background image

SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS 

Table 1. Port Identification. 

SP970A Pressure 

Regulator 

SP970A Minimum Position  SP970B  SP970C, D 

SP92 

SP93 

Main 

Pilot 

√ 

√ 

Branch 

Exhaust 

√ 

√ 

√ 

Calibration 

All SP970A and C models are calibrated at 8 psi (55 kPa) 

when the calibration mark (center punch) on the shaft is 
centered at the bottom of the molded V. To calibrate, 

align the center punch mark on the shaft with the bottom 
of the molded V groove on the plastic surrounding shaft. 

See Fig. 3. This setting equals 8 psi (55 kPa). Secure the 
knob to the shaft at the proper scale setting. The knob 

should be pointing to 8 psi (55 kPa). See Fig. 4. 

All SP970B and D models are calibrated at 8 psi (55 kPa) 
when the knob is set at 50 percent. 

The large range device can be field recalibrated to other 

end points with the same span from 0 psi (0 kPa) lower 
limit to 26 psi (179 kPa) upper limit. The small range 

device can be field recalibrated to other end points with 
the same span from 0 psi (0 kPa) lower limit to 16 psi 

(110 kPa) upper limit. 

Checkout and Test for All Models 

1.

  

With main air connected, insert a pressure gage 
into the branch line. 

2.

  

Check pressures equivalent to knob settings. 

3.

  

When minimum position is used, attach input and 

increase pilot pressure. 

4.

  

Verify correct operation. 

ENGINEERING DATA 

Specifications 

Models: 

- SP970A: A bleed type pressure regulator. 

- SP970B: A bleed type pressure regulator mounted 

on a sheet metal panel. 

- SP970C: A bleed type pressure regulator with a 

dead ended pilot chamber for minimum pressure 

applications. 

- SP970D: A bleed type pressure regulator with a 

dead ended pilot chamber for minimum pressure 
applications mounted on a sheet metal panel. 

Selectable Spans for psi (kPa): 

See Table 2. 

Table 2. Selectable Spans. 

Model 

Knob Rotation

188 

244 

300 

Small span 

5 (34) 

6.5 (45) 

8 (55) 

Large span 

10 (69) 

13 (90) 

16 (110) 

The setpoint knob normally rotates 188 degrees. Two 
breakaway stops on the knob allow rotation of 244 and 

300 degrees. 

Operating Pressure (Switch and Pilot) Range: 

Normal Main: 18 psi (124 kPa)

 

Branch: 3 to 15 psi (21 to 103 kPa)

 

Pilot: 3 to 15 psi (21 to 103 kPa)

 

Maximum Safe Air Pressure: 

30 psi (207 kPa) 

Ambient Operating Limits: 

Temperature: 0 to 140°F (-18 to 60°C)

 

Relative Humidity : 5 to 95%

 

Air Handling Capacity: 

SP970A, B: above minimum position, device feeding 

pilot determines capacity. Below minimum position, 
air capacity is 0.022 scfm (10 ml/s) 

SP970C, D: 0.022 scfm (10 ml/s) 

Air Consumption: 

0.022 scfm (10 ml/s) 

Scaleplate: 

All models ship with a 0 to 100 scaleplate 

(including knob and locknuts). 

Construction: 

Molded plastic with neoprene diaphragm, 

steel spring and shaft. 

Operation 

SP970A and B: Three Port Switches 

PRESSURE REGULATOR OPERATION 

Main line air flows through the restriction into the 

branchline chamber and out the nozzle. Branchline 
pressure increases until it is strong enough to compress 

the spring and lift the diaphragm off the nozzle. Airflow 
out the nozzle is controlled by the balance between the 

branchline pressure and spring force. 

MINIMUM POSITION OPERATION 

An external signal is connected to port 4 (exhaust port). 
When the external signal is greater than the spring load, 

the nozzle opens and branchline pressure is the same as 
the external signal. When the external signal is less than 

the spring load, branchline pressure is controlled as 
described in the previous paragraph. See Fig. 6. 

SP970A,B 

4  

SP970A,B 

BRANCH

BRANCH 

PILOT 

MAIN 

PILOT 

MAIN 

C4298 

Fig. 6. SP970A/B operation. 

3

  

95-7237EF 

Содержание SP907B

Страница 1: ...inimum Position Pressure Regulators provide regulated pressure to a Figs 1 and 2 show approximate dimensions SP970A 3 1 2 89 SP970C 3 7 8 98 0 8 0 60 40 2 0 10 0 2 1 2 63 1 1 2 38 7 8 22 2 1 4 57 1 7 8 48 C4857 FRONT VIEW SIDE VIEW Fig 1 SP970A and C dimensions in in mm 3 1 2 89 0 8 0 60 40 2 0 10 0 3 1 4 83 2 1 16 62 1 9 16 40 1 25 7 8 4 1 2 114 FRONT VIEW 22 SIDE VIEW C4858 Fig 2 SP970B and D di...

Страница 2: ...nished with SP970A and C Do not mount the knob during installation Refer to the Calibration section of this docu ment Surface Mounting Use the mounting bracket as a template and secure mounting bracket to surface See Fig 4 Screws are not provided Piping All connections are sharp barb 5 32 in 4 mm O D polyethylene tubing CAUTION Equipment Damage Hazard To prevent damage to the sharp barb connection...

Страница 3: ... chamber for minimum pressure applications mounted on a sheet metal panel Selectable Spans for psi kPa See Table 2 Table 2 Selectable Spans Model Knob Rotationa 188 244 300 Small span 5 34 6 5 45 8 55 Large span 10 69 13 90 16 110 a The setpoint knob normally rotates 188 degrees Two breakaway stops on the knob allow rotation of 244 and 300 degrees Operating Pressure Switch and Pilot Range Normal M...

Страница 4: ...es the damper The three port SP970A B is also used with a controller for automatic damper positioning with minimum position See Fig 8B When the external signal is less than the knob setting the spring maintains the branchline pressure as previously described When the external signal rises above the knob setting air from the signal flows directly to the branch During steady state conditions the ext...

Страница 5: ...Les Fig 1 et 2 donnent l encombrement approximatif des servomoteurs pneumatiques de registres Ils servent à appareils SP970A 89 3 1 2 SP970C 98 3 7 8 0 8 0 60 40 2 0 10 0 63 2 1 2 38 1 1 2 22 7 8 57 2 1 4 48 1 7 8 CF4857 VUE DE FACE VUE DE PROFIL Fig 1 Encombrement des SP970A et C en mm po CF4858 89 3 1 2 0 8 0 60 40 2 0 10 0 83 3 1 4 62 2 1 16 40 1 9 16 25 1 22 7 8 114 4 1 2 VUE DE FACE VUE DE PR...

Страница 6: ...t de l installation Consulter la section Étalon nage de la présente notice technique Montage en surface Utiliser le support de montage comme gabarit puis le fixer à la surface Voir la Fig 4 Les vis ne sont pas fournies Tuyaux Tous les raccords sont effectués avec des tuyaux à crans en polyéthylène de 4 mm 5 32 po de diam ext MISE EN GARDE Risque de dommage matériel Ne pas couper ni tirer les canal...

Страница 7: ...ure en kPa psi voir le Tableau 2 Tableau 2 Choix d intervalles Gamme de pression de service commutation et pilote Canal princ normale 124 kPa 18 psi Canal sec 21 à 103 kPa 3 à 15 psi Pilote 21 à 103 kPa 3 à 15 psi Pression d air admissible maximale 207 kPa 30 psi Limites ambiantes de service Température 18 à 60 C 0 à 140 F Humidité relative 5 à 95 Débit d air SP970A B au dessus de la position mini...

Страница 8: ...e la pression dans la canalisation secondaire et le registre se ferme Les appareils SP970A et B à trois orifices sont aussi utilisés avec des régulateurs pour positionner automatiquement un registre en position minimale Voir la Fig 8B Lorsque la pression du signal extérieur est inférieure à celle du réglage du bouton le ressort maintient la pression dans la canalisation secondaire comme il est déc...

Отзывы: