SiXCOMBO
Combination Smoke/Carbon Monoxide (CO) Detector / Combinación de detector de Humo/Monóxido de carbono (CO)
Quick Installation Guide
Guía Rápida de Instalación
This device is intended for use with Honeywell controls that support SiX series
devices including the SiXCOMBO. Check the control for compatibility with this
device. This device occupies 3 control panel zones, one zone for each service
(smoke detection, heat detection, carbon monoxide detection).
FEATURES
•
Multi-Criteria Sensing:
uses four sensing elements to react faster while
minimizing false alarms:
-
Photoelectric smoke sensor detects airborne smoke particles
-
Carbon Monoxide (CO) sensor detects smoldering fires
-
Infrared (IR) sensor measures ambient light and flame signatures, such as
flame flicker
-
Thermal detection monitors for dangerous rise in temperature
•
CO Detector End-of-Life reporting (detector needs replacing)
•
Smoke detector maintenance reporting (detector needs cleaning or replacing)
•
Low Battery Detection
•
One Go / All Go: all smoke/CO detectors in the system programmed as one-go-
all-go will sound on alarm.
•
Voice announcements (English only)
See
Installation Instructions
(800-22142 – https://mywebtech.honeywell.com/) and
the
Limitations of Fire Alarm Systems
Insert
(800-15144 12/15) and
System Smoke
Detectors Application Guide
(SPAG9101 7/12).
LED INDICATORS
The SiXCOMBO Smoke/CO detector has a multi-color top LED:
Green = Supervisory indication; blinks during power on, reset, and during normal
operation
Amber = Signal maintenance and trouble events
Red = Alarm condition (either Smoke or CO)
Side LED windows indicate alarms:
Red = smoke alarm
Blue = CO alarm
Este producto está diseñado para ser usado en controladores Honeywell que
soportan dispositivos de la serie SiX including the SiXCOMBO. Check the control for
compatibility with this device. This device occupies 3 control panel zones, one zone
for each service (smoke detection, heat detection, carbon monoxide detection).
CARACTERISTICAS
•
Detección multi-criterio: Utiliza cuatro elementos de detección para una más
rápida reacción mientras se minimizan falsas alarmas:
-
Sensores fotoeléctricos de humo que detectan partículas de humo en el aire
-
Sensores de detección de Monóxido de Carbono (CO) para detección de
incendios sin llama
-
Sensores infrarrojos (IR) que detectan luces de ambiente y señales de flamas
tales como movimiento de las llamas
-
Detección termal que monitorea aumento peligroso de temperaturas
•
Fin de vida útil del detector de CO (el detector necesita ser remplazado)
•
Reporte de mantenimiento del sensor de humo (Cuando el sensor requiere limpieza
or replacing)
•
Detección de batería baja.
•
Uno se activa / Todos se activan: todos los detectores de humo/CO en el sistema
programados como “uno se activa/todos se activan”, sonarán su propia alarma
•
Voice announcements (English only)
Vea la
guía de instalación de Honeywell
(800-22142-
https://mywebtech.honeywell.com/) y el inserto de las limitaciones de sistemas de
alarma de fuego. (800-15144SP 12/15). Consulte la Guía de aplicación de detectores
de humo del sistema (SPAG9101 7/12).
INDICADORES DE LED
El detector de humo/Monóxido de carbono SiXCOMBO contiene un LED multicolor:
Verde = Indicador de supervisión; parpadea durante iniciación, reinicio y durante
operación normal.
Ámbar = Señal de eventos de mantenimiento o problemas
Rojo = Condición de alarma (de humo o monóxido de carbono)
Ventanas de LED laterales: Rojo = Humo, Azul = Monóxido de carbon
ENROLLMENT
REGISTRO
IMPORTANT NOTES:
•
The Smoke, Heat, and Carbon Monoxide (CO) sensors each
have unique MAC ID numbers (serial numbers) that are
enrolled in separate zones.
•
Once enrolled, the device cannot be used with another system
until it is removed from the current controller. See the 24-hour
Enrollment Deletion section below or the controller’s
instructions.
Enroll the Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate (tamper switch
must be faulted when enrolling).
2. Put the control panel in Zone Programming mode.
For Lyric Controller:
Security
>
installer code
>
Program
> (
scroll down
) >
SiX Programming
3. Pull the battery tab to activate enrollment process (be sure
batteries are seated properly to avoid a false low battery
condition). If the battery tab has already been removed and
the unit is powered up, press either Test switch for less
than 3 seconds to activate the enrollment process.
4. The device attempts enrollment (green LED flashes about 8
seconds). If successful, the green LED lights steady for 3
seconds and the device announces successful enrollment.
If the LED does not light steady, enrollment failed. Retry by
pressing either Test switch for less than 3 seconds.
All services (Smoke, Heat, and CO) are automatically
enrolled in sequential (or next available) zone numbers with
the following default attributes:
Zone
Device Type
Zone Response Type
Smoke Det. Smoke Detector
Fire No Verification
Heat Det.
Heat Sensor
Fire No Verification
CO Det.
Carbon Mono. Det. Carbon Monoxide
NOTE
: Maintenance and CO End-of-Life are automatically
enrolled for the respective smoke and CO zones. Upon
either of these conditions, Contact ID code E386 “Low
Maintenance Smoke” is sent for the respective zone.
Supervision
: Detector supervision is factory set for 1
minute and is not programmable.
5. To assign zone descriptors for each of the zones and/or
change device type or zone response type, select the zone
then select
Edit
and make the desired changes. Press
Save
when done.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete
this device from the controller. This allows reenrollment in a
specific controller in case enrollment in that controller failed
(i.e., the device inadvertently enrolled in a different controller).
This resets the device to factory default settings and removes
the communication link data in the controller in which it is
enrolled, allowing the device to be reenrolled in the desired
controller.
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds, then release. The green light
flashes rapidly.
2. Press and hold both buttons again for one second and
release.
OPEN / ABIERTO
Operation Modes / Modos de operación
MODE / MODO Status LED (Top) /
Estado del LED
LED Windows
(Side)
/ Ventana
del LED (Lateral)
Sounder /
Sonador
Speaker / Bocina
Power Up /
Encendido
Blink Green, every
2 secs/ Parpadea
verde cada
2 segundos
Dark /
Apagado
Silent /
Silencio
Voice welcome,
instructions after
first time power-up
or after default
/ Bienvenida de
voz, seguido por
las instrucciones
POR para la
selección de
lenguaje,
enrolamiento,
pruebas
Normal (Standby)
/
Estado normal
Single Blink Green
every 10 sec /
parpadeo verde
cada 10 segundos
Dark /
Apagado
Silent /
Silencio
Silent /
Silencio
Smoke Alarm /
Alarma de humo
Blink Red every 10
secs / parpadeo rojo
cada 10 segundos
Blink Red /
Parpadeo rojo
Temp-3
“Warning, smoke,
evacuate”/
“Advertencia,
humo, evacuar”
Thermal Alarm /
Alarma termal
Blink Red every 10
secs / parpadeo rojo
cada 10 segundos
Blink Red /
Parpadeo rojo
Temp-3
“Warning, smoke,
evacuate”/
“Advertencia,
humo, evacuar”
CO Alarm / Alarma
de monóxido de
carbono
Blink Red every 10
secs / parpadeo rojo
cada 10 segundos
Blink Blue /
Parpadeo azul
Temp-4
“Warning, carbón
monoxide, move
to fresh air” /
Advertencia,
monóxido de
carbón, pasar al
aire fresco
Powered Down /
Apagado
Dark /
Apagado
Dark /
Apagado
Silent /
Silencio
Silent /
Silencio
TO SILENCE THE DETECTOR
Press the test switch. The detector sounds again after 5 minutes if the
alarm condition continues.
PARA SILENCIAR EL DETECTOR
Presione el interruptor de prueba. El detector volverá a sonar después
de 5 minutos si continúa la condición que originó la alarma.
NOTA IMPORTANTE:
•
The Smoke, Heat, and Carbon Monoxide (CO) sensors each
have unique MAC ID numbers (serial numbers) that are enrolled
in separate zones.
•
Una vez registrado, el dispositivo no se puede usar con otro
sistema hasta que sea removido del controlador actual. See the
24-hour Enrollment Deletion section below or the controller’s
instructions.
Enroll the Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate (tamper switch
must be faulted when enrolling).
2. Put the control panel in Zone Programming mode.
For Lyric Controller:
Security
>
installer code
>
Program
>
(
scroll down
) >
SiX Programming
3. Pull the battery tab to activate enrollment process (be sure
batteries are seated properly to avoid a false low battery
condition). If the battery tab has already been removed and
the unit is powered up, press either Test switch for less than
3 seconds to activate the enrollment process.
4. The device attempts enrollment (green LED flashes about 8
seconds). If successful, the green LED lights steady for 3
seconds and the device announces successful enrollment.
If the LED does not light steady, enrollment failed. Retry by
pressing either Test switch for less than 3 seconds.
All services (Smoke, Heat, and CO) are automatically
enrolled in sequential (or next available) zone numbers with
the following default attributes:
Zone
Device Type
Zone Response Type
Smoke Det. Smoke Detector
Fire No Verification
Heat Det.
Heat Sensor
Fire No Verification
CO Det.
Carbon Mono. Det. Carbon Monoxide
NOTE
: Maintenance and CO End-of-Life are automatically
enrolled for the respective smoke and CO zones. Upon either
of these conditions, Contact ID code E386 “Low Maintenance
Smoke” is sent for the respective zone.
Supervision
: Detector supervision is factory set for 1 minute
and is not programmable.
5. To assign zone descriptors for each of the zones and/or
change device type or zone response type, select the zone
then select
Edit
and make the desired changes. Press
Save
when done.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete
this device from the controller. This allows reenrollment in a
specific controller in case enrollment in that controller failed (i.e.,
the device inadvertently enrolled in a different controller). This
resets the device to factory default settings and removes the
communication link data in the controller in which it is enrolled,
allowing the device to be reenrolled in the desired controller.
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds, then release. The green light
flashes rapidly.
2. Press and hold both buttons again for one second and
release.
MOUNTING
If the device is not in its final mounting
location when enrolled, conduct Go/No Go
tests (see controller’s instructions) to verify
adequate signal strength. Adjust the device
location and orientation as necessary.
MONTAJE
Si el dispositivo no está en su ubicación final
de montaje cuando se registre, realice
pruebas de Va/No Va (vea las instrucciones
del controlador) para verificar que la
intensidad de la señal sea adecuada. Ajuste
la ubicación y orientación del dispositivo
según ea necesario.