage from misuse accident or neg...

Страница 24: ...ience Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Email analytics ap honeywell com Internet These Honeywell websites may be of interest to Industry Solution customers Honeywell Organization URL Corporate www honeywell com Honeywell Analytics www honeywellanalytics com Telephone Contact us by telephone at these numbers Organization Phone Number Americas Honeywell Analytics Inc 1 800 5...

Страница 25: ...1998M0908 Rev C September 2015 2014 Honeywell International Inc ...

Отзывы: