background image

 

Wiring Connections and Power Up   

Make sure that the following power supply constraint is met.  

1000

/

22

*

3

.

2

,

,

loop

Min

Txer

Min

S

R

V

V

V

  

 
Where 

ohms

in 

 

resistance

 

loop

 

is

ls

at termina

 

tage

supply vol

 

Minimum

Transmitte

 

is

 

tage

supply vol

 

minimum

 

is

,

,

loop

Min

Txer

Min

S

R

V

V

 

 

 

Wiring Options

 

There are 3 wiring options for connecting Remote Indicator to the loop.  
See 

Figure 9,

 

Figure 9 

and 

Figure 8

 for the wiring connections. 

 

DE Devices 

In this mode, the Remote Indicator shall be connected as shown in 

Figure 8. 

 

 

 

 

Figure 8: Remote Indicator connected to the negative loop wire 

 

Once the wiring is complete, power on the loop. The RMA device will take 6s (approx.) to 
turn on the display.   

 

Note

 

– The resistor “R” indicates (shown for representation only) the loop resistor which is 

needed for HART and DE communication and is typically provided by the user or control 
system.

 

 

 

Analog (4-20mA) Devices: 

Refer Figure 8 and 9 for  the Remote Indicator Connection on the Negative and positive 
side of the loop. 

 

Figure 9: Remote Indicator connected to the negative loop wire 

 

1. 

Remote Indicator installed as explosion proof in Class I, Division 1, Group A 
Hazardous (classified) locations in accordance with ANSI/NFPA 70, the US 
National Electrical Code, with 1/2 inch conduit do not require an explosion-proof 
seal for installation. If 3/4 inch conduit is used, a LISTED explosion proof seal must 
be installed in the conduit, within 18 inches (457.2 mm) of the Remote Indicator. 

 

Figure 10: Remote Indicator connected to the positive loop wire 

 

 

ATTENTION

  

For all wiring options, ensure that RMA chassis ground terminal is 
connected to earth ground.  
Connect the Loop Power shield to earth ground at the power supply 
end and not at RMA end. The shield shall be continuous from 
transmitter through RMA till the power supply

 

:

 

 

 

DEVICE CONFIGURATION 

Once the loop is powered, the RMA will be turned ON with a scrolling message “SmartLine” 
appearing on the display. 
 
For  DE  devices,  the  RMA  is  autoconfigured.  For  any  DE  configuration  change  in  the 
transmitter, database upload shall be performed to reflect the changes in RMA. 
To configure the device, open the front cover of the device. 
 
Use the ‘Menu’ and ‘Enter’ key buttons on display to configure the device. See table below 
for configuration parameters. 
  
Use the ‘Menu’ button to navigate the configuration parameters. Use the ‘Enter’ button to 
select and set a parameter value.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1. 

Temperature: °C, °F, °R, K, mV, Ohm 

Pressure Engineering Units: inH2O@39ºF, mH2O@4ºC, cmH2O@4ºC, Torr, 
mmH2O@68ºF, ftH2O@68ºF, inH2O@68ºF, inH2O@60ºF, atm, Pa, kPa, MPa, gf/cm2, 
kgf/cm2, psi, mbar, bar, inHg@0ºC, mmHg@0ºC, mmH2O@4ºC.

 

SNO      MENU 

Parameters 

Description 

SEL PV 

Select Process Variable (temperature, 

pressure, loop out, % out) 

UNIT 

Select Engineering Unit 
Units are visible as per PV selection 

ENTLRV  

Enter Lower Range Value  
(Numeric Value) 

ENTURV 

Enter Upper Range Value 
(Numeric Value) 

CAL Lo 

Input Calibration Low Point. See manual for 

details of calibration 

(Applicable in Analog Mode only) 

CAL Hi 

Input Calibration High Point. See manual for 

details of calibration. 

(Applicable in Analog Mode only) 

B UNIT 

Select Engineering Base Unit of Transmitter 
Base Units visible as per PV selection 
(Applicable in Analog Mode only) 

CNTRST 

Set LCD Contrast 

RMA DG 

RMA Diagnostic Messages. See manual for 

details of diagnostic messages 

10 

FW VER 

Firmware Version 

 

EXIT 

EXIT Menu 

 

Appendix A. PRODUCT CERTIFICATIONS

 

 

A1  European Directive Information (CE Mark) 

 

 

 

 

Содержание SmartLine RMA801

Страница 1: ...perating in a 4 20 mA current loop The RMA801 is a DE Analog Remote Indicator which can be connected anywhere along the current loop For analog PV the RMA801 measures the loop current and displays the equivalent PV value on the display The RMA801 will autoconfigure when connected to Honeywell STT700 STT250 DE transmitters when a database upload is performed This document provides the information f...

Страница 2: ...a Remote indicator Figure 4 Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe 4 Wall Mount Option Refer Figure 5 Position the bracket on the mounting surface at the desired location and secure the bracket to the mounting surface using the appropriate hardware Wall mounting hardware requirements to be determined and supplied by the end user Figure 5 Remote Indicator Secured to a Wall M...

Страница 3: ...h ground Connect the Loop Power shield to earth ground at the power supply end and not at RMA end The shield shall be continuous from transmitter through RMA till the power supply DEVICE CONFIGURATION Once the loop is powered the RMA will be turned ON with a scrolling message SmartLine appearing on the display For DE devices the RMA is autoconfigured For any DE configuration change in the transmit...

Страница 4: ...to 85o C Enclosure Type IP66 IP67 ALL ALL STANDARDS EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 11 2012 EN 60079 31 2014 EN 60079 7 2015 D IECEx Flame proof Ex db IIC T6 T4 Gb Ex tb IIIC T 95o C Db Note 1 T6 50ºC to 65ºC T4 T5 50 ºC to 85ºC Intrinsically Safe Ex ia IIC T4 Ga Note 2 50o C to 70o C Non Incendive Ex ec IIC T4 Gc Note 1 50o C to 70o C Enclosure IP66 IP67 ALL ALL STANDARDS IEC 60...

Страница 5: ...LOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 Intrinsically Safe Divisions 1 Zone 1 and Zone 2 Environments WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT Explosion Proof Division 1 and Zone 1 Environments WARNING DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS ...

Страница 6: ...44 0 1202645583 FAX 44 0 1344 655554 Email Sales sc cp apps salespa62 honeywell com or TAC hfs tac support honeywell com AMERICAS Honeywell Process Solutions Phone 1 800 423 9883 or 1 215 641 3610 TAC hfs tac support honeywell com Sales 1 800 343 0228 Email Sales FP Sales Apps honeywell com Knowledge Base search engine http bit ly 2N5Vldi WARRANTY REMEDY Honeywell warrants goods of its manufacture...

Отзывы: