INSTALLATION INSTRUCTIONS

Put Bar Code Here

62-0310-04

Spyder

®

 BACnet

®

Programmable Controllers

 

PRODUCT DESCRIPTION

The PUB and PVB controllers are part of the Spyder family. 

These controllers are BACnet MS/TP network devices 

designed to control HVAC equipment. These controllers 

provide many options and advanced system features that 

allow state-of-the-art commercial building control. Each 

controller is programmable and configurable through software.

These controllers are for use in VAV (Variable Air Volume), 

Unitary, and advanced HVAC applications. Each controller has 

flexible, universal inputs for external sensors, digital inputs, 

and a combination of analog and digital Triac outputs. All the 

models are described in Table 1. The photo to the left is the 

model PVB6436AS, which includes the actuator.

Table 1. Controller configurations.

Each controller communicates via an EIA-485 BACnet MS/TP network communications network, capable of baud rates between 

9.6 and 115.2 kilobits.
Controllers are field-mountable to either a panel or a DIN rail. 

SPECIFICATIONS

General Specifications

Rated Voltage: 20–30 Vac; 50/60 Hz

Power Consumption: 

100 VA for controller and all connected loads (including the 

actuator on models models PVL0000AS, PVL4022AS, 

and PVL6436AS).

Controller Only Load: 5 VA maximum; models PUB1012S, 

PUB4024S, PUB6438S, PVB4024NS, and PVB6438NS.

Controller and Actuator Load: 9 VA maximum; models 

PVL0000AS, PVL4022AS, and PVL6436AS.

External Sensors Power Output: 20 Vdc ±10% @ 75 mA max-

imum.

VAV Operating & Storage Temperature Ambient Rating (mod-

els PVB0000AS, PVB4022AS, PVB4024NS, PVB6436AS, 

and PVB6438NS).:

Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)

Unitary Operating & Storage Temperature Ambient Rating 

(models PUB1012S, PUB4024S, and PUB6438S.):

Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)

Relative Humidity: 5% to 95% non-condensing

LED: Provides status for normal operation, controller down-

load process, alarms, manual mode, and error conditions

Controller

Model

Programmable

Type

Universal

Inputs

(UI)

Digital

Inputs

(DI)

Analog

Outputs

(AO)

Digital

Outputs

(DO)

Velocity

Pressure

Sensor

(Microbridge)

Series 60

Floating

Actuator

PUB1012S

Unitary

1

a

0

1

2

NO

NO

PUB4024S

Unitary

4

a

0

2

4

NO

NO

PUB6438S

Unitary

6

4

3

8

NO

NO

PVB000AS

VAV

0

0

0

0

YES

YES

PVB4022AS

VAV

4

a

0

2

2

YES

YES

PVB4024NS

VAV

4

a

0

2

4

YES

NO

PVB6436AS

VAV

6

4

3

6

YES

YES

PVB6438NS

VAV

6

4

3

8

YES

NO

Содержание Spyder BACnet PUB1012S

Страница 1: ...cations Rated Voltage 20 30 Vac 50 60 Hz Power Consumption 100 VA for controller and all connected loads including the actuator on models models PVL0000AS PVL4022AS and PVL6436AS Controller Only Load 5 VA maximum models PUB1012S PUB4024S PUB6438S PVB4024NS and PVB6438NS Controller and Actuator Load 9 VA maximum models PVL0000AS PVL4022AS and PVL6436AS External Sensors Power Output 20 Vdc 10 75 mA ...

Страница 2: ...es to fully close on page 3 to begin the installation Mount Actuator onto Damper Shaft PVB0000AS PVB4022AS and PVB6436AS PVB0000AS PVB4022AS and PVB6436AS controllers include the direct coupled actuator with Declutch mechanism which is shipped hard wired to the controller The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb in 5 Nm torque 90 degree stroke and 90 second ti...

Страница 3: ...degrees Adjust the two mechanical end limit set screws to provide the desired amount of rotation Adjust the two set screws closer together to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 26 5 31 lb in 3 0 3 5 Nm torque d Using the Declutch button rotate the universal shaft adapter fully clockwise e Mount the actuator to the VAV damper box and shaf...

Страница 4: ...NTATION M33229 8 9 32 211 1 15 16 49 6 9 32 159 3 16 4 5 PANEL MOUNTING HOLE 4X 27 32 21 4 1 8 105 6 1 4 159 5 7 8 149 DEPTH IS 2 1 4 57 1 1 1 1 1 1 1 1 1 1 2 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 1 0 9 2 3 4 5 6 7 1 1 1 1 1 1 1 1 1 2 3 4 5 6 7 8 0 9 2 2 2 2 2 2 2 2 2 3 3 1 2 3 4 5 6 7 8 0 9 3 3 3 3 3 3 3 3 4 5 3 4 146 10 5 16 262 NOTE CONTROLLER CAN BE MOUNTED IN ANY ...

Страница 5: ...mm outside diameter with a 0 040 in 1 mm wall thickness plenum rated 1219 FR 94V 2 tubing Always use a fresh cut on the end of the tubing that connects to the air flow pickups and the restrictor ports on the controller Connect the high pressure or upstream tube to the plastic restrictor port labeled and the low pressure or down stream tube to the restrictor port labeled See labeling in Fig 9 When ...

Страница 6: ...or all power and earth ground wiring Screw type terminal blocks are designed to accept up to one 14 AWG 2 0 sq mm conductor or up to two 18 AWG 1 0 sq mm conductors More than two wires that are 18 AWG 2 0 sq mm can be con nected with a wire nut Include a pigtail with this wire group and attach the pigtail to the terminal block IMPORTANT Connect terminal 2 the 24 Vac common 24 VAC COM terminal to e...

Страница 7: ...led the MAC address would be 85 1 4 16 64 85 Setting the Device Instance Number The Device Instance Number must be unique across the entire BACnet system network because it is used to uniquely identify the BACnet devices It may be used to conveniently identify the BACnet device from other devices during installation The Spyder BACnet Controllers Device Instance Number is automatically set when it ...

Страница 8: ...erminal blocks 4 Remove the old controller and actuator assembly from its mounting Loosen the two bolts on the actuator clamp to release the actuator from the shaft Remove the controller s mounting screws Gently pull the controller and actuator assembly straight out until the assembly is clear of the actuator shaft AO 1 COM AO 2 AO 3 COM UI 1 COM UI 2 UI 3 COM UI 4 UI 5 COM UI 6 DI 1 DI 2 COM DI 3...

Страница 9: ...the bottom flex connectors see Fig 8 on page 5 5 Mount the new controller See Installation on page 2 6 Reconnect the two air flow pickup tubes to the pressure sensor See Piping PVB0000AS PVB4022AS PVB4024NS PVB6436AS and PVB6438NS on page 4 7 Replace the terminal blocks Insert each terminal block onto its alignment pins Press straight down to firmly seat it Repeat for each terminal block 8 Restore...

Страница 10: ...SPYDER BACNET PROGRAMMABLE CONTROLLERS 62 0310 04 10 ...

Страница 11: ...SPYDER BACNET PROGRAMMABLE CONTROLLERS 11 62 0310 04 ...

Страница 12: ... Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 0310 04 S B Rev 12 11 Printed in United States ...

Отзывы: