SINGLE STAGE HEAT PUMP PROGRAMMABLE COMMERCIAL THERMOSTAT

63-4361

 2

2.0

SEQUENCE OF OPERATIONS

The heating and cooling setpoints shall be individually adjustable for both the occupied and unoccupied periods. The
thermostat shall have a minimum deadband of 2

°

F (no mechanical heating or cooling shall operate within this

deadband). Space temperature deviation above the cooling setpoint or below the heating setpoint shall generate a
demand signal to control the system as follows.

2.1

Heating

2.1.1

The thermostat shall control the heating output based on the demand signal communicated from the
thermostat program, taking into account both space temperature deviation (proportional error) and the
duration of that temperature deviation (integral error).

2.1.2

The thermostat shall energize heating equipment when space temperature falls below heating
setpoint.

2.2

Cooling

2.2.1

The thermostat shall control the cooling output based on the demand signal communicated from the
thermostat program, taking into account both space temperature deviation (proportional error) and the
duration of that temperature deviation (integral error).

2.2.2

The thermostat shall energize cooling equipment when space temperature exceeds cooling setpoint.

2.3

Heating Setback and Cooling Setup

Initiation of heating setback or cooling setup for each of 7 days shall be provided by a programmed time
schedule manually entered into the thermostat. When all or a portion of a manually programmed schedule is
unavailable, the thermostat shall control to the default program as follows:

Table of Default Program

Occupied

Unoccupied

Heating Setpoints

70

°

F (21

°

C)

55

°

F (13

°

C)

Cooling Setpoints

78

°

F (26

°

C)

90

°

F (32

°

C)

2.4

Setpoint Recovery from Unoccupied to Occupied

The thermostat shall employ Intelligent Recovery™. This shall select the optimum time to begin building warm
up or cool down based on setpoints and occupied program as follows:

2.4.1

Heating: 5

°

F per hour.

2.4.2

Cooling: 5

°

F per hour.

2.5

Fan Operation

2.5.1

Fan operation shall be energized with calls for cooling and calls for heating (optional).

2.6

Heating and Cooling Operation Minimum On and Off Times

The thermostat shall incorporate a program to maintain minimum-stage operation in both the heating and
cooling:

2.6.1

Cooling: 2 minutes on and 4 minutes off.

2.6.2

Heating: 2 minutes on and 4 minutes off.

2.7

Power Interruption

The system shall cycle off and provide timed restaging of heating or cooling equipment upon restoration of
power. The restaging operation shall occur according to minimum stage operation times incorporated in the
thermostat. A power interruption is annunciated by a blank LCD display.

2.7.1

During a power interruption less than 2 hours, the thermostat retains all programmed occupied and
unoccupied start times and temperatures as well as the present time and day.

Содержание Single Stage Heat Pump ProgrammableCommercial Thermostat

Страница 1: ...anual changeover between heating and cooling setpoints i Display room temperature in F or C j Display time in 12 or 24 hour clock format 1 2 2 System Components a Seven day programmable thermostat b Wallplate 1 3 Codes and Standards 1 3 1 The system shall comply with applicable provisions of ASHRAE 90 75 1 3 2 These specifications are based on equipment from Honeywell to set a standard for design ...

Страница 2: ...g setup for each of 7 days shall be provided by a programmed time schedule manually entered into the thermostat When all or a portion of a manually programmed schedule is unavailable the thermostat shall control to the default program as follows Table of Default Program Occupied Unoccupied Heating Setpoints 70 F 21 C 55 F 13 C Cooling Setpoints 78 F 26 C 90 F 32 C 2 4 Setpoint Recovery from Unoccu...

Страница 3: ...int adjustments and clock and day adjustments c Lock out thermostat Installer Setup only 2 9 2 Thermostat shall allow for door to be locked by use of two Allen head screws to lock the cover and not allow access to the keypad 2 10 Overrides Temperature setpoints can be overridden in three ways 2 10 1 Thermostat shall allow for a 3 hour timed override from unoccupied setpoint to occupied setpoint fr...

Страница 4: ...rol Your World Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408 0524 M2H 2C9 63 4361 J A 2 97 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: