10.2.2 SmartDrive Compact - Mains voltage 380 - 480 V
* The maximum ambient operating temperature of COMP400-5P5-20 is
+40°C!
Note 1:
The input currents are calculated values with 100 kVA line transformer
supply.
Note 2:
The mechanical dimensions of the units are given in Chapter 3.1.1.
Mains voltage 380-480 V, 50/60 Hz, 3~ series
Product code
Rated loadability
Motor
shaft
power
Nominal
input
current
Mechanical
size and
weight (kg)
100%
continuous
current
I
N
[ A ]
150%
overload
current
[ A ]
380-480V
supply
P [ kW ]
[ A ]
COMP400-P37-20
1,3
2,0
0,37
2,2
MI1 0,55
COMP400-P55-20
1,9
2,9
0,55
2,8
MI1 0,55
COMP400-P75-20
2,4
3,6
0,75
3,2
MI1 0,55
COMP400-1P1-20
3,3
5,0
1,1
4,0
MI2 0,70
COMP400-1P5-20
4,3
6,5
1,5
5,6
MI2 0,70
COMP400-2P2-20
5,6
8,4
2,2
7,3
MI2 0,70
COMP400-3P0-20
7,6
11,4
3,0
9,6
MI3 0,99
COMP400-4P0-20
9,0
13,5
4,0
11,5
MI3 0,99
COMP400-5P5-20*
12,0
18,0
5,5
14,9
MI3 0,99
Table 10.3 : SmartDrive Compact power ratings, 380 - 480 V