Honeywell SILENT KNIGHT SK-Zone-6 Скачать руководство пользователя страница 2

FIGURE 2. TYPICAL MOUNTING HOLE LOCATIONS

 

BACKBOX
MOUNTING
HOLES

 C0235-00

2.  Module Installation

There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will 
be installed in front of it. Refer to Figure 3 for instructions. Method two is for 
installation of a rear module when another module will be installed in the 
chassis position in front of it. Refer to Figures 4a and 4b for method two. All 
necessary screws and stand-offs are supplied with the modules.

FIGURE 3. INSTALLATION OF REAR MODULE ONLY, METHOD ONE

 

2

3

1

 C0237-00

Step 1: 

 Insert the bottom of the SK-Zone-6 module down into a rear slot on 
the chassis. 

Step 2:   Carefully swing the upper edge of the board back towards the back of 

the chassis until it touches the two stand-offs.

Step 3:  Align two 4-40 screws with the two stand-offs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

The steps in Figures 4a and 4b describe and illustrate module installation 
when the rear chassis position and the position in front of it will be filled. 
Front position installation is possible only if the rear position is filled with a 
module. 

FIGURE 4A. INSTALLATION OF SK-ZONE-6 MODULE IN A REAR 

CHASSIS POSITION, METHOD TWO

 

1

 C0225-00

Step 1:   Insert the bottom edge of the SK-Zone-6 module down into a rear slot 

of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the short stand-off attached to the chassis.

Step 3:  Align the long stand-off with the short stand-off and tighten. 

FIGURE 4B. INSTALLATION OF SK-ZONE-6 MODULE IN FRONT CHASSIS 

POSITION

 

2

3

1

C0226-00

Step 1:   Insert the bottom edge of the SK-Zone-6 module down into a front 

slot of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the 1.25˝ (32 mm) stand-offs installed on the 
rear module.

Step 3:  Align two 4-40 screws with the two stand-offs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations.
NOTE: All references to power limited represent "Power Limited (Class 2)".
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All wiring to the SK-Zone-6 is done via terminal blocks. In order to prop-

erly make electrical connections strip approximately 0.25˝ of insulation 
from the end of wire, sliding the bare end of the wire under the clamping 
plate screw. 

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module between 01 and 154.

In Class B operation, the remaining modules are automatically assigned to the 
next five higher addresses. For example, if the base address switch is set to 28, 
the next five modules will be addressed to 29, 30, 31, 32 and 33.

The module is shipped in Class B position, remove shunts for Class A. When 
operating in Class A, alternate modules are paired together (+0/+1, +2/+3, 
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the 
modules while 29, 31 and 33 are available to be used for other modules on the 
SLC. For Class A and B operation, DO NOT set the lowest address above 154, 
as the other modules will be assigned to nonexistent addresses.

NOTE: The SK-Zone-6 must have power cycled for shunt changes to take effect.

4.   A shunt is provided to disable a maximum of two unused modules in 

Class B operation and Class A operation. Modules are disabled from the 
highest address and work downward. If two modules are disabled, the 
lowest four addresses will be functional, while the highest two will be 
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will 
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.

NOTE:  Place unused shunts on single pin to store on board for future use.

WIRING NOTES

•  Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•  All wiring must be in accordance with the NEC, NFPA 72 and all other 

applicable codes and standards. All external power supplies must be 
power limited with battery back-up. All external power supplies and 
detectors must be UL listed for fire protection signaling applications.

PROGRAMMING

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.

  

I56-3441-007 

 

 7/1/2022

Содержание SILENT KNIGHT SK-Zone-6

Страница 1: ...ally assigned to the next five higher addresses Provisions are included for disabling a maximum of two unused modules to release the addresses to be used elsewhere Each mod ule also has panel controlled bicolor LED indicators The panel can cause the LEDs to blink latch on or latch off Included 5 1 x 4 Terminal Blocks 2 1 25 Stand offs 3 Shunts 4 Machine Screws 2 Nuts 1 Long Power Supply Jumper 6 3...

Страница 2: ...ited represent Power Limited Class 2 1 Install module wiring in accordance with the job drawings and appropri ate wiring diagrams 2 All wiring to the SK Zone 6 is done via terminal blocks In order to prop erly make electrical connections strip approximately 0 25 of insulation from the end of wire sliding the bare end of the wire under the clamping plate screw 3 Set the address on the modules per t...

Страница 3: ...ATORS 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A IDC TYPICAL A B SELECT A B SELECT DISABLE 1 DISABLE 2 IDC 2 IDC 3 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETEC...

Страница 4: ...erienced radio TV technician for help FCC STATEMENT FIGURE 8 EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY Refer to figures 8 and 9 for typical wiring Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A A ó ó 0 1 IDC ADDRESS ó ó 2 3 IDC ADDRESS ó ó 4 5 IDC ADDRESS SLC ó ó A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 ó ó 0 1 IDC ADDRESS ó ó...

Отзывы: