Configuration & Operation
Item
Operation
Display
Reverse
Setting
• Press “SELECT” to choose “REVERSE”.
• Press key
S
“ST” value will switch between 0 and 1:
0
Æ
output1 in normal mode, 2—10Vdc or 4-20mA
1
Æ
output1 in reversing mode, 10—2Vdc or 20-4mA
• Press key
T
“ST” value will switch between 1 and 0.
• Press, “ENTER” button to save setting value.
Display
Setting
• Press “SELECT” to choose “DISPLAY”.
• Press key
S
“ST” value will switch between 0 and 1.
0: Normal Mode, output1 is decimal value signal
1: Percentage Mode, output1 is percent value (2Vdc or 4mA--0% 10Vdc or 20mA--100%).
• Press key
T
“ST” value will be 1 down.
• Press, “ENTER” button to save setting value.
• In percentage mode the screen will show “AO” and “%”.
Manual
Setting
• Press “SELECT” to choose “MANUAL”.
• Press key
S
“ST” value switches between 0 and 1: 0
Æ
MANUAL OFF
1
Æ
MANUAL ON
• Press key
T
“ST” value switches between 1 and 0.
• Press, “ENTER” button to save setting value.
• If manual on, PV screen will show “AO” and “%”, ST screen shows measured value
• If manual on, press key
S
1 time, the displayed value will be 1% up. Hold the key 2 seconds up; the value
increases continuously until reaches 100%.
• If manual on, press key
T
, the value will be 1% down. Hold the key 2 seconds up; the value decreases
continuously until reaches 0%.
• After 90 minutes manual on operation, the controller will return to manual off mode automatically.
F1 Setting
• Press key “SELECT” to choose “F1”.
• Press key
S
1 time “ST” value will be 0.1 second up; the range is from 0.1 to 60 seconds. Hold the key 2
seconds up; the value increases 0.1 second until reaches 60.
• Press the key
T
everything is reverse.
• Press “ENTER” to save.
• This value setting shows how long the output1 will update the output value.