SK-FML/SK-FSL Fiber Option Modules Installation Instructions

2

P/N LS10178-001SK-E Rev A

ECN: 17-0196

Section 3 Installation

S

ection 3.2 SK-FML/SK-FSL Installation

Section 3.1 Installation Requirements

CAUTION:

 

STATIC SENSITIVE EQUIPMENT:

THIS EQUIPMENT IS SENSITIVE TO STATIC 
ELECTRICITY. IT MAY BE DAMAGED IF NOT 
PROPERLY HANDLED. TRANSPORT AND STORE 
THIS UNIT IN A STATIC-SHIELDING BAG. 
FAILURE TO OBSERVE THIS REQUIREMENT 
COULD CAUSE LATENT DAMAGE TO THE 
EQUIPMENT WHICH MIGHT NOT MANIFEST ITSELF 
UNTIL AFTER THE EQUIPMENT IS PLACED IN 
SERVICE.

DISCONNECT ALL POWER:

REMOVE ALL SOURCES OF POWER BEFORE YOU 
SERVICE, REMOVE OR INSTALL ANY UNITS.

All components should be located per the following 
requirements:

Installations are to be indoors only, in dry loca-
tions, protected from rain, water, and rapid 
changes in temperature that could cause con-
densation. Equipment must be securely 
mounted on rigid, permanent walls.

Operating temperature shall not exceed the 
range of 32° to 120° F (0 to 49° C).

Operating humidity not to exceed 93% non-con-
densing at 90° F (32° C).

All sub-assemblies and components are to be 
located in compliance with the local, the national 
codes and the manufacturer’s recommenda-
tions.

All installation field wiring shall be in compliance 
with the local code, the national code and the 
manufacturer’s recommendations.

Use the Architects and Engineering Specifica-
tions for detailed information on your Facility’s 
Configuration.

1.

Remove the unit from its static-shield bag, 
observing proper static protection measures.

2.

Visually inspect the unit for damage.
If any components are damaged, notify the 
shipping carrier immediately. Report missing 
components to the Silent Knight Customer 
Service.

3.

Use the Hardware Kit provided with the unit.

4.

Plug the Fiber Module #1 into P6 of the ECS-
NVCM or SK-NIC circuit as shown in Location 1 
in Figure 3.2.1 and Figure 3.2.2

5.

To connect the Fiber Module # 1 to the ECS-
NVCM or SK-NIC, insert and secure three 
screws (#4-40 x 1/4”) as shown in Location 2 in 
Figure 3.2.1 and Figure 3.2.2.

Section 3.2 SK-FML/SK-FSL Installation
                    (continued)

6.

Plug the Fiber Module #1 into P5 of the
ECS-NVCM or SK-NIC circuit as shown in 
Location 3 in Figure 3.2.1 and Figure 3.2.2.

7.

To connect the Fiber Module #1 to the ECS-
NVCM or SK-NIC, insert and secure three 
screws (#4-40 x 1/4”) as shown in Location 4 in 
Figure 3.2.1 and Figure 3.2.2.

Figure 3.2.1 illustrates the SK-FML/SK-FSL installed 
to the SK-NIC.

Note:

FIBER MODULES:SK-FSL AND SK-FML. INSTALL 
A MAXIMUM OF TWO BOARDS PER 
INSTALLATION.THE FIBER MODULES CAN BE 
COMBINED.

Figure 3.2.1 SK-FML Installation

Figure 3.2.2 illustrates the SK-FML/SK-FSL installed 
to the ECS-NVCM.

Figure 3.2.2  SK-FSL Installation

 

2

4

2

2

4

4

4

2

1

1

3

3

4

4

2

2

SK

-N

IC

J6

J5

SK

-F

ML

SK

-FS

L

AB

AB

SK

-F

ML

SK

-F

SL

1

FIBER MODULE #2

FIBER MODULE #1

SCREW
(#4-40 X ¼”)
(6.35 mm)
(3 PLACES)

SCREW
(#4-40 X ¼”)
(6.35 mm)
(3 PLACES)

1

2

2

2

4

1

4

3

4

4

4

4

2

1

J5

3

J6

2

2

O

U

T

+

V

B

U

S

2

IN

+

O

U

T

+

V

B

U

S

1

IN

+

P

O

R

T

 1

A

  

  

  

  

B

P

O

R

T

 2

A

  

  

  

  

B

CM

D2

CO

M

M

O

N

 C

M

D1

AU

AU

DI

O

G

N

   

IN

SK

-F

ML

SK

-F

SL

EC

S-

NV

CM

FIBER MODULE #2

FIBER MODULE #1

SCREW
(#4-40 X ¼”) (6.35 mm)
(3 PLACES)

SCREW
(#4-40 X ¼”) (6.35 mm)
(3 PLACES)

firealarmresources.com

Содержание SILENT KNIGHT SK-FML

Страница 1: ...e Figure 1 1 SK FML Circuit Board SK FSL Fiber Optic Single Mode Transmitter The SK FSL is a fiber module that is used as one channel to transmit or receive communications with the ECS NVCM Network Voice Control Module or SK NIC Network Interface Card It allows the single mode fiber to network between the SK FSL module boards Figure 1 2 shows the SK FSL fiber module Figure 1 2 SK FSL Circuit Board...

Страница 2: ...s static shield bag observing proper static protection measures 2 Visually inspect the unit for damage If any components are damaged notify the shipping carrier immediately Report missing components to the Silent Knight Customer Service 3 Use the Hardware Kit provided with the unit 4 Plug the Fiber Module 1 into P6 of the ECS NVCM or SK NIC circuit as shown in Location 1 in Figure 3 2 1 and Figure...

Страница 3: ...tput power for the transmitting fiber See Table 4 2 2 SW1 4 Not used P1 Plugs onto P5 Port 1 or P6 Port 2 of the ECS NVCM or SK NIC NOTE Use standard ST connector fiber optic cable multi mode up to 200 µ optimized for 62 5 125 µ Signal loss up to 8dB maximum between nodes Table 4 2 1 SK FML Terminal Wiring Designations J2 J1 FIBER IN FIBER OUT SW1 1 SW1 2 SW1 3 Drive Current OFF OFF OFF 10 mA OFF ...

Страница 4: ... flickers and turns ON If no activity is detected the TX light turns OFF 2 RX Green Lights while data is received on the Repeater When activity is detected the RX light flickers and turns ON When no activity is detected the RX light turns OFF Table 4 4 2 SK FSL LED Indicators Part Number Title LS10143 001SK E IFP 2100 ECS Installation and Operation Manual LS10144 001SK E 6820 EVS Installation and ...

Отзывы: