Honeywell SmartLine RMA3000-EU Скачать руководство пользователя страница 3

 

Revision 4 

Foundation Fieldbus RMA803 Remote Indicator User's Guide 

Page iii 

About This Document 

This guide provides the details of programming Honeywell RMA803 Remote Indicator for applications 
involving FOUNDATION Fieldbus protocol. For installation, wiring, and maintenance information, refer to 
the 

RMA803 Remote Indicator User Manual

The configuration of your Remote Indicator depends on the mode of operation and the options selected for it 
with respect to operating controls, displays and mechanical installation. 

An RMA803 Remote Indicator can be digitally integrated with: 

 

Experion PKS, you need to supplement the information in this document with the data and procedures in 
the Experion PDF Collection. 

Release Information 

 

Document Name 

Foundation Fieldbus RMA803 Remote Indicator 

User's Guide 

Document ID 

34-ST-25-51 

Release 
Number 

Publication Date 

1

st

  Release 

 

June 2014  

Ferrite core info added 

 

September 2014  

FM Approvals updated. Certs updated to include 801 

February 2019 

SAEx approval added 

March 2020 

 

 

References 

The following list identifies all documents that may be sources of reference for material discussed in this 
publication. 
 

Quick Start Installation Guide, 

# 34-ST-25-52 

HART/DE Option User Manual

, Document # 34-ST-25-40

 

Содержание SmartLine RMA3000-EU

Страница 1: ...Honeywell Process Solutions Foundation Fieldbus RMA803 Remote Indicator User s Guide 34 ST 25 51 Revision 4 March 2020 ...

Страница 2: ...se and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell PlantScape Experion PKS and TotalPlant are registered trademarks of Honeywell International Inc Ot...

Страница 3: ... RMA803 Remote Indicator can be digitally integrated with Experion PKS you need to supplement the information in this document with the data and procedures in the Experion PDF Collection Release Information Document Name Foundation Fieldbus RMA803 Remote Indicator User s Guide Document ID 34 ST 25 51 Release Number Publication Date 1st Release 1 June 2014 Ferrite core info added 2 September 2014 F...

Страница 4: ...ge or refer to the appropriate Honeywell Solution Support web site Honeywell Corporate www honeywellprocess com Honeywell Process Solutions https www honeywellprocess com remote meter assemblies Training Classes www honeywellprocess com en US training Telephone and Email Contacts Area Organization Phone Number United States and Canada Honeywell Inc 1 800 343 0228 Customer Service 1 800 423 9883 Gl...

Страница 5: ...AUTION symbol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual WARNING Indicates a potentially hazardous situation which if not avoided could result in serious injury or death WARNING symbol on the equipment refers the user to the product manual for additional information The symbol appears next to requi...

Страница 6: ... connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements Chassis Ground Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements ...

Страница 7: ...ty capable of performing one or more specific functions Examples include Remote Indicators actuators controllers operator interfaces DCS Distributed Control System DD Device Description Device Description Description of FBAPs within a device Files that describe the software objects in a device such as function blocks and parameters The DD binary are created by passing DD source files through a sta...

Страница 8: ...ich is responsible for keeping a link operational The LAS executes the link schedule circulates tokens distributes time messages and probes for new devices LRL Lower Range Limit LRV Lower Range Value Macrocycle The least common multiple of all the loop times on a given link mAdc Milliamperes Direct Current Manufacturer s Signal Processing A term used to describe signal processing in a device that ...

Страница 9: ...te Pu Static pressure at upstream point PV Process Variable PWA Printed Wiring Assembly RFI Radio Frequency Interference RMA Remote Meter Assembly RTD Resistance Temperature Detector Stack The software component that implement the Foundation Fieldbus communications protocol specifications including FMS FAS DLL SM and NM Status A coded value that qualifies dynamic variables parameters in function b...

Страница 10: ...bus communications can primarily only take place along an active communications path that consists of two VCR endpoints Virtual Field Device A logical grouping of user layer functions Function blocks are grouped into a VFD and system and network management are grouped into a VFD For example to establish communications between a transducer block and a function block a VCR must be defined at the tra...

Страница 11: ...erifying communication with the Remote Indicator 8 Identify the Remote Indicator 8 2 3 Establishing communication with host systems 9 Device Description DD 9 Enhanced Device Description EDD 9 Device Type Manager DTM 9 3 INSTALLATION AND STARTUP 11 3 1 Installation Site Evaluation 11 3 2 Display Installation Precautions 11 3 3 Mounting Remote Indicator 11 Summary 11 Mounting Dimensions 12 Bracket M...

Страница 12: ...ing the Resource block 35 RESTART 35 Execution 36 CYCLE TYPE 36 MEMORY 36 MAX NOTIFY 36 FEATURES 36 Reports 36 SOFT W LOCK and HARD W LOCK 37 Field Diagnostics 38 Parameter List 41 5 4 Diagnostic Transducer block 45 Execution 45 Parameter List 46 5 5 LCD Transducer block 48 Execution 48 Advanced Display 48 Parameters List 51 5 6 Proportional Integral Derivative PID block with auto tune 54 Executio...

Страница 13: ...Class 3 94 Recommendations 94 Downloading the File 95 7 5 Licensing for Function Blocks 96 8 RMA803 FF REMOTE INDICATOR TROUBLESHOOTING 97 8 1 Troubleshooting overview 97 Device status and faults 97 8 2 Troubleshooting the Remote Indicator 98 Device not visible on the network 98 Incorrect or non compatible tools 99 8 3 Troubleshooting blocks 100 Non functioning blocks 100 Troubleshooting block con...

Страница 14: ...ults 111 8 6 Understanding simulation mode 112 About simulation mode jumper 112 Setting simulation jumper 112 Enabling simulation mode 113 Simulation mode truth table 113 8 7 Understanding write protection 114 8 8 Critical Diagnostics Screens 114 Fault Conditions and Recommended Corrective Actions 114 9 PARTS LIST 115 9 1 Overview 115 APPENDIX A PRODUCT CERTIFICATIONS 118 10 INDEX 126 ...

Страница 15: ...ransducer block parameters 51 Table 19 PID Tuning parameters 57 Table 20 PID block parameters 59 Table 21 Input Selector block parameters 66 Table 22 Integrator block parameters 75 Table 23 Arithmetic block parameters 81 Table 24 Signal Characterizer block parameters 85 Table 25 MAO block parameters 88 Table 26 Resource block 100 Table 27 Diagnostics Transducer block 101 Table 28 LCD Transducer bl...

Страница 16: ...4 Figure 11 PID block schematic diagram 54 Figure 12 Input Selector block 64 Figure 13 Input Selector schematic diagram 65 Figure 14 Integrator Block 69 Figure 15 Two Rate Inputs 70 Figure 16 Arithmetic block 78 Figure 17 Arithmetic schematic diagram 79 Figure 18 Signal Characterizer Block 83 Figure 19 Signal characterizer curve 84 Figure 20 Multiple Analog Output block 87 Figure 21 Connecting the...

Страница 17: ...ser configurable rate The user can also step through the values on demand using the local pushbuttons LCD Display formats The RMA803 provides three user friendly formats including bar graph and trend The scale limits of the bar graph and trend are configured by the user to allow optimum visibility of the process value The trend format will plot the trend of the selected function block value The du...

Страница 18: ...rating Software Consists of Resource block AI block LCD Transducer block Diagnostic Transducer block and MAO Multiple Analog Output function block Additional Function Blocks Consists of PID block Signal Characterizer block Arithmetic block Input Selector block and Integrator block Refer to Section 7 5 for more details Note Additional Function blocks are available post liscensing ...

Страница 19: ...isplay screens with 3 formats are possible Large PV or PV with Bar Graph or PV with Trend Graph Configurable screen rotation timing 4 to 30 sec Ability to enable disable screen rotation Three button programming optional Advanced display languages East Asian EN CH JP Western EN GE FR IT SP RU TU Approvals See Appendix C for details ATEX CSA FM IECx NEPSI Mounting Brackets Pipe mounting and wall mou...

Страница 20: ...ator User s Guide Revision 4 1 3 RMA803 major assembly and electronic housing components The following illustrations depict the major assembly and electronic housing components Figure 1 RMA803 Major assemblies Figure 2 Electronic Housing components ...

Страница 21: ...ieldbus network It supports the following features Link master capability Supports the following standard function blocks apart from the Resource and Transducer blocks Input Selector block AI block Integrator block Signal Characterizer block PID with auto tune block Arithmetic block Multiple Analog Output Block Function block instantiation is supported by the following blocks Input Selector block ...

Страница 22: ...s that disclose the Remote Indicator compliance information Refer to Appendix A of this document for safety certification requirements and details 1 7 Display Options The RMA803 Foundation Fieldbus Remote Indicator has Advanced Display option Table 2 Available Display Characteristics Advanced Display 360 rotation in 90 increments Three 3 configurable screen formats with configurable rotation inter...

Страница 23: ...ysical location The device serial number is the PROM ID which is stamped on the Remote Indicator housing nameplate Verify connection with host computer to device On the operator interface check and make sure communications are established with the device on the Fieldbus network Verify or assign Device Tag and address Check that the Device Tag and node address are set If not assign the Device Tag a...

Страница 24: ...with the Remote Indicator This helps in getting the correct parameter names and its corresponding descriptions while viewing the device parameters Table 4 Remote Indicator parameters Parameter To verify Resource block DEV_TYPE That the Remote Indicator is of the proper device type For all the RMA803 Remote Indicators the value is 0005 Device Tag Physical device tag name of the Remote Indicator The...

Страница 25: ...r all standard function blocks and transducer blocks on a CD ROM The Fieldbus Foundation also provides this information on its website www fieldbus org Enhanced Device Description EDD There are two types of EDDs are available namely ff5 sy5 and ffo sym The ffo sym binary files are generated for the legacy hosts to load the device DD that is generated using latest tokenizer Few constructs like Imag...

Страница 26: ...Page 10 Foundation Fieldbus RMA803 Remote Indicator User s Guide Revision 4 This page is left blank intentionally ...

Страница 27: ...Process Parameters o Temperature o Maximum Pressure Rating 3 2 Display Installation Precautions Temperature extremes can affect display quality The display can go blank if the temperature is below 20 C however this is only a temporary condition The display will again be readable when temperatures return to within operable limits The display update rate may increase at cold temperature extremes but...

Страница 28: ...o mounting holes in the Remote Indicator with the two slots in the mounting bracket and assemble the 2 M8 hex cap screws 2 lockwashers and 2 flat washers provided Rotate Remote Indicator assembly to the desired position and torque the M8 hex cap screws to 27 0 Nm 20 0 Lb ft maximum Pipe Mount Option Refer to Figure 4 2 Position the bracket on a 2 inch 50 8 mm horizontal or vertical pipe and instal...

Страница 29: ...ignal and affords protection against lightning and static discharge An optional lightning terminal block can be installed in place of the non lightning terminal block for Remote Indicators that will be installed in an area that is highly susceptible to lightning strikes For this to be effective the instrument case must be connected to earth ground ATTENTION Wiring must comply with local codes regu...

Страница 30: ...l per 94 9EC the power supply has to include a voltage limiting device Voltage must be limited such that it does not exceed 9 to 32 V DC Consult the process design system documentation for specifics ATTENTION FF power Supply along with the Terminators has to be used Explosion Proof Conduit Seal WARNING When installed as explosion proof in a Division 1 Hazardous Location keep covers tight while the...

Страница 31: ...rocesses involved for Fieldbus device operation using the 3 button option 4 2 Three Button Operation The RMA803 optional three button interface provides a user interface and operation capability without opening the Remote Indicator Figure 6 shows the location of the three button option and the labels for each button Figure 6 Three Button Option ...

Страница 32: ...or activation When an item is selected for data entry or activation the cursor will call up a pop up to allow editing of the value No action is taken against a menu item until the button is pressed If a user presses the button to begin a data entry operation they must press another button within 10 seconds or the Remote Indicator firmware will assume that the user wants to abort the operation or h...

Страница 33: ...ric Value Editing a Numeric Value Editing of a numeric value is a digit by digit process starting with the left most digit 1 Press to begin the edit process 2 The Advanced Display will show the current value of the item in a pop up window in the middle of the screen 3 Press the or buttons to select the desired digit and then press to advance to the next digit to the right 4 After the last digit ha...

Страница 34: ... Contrast Rotation time and Rotation Enable are editable parameters Rest all are read only Information Display Elec Module Model Options For details go to the Information Menu table Table 8 Diagnostics Menu All Diagnostics menu items are Read Only Return Return to the Level 1 menu Critical Return Active Diags Shows the number of Critical Diagnostics that are currently active Elec Module OK FAULT F...

Страница 35: ...selected language Default English Read Only Rotation Time Time duration in seconds that each configured screen is shown before moving to the next screen Range 3 to 30 seconds Default 10 seconds Press to enter menu selection and to select number to enter and shift to next digit Rotation Enable Yes No Option Yes or No enables or disables the screen rotation Press to enter menu selection and to selec...

Страница 36: ...d Display Units Pressure inH2O inHg ftH2O mmH2O mmHg psi bar mbar gf cm2 kgf cm2 Pa kPa Torr atm inH2O inH2O mmH2O Temperature C F R K mV Ohm Volumetric Flow CFM gal min L min m3 h Mgal d gal h L h Mass Flow kg min kg h lb min lb h Miscellaneous mA pH Level m Shows the selected Display Units Read Only ...

Страница 37: ...inued ft cm in mm yd km mile Custom Units Shows the selected units Read Only Decimal None Shows the selected decimal value Read Only X X X XX X XXX Disp Low Limit Shows the selected low limit Read Only Disp High Limit Shows the selected high limit Custom Tag Shows the selected custom tag Read Only ...

Страница 38: ...que serial number of the Remote indicator Read only License Key License key to enable optional function block Write only The integrated circuits in the Remote Indicator PWA are vulnerable to damage by stray static discharges when removed from the Electronics Housing Minimize the possibility of static discharge damage when handling the PWA as follows Do not touch terminals connectors component lead...

Страница 39: ...uide Page 23 The following procedure outlines the steps for positioning the write protect and failsafe jumpers on the electronics module See Figure 7 for the locations of the failsafe and write protect jumpers Figure 7 Locating Simulation and Write Protect Jumpers ...

Страница 40: ...ly depress the two tabs on the sides of the Display Module and pull it off 4 If necessary unplug the interface connector from the Communication module Do not discard the connector Set the Failsafe Jumper top jumper to the desired position UP or DOWN If applicable re install the Display module as follows Orient the display as desired Install the Interface Connector in the Display module such that i...

Страница 41: ...ssentially all three formats provide the same information but with the following differences Bar Graph User Configurable 126 segment Bar Graph with range settings The Bar Graph displays the current value of the configured PV PV Trend User configurable display period from one hour to 24 hours The chart displays minimum maximum and average of the configured PV over the selected trend period Figure 8...

Страница 42: ... details concerning the Non Critical diagnostics M Maintenance Mode is active This indicator is set by the Experion DCS When this Mode is active a screen with the text Available for Maintenance will be inserted into the normal screen rotation to make it easy to identify Remote Indicators that are available for maintenance PV Value User Configurable This field has 7 characters Maximum allowable num...

Страница 43: ...f cm2 kgf cm2 Pa kPa Torr atm inH2O inH2O mmH2O Level m ft cm in mm yd km mile Temperature o C o F o R K mV ohm Mass Flow kg min kg h lb min lb h Volumetric Flow CFM gal min L min m3 h Mgal d gal h L h Miscellaneous mA pH Bar Graph The limits of the bar graph are user configurable for each screen Trend graph The limits of the trend graph are user configurable for each screen The amount of time vis...

Страница 44: ...mpatibility Experion Release DD Compatibility 430 Yes 410 4 Yes 400 4 CP3 Yes 311 3 Yes The steps in the following procedure are specific to Experion R410 only Step Action 1 From the Control builder main screen click Fieldbus Device Description Import OR Select File New Type Fieldbus Device 2 You can Import the DD using one of the following steps Choose Browse to locate the folder where you have s...

Страница 45: ...g dialog box appears Click OK 3 Type the Device Type Name and then click Save As only applicable if the same DD version is available and being imported 4 The following dialog box appears Click OK 5 The following dialog box appears Click OK ATTENTION The device type RMA803FF_0101_1 is used as an example ...

Страница 46: ...ou want to change the name in the destination column type the new name or if you want to use the default name click Finish The device is added on the FF link on the Project Assignment window A series of steps for commissioning the device has to be followed in each type of DCS 9 Right click the new device and then click Load 10 The following WARNING appears Click Continue 11 The following dialog bo...

Страница 47: ...ou have to create control strategies Control strategy A control strategy is an organized approach to define a specific process using detailed information to create control modules in an associated controlled environment configure function blocks to enable control applications and runs in a control software infrastructure To build a control strategy a Control Module CM must be created where functio...

Страница 48: ...rated whenever the BLOCK_ERR has an error bit set The types of block error for all the blocks are shown in Table 8 The following alarms are supported by each function block Block Alarms Table 12 Bit mapping of the BLOCK_ERR Block_ERR Bit Block Alarms Description 0 Other Least significant bit LSB NOTE It is not applicable to the Remote Indicator 1 Block Configuration error A feature in FEATURES_SEL...

Страница 49: ...ed to be saved to NV at the next NV write cycle but prevented the write due to power failure 11 Readback Check failed This indicates the readback of the actual continuous valve or other actuator position in transducer units has failed 12 Device needs maintenance now A diagnostic algorithm has found an invalid condition but the device is still able to operate and communicate The NV memory has reach...

Страница 50: ...rity of each alarm is set by the following parameters HI_PRI HI_HI_PRI DV_HI_PRI DV_LO_PRI LO_PRI LO_LO_PRI The following is the order of priority for alarms Table 13 Priority for Alarms Priority Description 0 To disable the triggered alarm the priority of an alarm condition is changed to 0 1 Alarm condition with a priority 1 is reported to the system but not reported as an event and alarm 2 Alarm...

Страница 51: ...esource The OOS mode stops all function block execution The Actual mode of the function blocks changes to OOS but the target mode does not change The AUTO mode allows normal operation of the resource Configuring the Resource block The Resource block supports scalar input only as HARD_TYPES This parameter is a read only bit string that indicates the types of hardware that are available for this res...

Страница 52: ...e These constants are used by each function block and are configurable values MAX NOTIFY The MAX_NOTIFY parameter value is the maximum number of alert reports that this resource can send without getting a confirmation and to control alert flooding adjust the LIM_NOTIFY parameter to a lower value If LIM_NOTIFY is set to zero no alerts are reported The CONFIRM_TIME parameter is the time for the reso...

Страница 53: ...t support hard write lock and have the associated FEATURE_SEL attribute enabled the parameter WRITE_LOCK is only an indicator of the state of write lock The writing to WRITE_LOCK is rejected by the device Software write lock To activate write lock the soft write lock supported bit in FEATURE_SEL must be set and then set the WRITE_LOCK to locked To deactivate write lock set the WRITE_LOCK to unlock...

Страница 54: ...evice or process characteristics Check Function Output signal temporarily invalid due to on going work on the device Failed Output signal invalid due to malfunction in the field device or its peripherals FAILED_ALARMS Failed alarms indicate a failure within a device that makes the device or some part of the device non operational This implies that the device needs repair and must be fixed immediat...

Страница 55: ...g and is not reported MAINT_PRI designates the alarming priority of the MAINT_ALM The default is 0 MAINT_ACTIVE parameter displays the alarms that are active MAINT_ALM parameter indicates that the device needs maintenance If the condition is ignored the device fails CHECK_ALARMS It indicates that the output signal is temporarily invalid due to on going work on the device CHECK_MAPPED parameter con...

Страница 56: ...arming priority of the OFFSPEC_ALM The default is 0 OFFSPEC_ACTIVE parameter displays the offspec alarms that are active OFFSPEC_ALM parameter indicates offspec alarms These conditions do not have a direct impact on the process or device integrity RECOMMENDED_ACTION The RECOMMENDED_ACTION parameter displays a text string that give a recommended course of action to take based on which type and whic...

Страница 57: ... It is a bit string so that multiple errors may be shown RS_STATE Indicates the State of the function block application state machine TEST_RW Read write test parameter is used only for conformance testing DD_RESOURCE String identifying the tag of the resource which contains the Device Description for the resource MANUFAC_ID Manufacturer identification number is used by an interface device to locat...

Страница 58: ...t promoted to an output block or a physical contact When Fault State condition is set output function blocks perform their FSTATE actions SET_FSTATE Allows the Fault State condition to be manually initiated by selecting Set CLR_FSTATE Writing a Clear to this parameter removes the device fault state if the field condition if any has cleared MAX_NOTIFY Maximum numbers of unconfirmed notify messages ...

Страница 59: ...signates the alarming priority of the MAINT_ALM The valid range is 0 15 FD_MAINT_MAP Mapped MAINT_ALM alarm conditions and corresponds bit for bit to the MAINT_ACTIVE A bit on means that the corresponding alarm condition is Mapped and is not detected A bit off means the corresponding alarm condition is disabled and is not detected FD_MAINT_MASK Mask of MAINT_ALM It corresponds to the bit of bit to...

Страница 60: ...ision number of the communications module MODEL_KEY The key number of RMA803 Remote Indicator Example RMA803 MOD_PART_1 First part of the Model number information MOD_PART_2 Second part of the Model number information MOD_PART_3 Third part of the Model number information MOD_PART_4 Fourth part of the Model number information HW_SIMULATE_JUM PER_STATE State of Hardware Simulation Jumper Enabled Dis...

Страница 61: ...tics The block is executed as follows Device Diagnostics Electronics Housing Temperature Diagnostics Electronics housing temperature is the temperature of the electronic housing unit and Electronics temperature value is its corresponding value Time in Service The amount of time the device is in operation and is shown in minutes Service Life The average service life of the device under ideal condit...

Страница 62: ... a bit string so that multiple errors may be shown UPDATE_EVT This alert is generated by any change to the static data BLOCK_ALM The BLOCK_ALM is used for all configuration hardware and connection failure or system problems in the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status attribute As soon as the Unreported st...

Страница 63: ... Fieldbus RMA803 Remote Indicator User s Guide Page 47 Attributes Supported Modes The block supports the following modes AUTO Automatic OOS Out of Service Alarm Types The block supports standard block alarms see section 5 2 ...

Страница 64: ... Bar Graph and PV Trend Essentially all three formats provide the same information but with the following differences PV It is a user configurable display and it shows the configured PV Bar Graph It is a user configurable 126 segment Bar Graph with range settings The Bar Graph displays the current value of the configured PV PV Trend It is a user configurable display period from one hour to 24 hour...

Страница 65: ...lock FF Parameter PID BLOCK PID SP PV OUT IN CAS_IN BKCAL_IN BKCAL_OUT RCAS_IN ROUT_IN RCAS_OUT ROUT_OUT FF_VAL TRK_VAL ARITHMETIC FUNCTION BLOCK OUT IN IN_LO IN_1 IN_2 IN_3 INTEGRATOR BLOCK OUT IN_1 IN_2 SIGNAL CHARACTERIZER BLOCK OUT_1 OUT_2 IN_1 IN_2 INPUT SELECTOR BLOCK OUT IN_1 IN_2 IN_3 IN_4 IN_5 ...

Страница 66: ...ion Fieldbus RMA803 Remote Indicator User s Guide Revision 4 Block FF Parameter IN_6 IN_7 IN_8 MULTIPLE ANALOG OUTPUT BLOCK IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 AI BLOCK PV OUT FIELD_VAL DIAGTB BLOCK EL_TEMP VALUE ...

Страница 67: ...in the Status attribute As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed DISP_SEQ_TIME Periodic rotation time of the display screens in seconds Range 3 30 sec LANGUAGE Language selection for the Display Supported Languages English French German Spanish Russian Italian Turkish Ch...

Страница 68: ...template Possible Values a PV Regular PV value is displayed b PV and Trend PV value followed by a Trend is shown on the display c PV and Bargraph PV value followed by a Bargraph is shown on the display d None Screen will not be seen The DISPLAY_TEMPLATE is present in all the eight screens DISPLAY_TEMPLATE_1 DISPLAY_TEMPLATE_2 DISPLAY_TEMPLATE_3 DISPLAY_TEMPLATE_4 DISPLAY_TEMPLATE_5 DISPLAY_TEMPLAT...

Страница 69: ... block supports the following modes AUTO Automatic OOS Out of Service Alarm Types The block supports standard block alarms see section 5 2 Note Additional Function blocks PID block Signal Characterizer block Arithmetic block Input Selector block and Integrator block are available only for a licensed version ...

Страница 70: ... control schemes and it is commonly used The PID function integrates the errors If there is difference in process time constants of a primary process and secondary process measurement then the block can be cascaded if required Auto tuning is a feature that tunes the PID constants as per the process automatically Figure 10 PID block Figure 11 PID block schematic diagram ...

Страница 71: ...scade control schemes are stable BYPASS can only be changed when the block mode is in MAN or OOS mode When BYPASS is set the value of SP in percent of range is passed directly to the target output and the value of OUT is used for BKCAL_OUT When the mode is changed to Cas the upstream block is requested to initialize to the value of OUT When a block is in Cas mode on the transition out of BYPASS th...

Страница 72: ... the tuning constant of the Proportional term 2 RESET is the tuning constant of the Integral 3 RATE is the tuning constant of the Derivative RATE is usually modified by a lag which is set at some fixed ratio higher than the rate time to create a rate gain There is no lag with the rate in this implementation 4 OUT_LAG is the fourth tuning constant used in the robust PID it adds roll off to the outp...

Страница 73: ...ues outside the following ranges Table 19 PID Tuning parameters Parameter Initial Value Minimum Value Maximum Value Comment PV_FTIME 0 0 200 Units seconds GAIN 0 004 250 GAIN_NLIN 0 004 250 RATE sec 0 32 Ts 7500 The value of ZERO is permitted to turn off rate action RESET sec INF 2 Ts 7500 The value of INF is permitted to turn off reset action Some versions of NI configurator program cannot set IN...

Страница 74: ...n Step control and is used for integrating process Auto tuning procedure There are nine parameters applicable for auto tuning AT_TYPE TUNING_CRITERIA TUNE_REQ ATI AT_MODE AT_ERR AT_GAIN AT_RESET and AT_RATE AT_Type There are two types of selections namely Disable and Cycle Tune When Disable is selected AT_MODE becomes inactive When Cycle Tune is selected AT_MODE becomes AT Ready TUNING_CRITERIA Th...

Страница 75: ...etpoint limiting and setpoint rate of change limiting OUT The block input value and status PV_SCALE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with PV OUT_SCALE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with OUT GRANT_DENY Options for controlling ...

Страница 76: ... and to pass limit status OUT_HI_LIM The maximum output value allowed OUT LO_LIM The minimum output value allowed BKCAL_HYS The amount the output value must change away from its output limit before limit status is turned off BKCAL_OUT The value and status required by the BKCAL_IN input of another block to prevent reset windup and to provide bump less transfer of closed loop control RCAS_IN Target ...

Страница 77: ... alarms in the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status parameter As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed ACK_OPTION Used to set auto acknowledgment of alarms ALARM_HYS The amount ...

Страница 78: ...figurable lag filter applied to calculated output value See OUT_LAG parameter Linear and non linear gain parameters are available ALGO_TYPE Configuration parameter specifies algorithm type which can be A B or C Type A equation where Proportional Integral and Derivative act on ERROR Type B equation where Proportional and Integral act on ERROR and Derivative acts on PV Type C equation where Integral...

Страница 79: ..._ERROR Auto Tune Error supports the following errors Abort Not ready OK and Run AT_GAIN Auto tuned Gain AT_RESET Auto tuned Reset AT_RATE Auto tuned Rate LICENSE_STATUS_ PID License status of the function block Attributes Supported Modes The block supports the following modes AUTO Automatic MAN Manual OOS Out of Service IMan Cas RCas ROut LO Alarm Types The block supports standard block alarms see...

Страница 80: ...rameter As a switch the block receives switching information from either the connected inputs or from an operator input The block supports signal status propagation The block is used to provide control input selection in the forward path only and hence no back calculation support is provided SELECTED indicates which input has been selected or the number of inputs selected by the algorithm The bloc...

Страница 81: ...ck The value of SELECTED is the number of the input with the lowest value If SELECT_TYPE is Maximum it transfers the highest value to the output of the block The value of SELECTED is the number of the input with the highest value If SELECT_TYPE is Middle if there are 3 or 4 values the highest and lowest value is discarded The average of the remaining two values is computed and the value is transfe...

Страница 82: ...ing so that multiple errors may be shown OUT The block output value and status OUT_RANGE High and low scale values engineering units code and number of digits to the right of the decimal point associated with OUT GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block Not used by device STATUS_OPTI ONS It helps to s...

Страница 83: ... is less than the value of MIN_GOOD then set the OUT status to Bad SELECTED The integer indicating the selected input number OP_SELECT An operator settable parameter to force a given input to be used UPDATE_EVT This alert is generated by any change to the static data BLOCK_ALM The block alarm is used for all configuration hardware connection failure or system problems in the block The cause of the...

Страница 84: ...ng normal operations the value and status of the selected input is shown by OUT If the number of inputs with Good status is fewer than MIN_GOOD then the output status is Bad The SELECTED output status is Good NC until the block is out of service The block supports two status option Uncertain as Good If the selected input status is Uncertain set the OUT status as Good Uncertain if in Manual mode If...

Страница 85: ... to calculate volume or mass variation in vessels or as an optimizing tool for flow ratio control The block does not support process alarms ATTENTION Alternatively IN_1 and IN_2 can be used as pulse inputs coming from other blocks The same general rules for integration applies for the accumulation of pulses Figure 14 Integrator Block Execution The basic function of the Integrator block is to integ...

Страница 86: ... the input option is Rate Each input needs a parameter to define the rate time unit IN_1 IN_2 The time unit can be selected in seconds minutes hours days The second analog input must be converted into the same unit as that of the first input IN_2 must be converted into the same units of IN_1 This can be done by using the parameter UNIT_CONV For example if IN_1 is in seconds and if IN_2 is in minut...

Страница 87: ...AL1 or PULSE_VAL2 as appropriate The result is the increment in engineering units of for example mass volume or energy per block execution Net Flow The Net Flow is calculated by considering the direction of flow The direction of the flow is calculated by selecting the parameters REV_FLOW and REV_FLOW2 When the status is set to True for any of these two parameters the direction of the flow for that...

Страница 88: ...he output becomes zero The integration starts as SP and increments are subtracted from the SP DN_DEM The output is calculated even beyond zero till the block is reset The integration starts from SP PERIODIC The integration is done for the assigned period specified in seconds in CLOCK_PER After that period the block is reset automatically DEMAND The integration is done positive or negative dependin...

Страница 89: ... 3 or 4 it starts from a value given by TOTAL_SP When the value of OUT is equal to or less than PRE_TRIP the discrete output OUT_PTRIP is set When the count reaches zero the discrete output OUT_TRIP is set OUT_PTRIP remains set When a reset occurs the comparisons that set OUT_PTRIP and OUT_TRIP are no longer True so they are cleared OUT_TRIP shall remain set for five seconds after an automatic res...

Страница 90: ...the input IN_1 IN_2 whose status is Bad is considered for integration INTEG_OPTS 0 Carry This option is used only for UP_AUTO and DN_AUTO kind of integrations only When this option is selected the residual value after the integration is added subtracted from the integral value in the next cycle of integration INTEG_OPTS 0 Add Zero if Bad When this option is selected if IN_1 IN_2 is bad the input v...

Страница 91: ...h totalization OUT The block output value and status OUT_RANGE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with OUT GRAND_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block not used by the device STATUS_OPTS It helps to select option for statu...

Страница 92: ...hen counting down N_RESET Counts the number of resets It cannot be written or reset PCT_INC Indicates the percentage of inputs with Good status compared to the ones with Bad or Uncertain and Bad status GOOD_LIMIT Sets the limit for PCT_INC Below this limit OUT receives the status Good UNCERTAIN_LIMIT Sets the limit for PCT_INC Below this limit OUT receives the status Uncertain OP_CMD_INT Operator ...

Страница 93: ...ts are added together and the resulting status is the worst of the two The option Add zero if Bad in INTEG_OPTS causes the net increment to be zero if its status is Bad The percentage of Bad or Uncertain and Bad counts can be determined by calculating the value of PCT_INCL from Rtotal and Atotal As Atotal is the sum of increments with Good and Bad status and Rtotal is the sum of increments with Ba...

Страница 94: ...ol path The block does not support process alarms The Arithmetic block supports the following functions Flow compensation linear Flow compensation square root Flow compensation approximate BTU flow Traditional Multiply Divide Average Traditional Summer Fourth order polynomial Simple HTG compensated level Fourth order Polynomial Based on PV Figure 16 Arithmetic block Execution The block has five in...

Страница 95: ...r the range of RANGE_LO to RANGE_HI The equation for PV follows 𝑃𝑃𝑃𝑃 𝑔𝑔 𝐼𝐼𝐼𝐼 1 𝑔𝑔 𝐼𝐼𝐼𝐼_𝐿𝐿𝐿𝐿 If the status of IN_LO is not usable and IN is usable and greater than RANGE_LO then g is set to one If the status of IN is unusable and IN_LO is usable and less than RANGE_HI then g is set to zero For three auxiliary inputs six constants are used and each input has a BIAS_IN_i and a GAIN_IN_i The output ha...

Страница 96: ...𝑡𝑡_2 𝑡𝑡_3 𝑓𝑓 f number of inputs used in computation unusable inputs are not used 7 Traditional Summer 𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 𝑃𝑃𝑃𝑃 𝑡𝑡_1 𝑡𝑡_2 𝑡𝑡_3 8 Fourth order polynomial All inputs except IN_LO not used are linked together 𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 PV 𝑡𝑡_1 2 𝑡𝑡_2 3 𝑡𝑡_3 4 9 Simple HTG compensated level where PV is the tank base pressure IN_1 is the top pressure IN_2 is the density correction pressure and GAIN is the height of ...

Страница 97: ... errors may be shown PV It calculates the proportions of IN and IN_LO to for PV OUT The analog output value and status PRE_OUT Displays what would be the OUT value if the mode is AUTO or lower PV_SCALE The high and low scale values the engineering units code and the number of digits to the right of the decimal point associated with the PV OUT_RANGE The high and low scale values engineering units c...

Страница 98: ... to calculate the output OUT_HI_LIM The maximum output value allowed OUT_LO_LIM The minimum output value allowed UPDATE_EVT This alert is generated by any changes to the static data BLOCK_ALM Used for all configuration hardware connection failure or system problem in the block The cause of the alert is entered in the subcode field The first active alarm sets the active status in the status paramet...

Страница 99: ... output To use the backward control path the block provides an option to swap the axes of the function Figure 18 Signal Characterizer Block The block calculates OUT_1 from IN_1 and OUT_2 from IN_2 using a curve given by the co ordinates x1 y1 x2 y2 x21 y21 Where x is the Input and y is the Output The x coordinates are given in engineering units of X_RANGE The y coordinates are given in engineering...

Страница 100: ...put is smaller than x1 and the output is at ym when the input is larger than xm Since the ends of the y curve act as limits the OUT status is shown when either limit is active Backward Control path A reverse function swaps the interpretation of IN_2 and OUT_2 that provides a way to do reverse calculation using the same curve If the parameter SWAP_2 is set to True the block provides IN_1 x and OUT_...

Страница 101: ...output value and status X_RANGE The display scaling of the variable corresponding to the x axis for display It has no effect on the block Y_RANGE The display scaling of the variable corresponding to the y axis for display It has no effect on the block GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block Not used ...

Страница 102: ...eached or the input is limited the appropriate limit must be indicated in the output sub status Limits shall be reversed if the curve slope is negative If SWAP_2 is set cascade initialization is controlled by the lower block When this block is in OOS mode the cascade to both the lower and upper blocks is broken by Bad status at the outputs When the block goes to AUTO mode the lower block can begin...

Страница 103: ...eter of MAO function block When the MAO function block is in LO mode all the inputs transferred to LCD Transducer Block transition to the fault state status Fault State Operation Operation in fault state status is defined by MO_OPTS MO_OPTS Definition Bit Name 0 Fault state to value 1 Used when the input 1 is in the fault state 1 Fault state to value 2 Used when the input 2 is in the fault state 2...

Страница 104: ...ion may be used in the host for sorting alarms etc MODE_BLK The actual target permitted and normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may take on Normal Most common mode for target BLOCK_ERR This parameter reflects the error status associated with the hardware or software components associated with a block It is...

Страница 105: ...A value transferred as input 6 to LCD Transducer Block during fault state condition Transition will occur if MO_OPT bit is enabled FSTATE_VAL7 A value transferred as input 7 to LCD Transducer Block during fault state condition Transition will occur if MO_OPT bit is enabled FSTATE_VAL8 A value transferred as input 8 to LCD Transducer Block during fault state condition Transition will occur if MO_OP...

Страница 106: ...ct control configurations where the above parameters are written continuously via a computer application for example or at rates greater than the NV_CYCLE_T interval This consideration helps to minimize the possibility of NVM wear out In the case of MODE this must not be a problem When users wish to provide set points to the PID block via a computer application users should use RCAS mode with its ...

Страница 107: ...ters After Instantiation the instantiated block must be loaded into the device and then the strategies can be created ATTENTION Note that ten blocks can be instantiated at a time For example you can instantiate 3 Input Selector and 3 Signal Characterizer block 1 PID Block and 3 Arithmetic block Block instantiation using Experion PKS The following are the steps for performing block instantiation us...

Страница 108: ...Schedules The RMA803 Remote Indicator does not require any specific maintenance at regularly scheduled intervals 7 3 Replacing the Local Display and Communication Electronic Assembly The Communication module includes a connector to the Display module This section includes the procedure to replace the Communication module The Remote Indicator does not have to be removed from service to replace the ...

Страница 109: ...rom the Electronics compartment 6 Carefully insert the Communication module into the Electronics compartment 7 Tighten the two Communication module retaining screws 8 Refer to the SmartLine User s Manual to change the FAILSAFE READ WRITE and SIM OFF SIM ON Fieldbus Only configuration settings 9 If applicable re install the Display module as follows a Orient the display as desired b Install the Int...

Страница 110: ... 3 only A class 3 firmware download is performed irrespective of whether the device is ON OFF process Class 3 When class 3 download is performed the device prepares for the download and goes out of the link as the memory of the device is re written with the new firmware After the restart of the device the device comes back to the link automatically However the device retains the following credenti...

Страница 111: ...sion ffd where Manufacturer ID is represented as six hexadecimal digits leading and trailing zeroes are included Device Family is represented as four hexadecimal digits leading and trailing zeroes are included For Multidomain devices Device Family is replaced by Multidomain Family Device Type is represented as four hexadecimal digits leading and trailing zeroes are included Leading 0 s is not supp...

Страница 112: ...al number of the device Device Type Fieldbus Remote Indicator Feature requires license Additional Function Block Part Number 50097037 501 The RDC generates and sends a License Key to customer Customer activates the license by writing License Key parameter present in Device Information menu This can be activated through DD host and Local display ATTENTION Serial number can be found in Device Inform...

Страница 113: ...nd diagnostics to monitor the functions and status of the device operations When errors and or faults are detected they are reported in the status bits of certain block parameters for example BLOCK_ERR The other parameters can be seen by viewing the status descriptions and or a value which may help to identify a fault Device status and operational faults are identified by viewing key parameter val...

Страница 114: ...oltage at the device s SIGNAL terminals Voltage must be within the limits If no voltage or voltage is out of operating limits determine the cause and correct it Insufficient current to the device Measure the DC current to the device The DC current must be within the limits If the current is insufficient determine the cause and correct it More than two or less than two terminators are wired to fiel...

Страница 115: ...commended action Incorrect Standard Dictionary Device Description DD or Symbols on host computer Verify that the Standard Dictionary the DD or symbols files are correct for the device Install the compatible version of Standard Dictionary and DD for the device on the host computer Incorrect pathnames to descriptions on host computer Check that the pathnames to locations of the Standard Dictionary a...

Страница 116: ...ource block Problem cause Things to check Recommended action Resource block mode is OOS mode and is not going to AUTO mode Read MODE_BLOCK PERMITTED Add AUTO mode to MODE_BLOCK PERMITTED Read MODE_BLOCK ACTUAL of Resource block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Resource block is not running Check BLOCK_ERR ...

Страница 117: ...O mode Read MODE_BLOCK PERMITTED Add AUTO mode to MODE_BLOCK PERMITTED Read MODE_BLOCK ACTUAL of Resource block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Block alarms are not reported Read FEATURE_SEL Reports are not selected in FEATURE_SEL If features do not include reports then the host must poll for alarms Read ...

Страница 118: ... display is not powering up contact Honeywell TAC NOTE If a user goes to menus sub menus in the display the parameter change will fail He must navigate out of the menus Writing to some of display parameter in SCREEN_1 SCREEN_2 SCREEN_3 SCREEN_4 SCREEN_5 SCREEN_6 SCREEN_7 and SCREEN_8 fails Check DISPLAY_TYPE If there is No Display then writing to the parameters fails Parameters write is supported ...

Страница 119: ...ion Error Read parameters BYPASS SHED_OP The default values of these parameters are configuration errors and they must be set to a valid range See Table 34 Read SP_HI_LIM SP_LO_LIM OUT_HI_LIM OUT_LO_LIM Check that SP_HI_LIM SP_LO_LIM OUT_HI_LIM OUT_LO_LIM PID block is not running Read the first element of BLOCK_TEST Number must be increasing indicating that block is running If the second element o...

Страница 120: ...ITTED Read MODE_BLOCK ACTUAL of Resource block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Schedule Block is not scheduled and therefore cannot execute to go to Target Mode Schedule the block to execute Check the License Status parameter value of the block Check whether License for additional function blocks has been...

Страница 121: ...Cause Things to check Recommended Action Block alarms are not reported Read FEATURE_SEL Reports are not selected in FEATURE_SEL If features do not include Reports then the host must poll for alarms Read LIM_NOTIFY Set LIM_NOTIFY to a value higher than zero but not higher than MAX_NOTIFY ...

Страница 122: ...Integrator block mode is in OOS mode with Block Configuration Error Check INTEG_TYPE INTEG_TYPE must not be zero blank Check TIME_UNIT 1 and TIME_UNIT 2 TIME_UNIT1 TIME_UNIT 2 must not be zero blank Value of output does not make sense Check TOTAL_SP TOTAL_SP must be set to a valid value and cannot be left at 0 if INTEG_TYPE is UP_AUTO DN_AUTO Value of output is going in negative value Check REV_FL...

Страница 123: ...OTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Mode does not change from OOS Configuration error BLOCK_ERR shows the Block Configuration Error condition since ARITH_TYPE is not set Value of output is incorrect Error in configuration Ensure that engineering units are correct for the computation If that fails see section 3 Block alarms are not reported Read FEATURE...

Страница 124: ... block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Mode does not change from OOS Configuration error BLOCK_ERR shows the Block Configuration Error condition due to array configuration errors Value of output is incorrect Error in X or Y array See section 3 Block alarms are not reported Read FEATURE_SEL Reports are not...

Страница 125: ...lock configuration errors Parameter Initial Value Valid Range Corrective Action ALERT_KEY 0 non zero Initial Value is a configuration error Set value to non zero number SIMULATE 1 disabled 1 2 disabled enabled Set value in valid range PV_FTIME 0 0 200 Set value to valid range ALARM_HYS 0 5 0 50 Set value to valid range HI_HI_PRI HI_PRI LO_LO_PRI LO_PRI 0 0 15 Set value to valid range HI_HI_LIM HI_...

Страница 126: ...f the Remote Indicator application shown in Table 35 Table 35 Diagnostics Device Functional Area Location Block object database DB RAM and EEPROM Communication stack database DB EEPROM Boot ROM ROM Program ROM ROM Trend and link object databases DB ROM BLOCK_ERR parameter BLOCK_ERR parameter shows diagnostic faults of hardware and software components within the Remote Indicator Each block object i...

Страница 127: ...hether it is critical or non critical ATTENTION Depending on the fieldbus interface application device operating status and parameter values may appear as text messages The text in the table is typical of values or messages seen when using the NI FBUS configurator Critical Fault In the case of a critical fault due to Memory Failure NV Static data loss or the readback check failure writes to the RE...

Страница 128: ...s in system debug When simulation mode is enabled user can simulate Field Diagnostic Alarm from Resource Blocks Setting simulation jumper A hardware jumper on the Communication Module assembly is set to enable or disable the SIMULATE parameter See Figure 23 for jumper location Table 36 shows how to set the simulation jumper on the Communication Module assembly Figure 23 Simulation Write Lock Jumpe...

Страница 129: ...d Enabling simulation mode The SIMULATE parameter is enabled by setting the hardware simulation jumper to the ON position Simulation mode truth table Table 37 shows the states of the simulation jumper and SIMULATE parameter shows how to activate the simulation mode Table 37 Simulation Mode Truth Table When the Simulation Jumper HW_SIMULATE_JUMPE R_STATE on Transducer board is set to and the SIMULA...

Страница 130: ...ion on the Transducer board 8 8 Critical Diagnostics Screens When a Critical Diagnostic is present in the Remote Indicator the Advanced Display will show the screen pictured in Figure 24 This screen will be inserted into the normal screen rotation and displayed between the user defined operator screens A description of the diagnostic conditions is given Table 39 along with suggested actions for re...

Страница 131: ...y key number callout Table 40 is a summarized list of recommended spare parts Table 40 Summary List of Recommended Spare Parts Part Number Description Figure No Electronics Housing Assembly 50086423 505 50086423 506 FieldBus Electronics Module Without REED Sensor PWA FIeldBus Electronics Module With REED Sensor PWA Figure 26 5 1 1 2 2 4 50075472 533 50075472 534 FieldBus Terminal Block Assy Withou...

Страница 132: ...90524 501 Carbon Steel Pipe Bracket Mounting kit for all models 1 2 50090524 503 316 Stainless Steel Pipe Bracket Mounting kit for all models 1 3 50092363 501 Carbon Steel Wall Bracket Mounting kit for all models 1 4 50092363 503 316 Stainless Steel Wall Bracket Mounting kit for all models 1 Figure 26 Electronic Housing Display End ...

Страница 133: ...26 3 50075472 533 50075472 534 Terminal Assy FF PB without Lightning protection Terminal Assy FF PB with Lightning protection 1 4 50049846 501 Advanced Display 1 See Fig 26 5 50049849 507 50049849 508 FF Electronics Module Assembly PWA without Reed sensor FF Electronics Module Assembly PWA with Reed sensor 1 See Fig 26 6 50049915 501 External Zero Span Config Buttons 1 K1 30757503 005 Electronics ...

Страница 134: ...mote Indicator User s Guide Revision 4 Appendix A Product Certifications A1 European Directive Information CE Mark RMA800 SmartLine Remote Indicator Series EU Declaration of conformity Document 32302406 can be downloaded here EU Declaration ...

Страница 135: ...C T4 Gc Note 1 50 ºC to 85ºC Enclosure Type 4X IP66 IP67 ALL ALL Standards FM 3600 2018 FM 3611 2018 ANSI UL 60079 0 2013 ANSI UL 60079 1 2015 FM 3610 2018 ANSI UL 60079 11 2014 FM 3810 2018 ANSI UL 60079 15 2013 ANSI UL 60079 31 2015 FM Class 3615 2018 FM 3616 2011 B CSA Canada Explosion proof CSA 14 2689056 Class I Division 1 Groups A B C D T6 T4 Dust Ignition Proof Class II III Division 1 Group...

Страница 136: ...S IEC 60079 0 2011 Edition 6 IEC 60079 1 2007 04 Edition 6 IEC 60079 11 2011 Edition 6 IEC 60079 15 2010 Edition 4 IEC 60079 26 2006 Edition 2 IEC 60079 31 2008 Edition 1 IEC 60529 2009 with Corr 3 E SAEx Flame proof Ex db IIC T6 T5 Gb Ex tb IIIC T 95o C Db Note 1 T6 20o C to 65o C T95o C T5 20o C to 85o C Intrinsically Safe Ex ia IIC T4 Ga Ex ic IIC T4 Gc Note 2 20o C to 70o C Non Incendive Ex ec...

Страница 137: ... protection has been checked on the nameplate the equipment shall not then be reinstalled using any of the other certification types c WARNINGS and Cautions Non Incendive Non Sparking Division 2 and Zone 2 Environments WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 Intrinsically Safe Divisions 1 Zone 1 and Zone 2 Environments WARNING EXPLOSION HAZ...

Страница 138: ...as follows RMA801 T4 for 50 C Ta 85 C RMA803 T4 for 20 C Ta 70 C d The RMA800 series enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction Care must be considered during installation and use to prevent impact or friction to avoid impact e If a charge generating mechanism is present the exposed metallic part on the enclosure is capable of storin...

Страница 139: ...Revision 4 Foundation Fieldbus RMA803 Remote Indicator User s Guide Page 123 Control Drawing 50089981 ...

Страница 140: ...Page 124 Foundation Fieldbus RMA803 Remote Indicator User s Guide Revision 4 ...

Страница 141: ...Revision 4 Foundation Fieldbus RMA803 Remote Indicator User s Guide Page 125 ...

Страница 142: ...mporting DD files 28 Input Selector block 64 Installation and Startup 11 Integrator block 69 L LCD Transducer block 48 Licensing for Function Blocks 96 M Maintenance 92 Preventive Maintenance Practices and Schedules 92 Replacing the Communication Module 92 MAO Block 87 Monitoring the Basic and Advanced Displays Advanced Displays 25 Mounting Remote Indicator 11 O Operation 15 Three Button Operation...

Страница 143: ...Revision 4 Foundation Fieldbus RMA803 Remote Indicator User s Guide Page 127 V Verifying communication 8 Verifying the installation 7 W Wiring a Remote Indicator 13 Write protection 114 ...

Страница 144: ...contact one of the offices below ASIA PACIFIC Honeywell Process Solutions TAC hfs tac support honeywell com Australia Honeywell Limited Phone 61 7 3846 1255 FAX 61 7 3840 6481 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Korea...