![Honeywell SmartLine SLN 700 82 Series Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/honeywell/smartline-sln-700-82-series/smartline-sln-700-82-series_user-manual_154963018.webp)
Page 10
SLN 700 SmartLine NCR Level Transmitter User’s Manual
Revision 1
Nozzle installations
In the case of a material with good reflection properties (high dielectric constant, DK), the
sensor may be mounted on a nozzle. The background subtraction ("virtual echo learning")
feature can further reduce false echoes from nozzle openings.
shows detail of the size limitations of the nozzle.
Figure 3-5: nozzle specifications diagram
Table 3-2: nozzle specifications table
Nozzle Diameter
d
(
mm
)
Maximum Nozzle Height h
(
mm
)
83A
82A 82B
83B 83C
82C 82D
83D 83E
87A 87B
87C 87D
40
150
NA
NA
NA
50
150
150
NA
NA
80
200
200
200
NA
100
300
300
300
300
125
400
400
400
400
150
500
500
500
500