SK-460-009 

I56-3443-000

INSTALLATION STEPS

1.  Cabinet Mounting
 

 In a clean, dry area, mount the backbox using the four holes pro-

vided in the back surface of the cabinet (Figure 2).

2.  Module Installation
 

 There are two methods for installing a module in the rear position 
of a chassis. Method one is for installation of a rear module only, 
when no module will be installed in front of it. Refer to Figure 3 for 
instructions. Method two is for installation of a rear module when 
another module will be installed in the chassis position in front of 
it.  Refer to Figures 4a and 4b for method two. All necessary screws 
and standoffs are supplied with the modules.

C0237-00

FIGURE 3: INSTALLATION OF REAR MODULE ONLY, METhOD ONE

2

3

1

Step 1:   Insert the bottom edge of the SK-Mon-10 module down into a rear 

slot of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the short standoff attached to the chassis.

Step 3:  Align the long standoff with the short stand off and tighten.

FIGURE 4A: INSTALLATION OF SK-MON-10 MODULE IN A REAR ChAS-
SIS POSITION, METhOD TwO

1

2

3

1

FIGURE 4B: INSTALLATION OF SK-MON-10 MODULE IN FRONT ChAS-
SIS POSITION

Step 1:   Insert the bottom edge of the SK-Mon-10 module down into a front 

slot of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the 11⁄4˝ (31.75mm) standoffs installed on the 
rear module.

Step 3:  Align two 4-40 screws with the two standoffs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

wIRING

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 
regulations.
1.    Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All wiring to the SK-Mon-10 is done via terminal blocks. In order to prop-

erly  make  electrical  connections  strip  approximately  1⁄4˝  of  insulation 
from the end of wire, sliding the bare end of the wire under the clamping 
plate screw.  

3.    Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module between 01 and 90 (or 01 
and 150 for panels that support 159 addresses).

In  Class  B  operation,  the  remaining  modules  are  automati 
cally assigned to the next nine higher addresses. For example, if the base ad-
dress switch is set to 28, the next nine modules will be addressed to 29, 30, 31, 
32, 33, 34, 35, 36, and 37.

The  module  is  shipped  in  Class  B  position,  remove  shunt  for  Class  A. 
When operating in Class A

, alternate modules are paired together (+0/+1, 

+2/+3, +4/+5, +6/+7, +8/+9), resulting in a total of five modules. For 
example, if the base address switch is set to 28, then 30, 32, 34 and 36 will be 
automatically assigned to the modules while 29, 31, 33, 35 and 37 are avail-
able to be used for other modules on the SLC. For Class A and B operation, 
DO NOT set the lowest address above 90 (or 150 for panels that support 159 
addresses), as the other modules will be assigned to nonexistent addresses.

NOTE: The SK-Mon-10 must have power cycled for shunt changes to take ef-
fect. 
4.    A shunt is provided to disable a maximum of two unused modules in 

Class B operation and one unused module in Class A operation. Modules 
are disabled from the highest address and work downward.  If two mod-
ules are disabled, the lowest eight addresses will be functional, while the 
highest two will be disabled. For example, in Class B operation, if the 
shunt for Address Disable is placed on “two” and the base switch is set 
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34 and 35 
while disabling the highest two positions.

5.    A communications loss feature is available on some panels. Upon a com-

munication loss, due to a microprocessor failure at the control unit, the 
SK-Mon-10 will send a signal to the control unit to activate the notifica-
tion device circuits upon initiating of an alarm on the SK-Mon-10. A sin-
gle shunt is used to enable (shunt on) or disable (shunt off) this feature 
for all modules on the board.

NOTE: Place unused shunts on single pin to store on board for future use.

wIRING NOTES

Power-limited  circuits  must  employ  type  FPL,  FPLR,  or  FPLP  cable  as 

• 

required by Article 760 of the NEC.

PROGRAMMING

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.  

C0225-00

C0226-00

BACKBOX
MOUNTING
HOLES

C0235-00

FIGURE 2: TYPICAL MOUNTING hOLE LOCATIONS

Step 1:   Insert the bottom of the SK-Mon-10 module down into a rear slot on 

the chassis. 

Step 2:   Carefully swing the upper edge of the board back towards the back of 

the chassis until it touches the two standoffs.

Step 3:  Align two 4-40 screws with the two standoffs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

The steps in Figures 4a and 4b describe and illustrate module in-
stallation when the rear chassis position and the position in front 
of it will be filled.  Front position installation is possible only if the 
rear position is filled with a module.