SKE-SeriesVoice Evacuation System Installation/Operation Manual
4-2
151267
SW2
Evacuation
Tone Pattern
off
off
off
ANSI Cadence
This option selects the
tone sound that will be
made during
evacuation.
For UL 864
installations, this
option must be set to
ANSI cadence.
on
off
off
March Code
off
on
off
California
on
on
off
Steady
off
off
on
Alert Tone
on
off
on
Hi-Lo
off
on
on
ANSI Whoop
on
on
on
Continuous Whoop
Local Mic.
Supervision
Selection
off
Not supervised
This selection
determines if the local
microphone will be
supervised.
For UL 864
installations, this
option must be set to
O
N. OFF
is not
acceptable for UL 864
installations.
on
Supervised
Remote Mic
off
Not supervised
This selection
determines if the
remote microphone
will be supervised.
For UL 864
installations, this
option must be set to
O
N. OFF
is not
acceptable for UL 864
installations.
on
Supervised
CMD1 uses
recorded
message
off
Play Pre-recorded
CMD1 message
This option selects
which message will be
played for CMD1 or
CMD2, either the pre-
recorded or the
recorded message.
on
Play Recorded
Message
CMD2 uses
recorded
message
off
Play Pre-recorded
CMD2 message
on
Play Recorded
Message
Enter Record
Mode
off
on
Table 4-1: DIP Switch Programming
DIP
Switch
Function
Switch Number
Setting
Comments
1
2
3
4
5
6
7
8
firealarmresources.com