50
Parameters
Honeywell
9
9.8 DIGITAL AND ANALOGUE OUTPUTS(CONTROL PANEL: MENU PAR-
>P7)
Code
Parameter
Min
Max
Unit Default
ID
Selections
Only in API FULL
P7.1
0
11
2
313
0
= Not used
1
= Ready
2
= Run
3
= Fault
4
= Fault Inverted
5
= Alarm
6
= Reversed
7
= At Speed
8
= Motor Regulator Active
9
= FBControlWord.B13
10
= FBControlWord.B14
11
= FBControlWord.B15
In all API versions
P7.2
Relay output 2
content
0
11
3
314
As parameter 7.1
Only in API FULL
P7.3
Digital output 1
content
0
11
1
312
As parameter 7.1
P7.4
0
4
1
307
0
= Not in use
1
= Output freq. (0-f
max
)
2
= Output current (0-I
nMo-
tor
)
3
= Torque (0-Nominal
torque)
4
= PI controller output
P7.5
0
1
1
310
0
= 0 mA
1
= 4 mA
Only in API Limited
P7.6
Relay 2 invert
0
1
0
489
1
= Relay 2 inverted
Table 9.8: Digital and analogue outputs