Parameter Descriptions
Honeywell
10
10.9 FAULT AUTORESTART PARAMETERS (CONTROL PANEL: MENU
PAR -> P10)
10.2 A
UTOMATIC
RESTART
,
TRIAL
TIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first autorestart. If the number of faults occurring
during the trial time exceeds three, the fault state becomes active. Otherwise
the fault is cleared after the trial time has elapsed and the next fault starts the
trial time count again. See Figure 10.15.
If a single fault remains during the trial time, a fault state is true.
Figure 10.15: Automatic restart
Fault trigger
Motor stop signal
Motor start signal
Supervision
Wait time
par.10.1
Restart 1
Restart 2
Trial time
par.10.2
Fault active
RESET/
Fault reset
Autoreset function: (Trials = 2)
Wait time
par.10.1
Wait time
par.10.1