Model SK-5208 Fire Control/Communicator Installation and Operation Manual
6-2
P/N 151204
6.2
Reporting Codes
Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the
type of reporting format used.
Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting
formats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1
format reporting values.
Table 6-2: Event and Reporting Code by Format
Event
SIA8 & 20
SK4/2
3/1 1400 &2300
Contact ID
AC Trouble
AT0
T0
Trouble Code
1 301 000
AC Restore
AR0
R0
Restore Code
3 301 000
Annunciator Trouble 1-7
ET17 - ET23
T7 - T3
Trouble Code
1 330 017 - 1 330 023
Annunciator Restore 1-7
ER17 - ER23
R7 - R3
Restore Code
3 330 017 - 3 330 023
Bell Trouble 1-4
ET32-ET35
T2 - T5
Trouble Code
1 330 032 - 1 320 035
Bell Restore 1-4
ER32-ET35
R2 - R5
Restore Code
3 330 032 - 3 320 035
Smoke (Loop) Power Trouble
ET36
T6
Trouble Code
1 320 036
Smoke (Loop) Power Restore
ET36
R6
Restore Code
3 320 036
Aux Power Trouble
ET37
T7
Trouble Code
1 330 037
Aux Power Restore
ER37
R7
Restore Code
3 330 037
Earth Ground Trouble
ET38
T8
Trouble Code
1 330 038
Earth Ground Restore
ER38
R8
Restore Code
3 330 038
Keypad Power Trouble
ET40
T0
Trouble Code
1 330 040
Keypad Power Trouble
ET40
R0
Restore Code
3 330 040
5217 Expander Trouble
ET51-ET52
T1 - T2
Trouble Code
1 330 051 - 1 330 052
5217 Expander Restore
ER51-ER52
R1 - R2
Restore Code
3 330 051 - 3 330 052
5280 Expander Trouble
ET61-ET68
T1 - T8
Trouble Code
1-330 061 - 1 330 068
5280 Expander Restore
ER61-ER68
R1 - R8
Restore Code
3-330 061 - 3 330 068
NAC Bypass
ET101-ET104
T1 - T4
Trouble Code
1-330 101 - 1 330 104
NAC Restore
ER101-ER104
R1 - R4
Restore Code
3-330 101 - 3 330 104
NAC Supervisory (See Note)
SS101-SS104
S1 - S4
Supervisory Code
1 203 101 - 1 203 104
NAC Supervisory Restore (See Note)
SR101-SR104
R1 - R4
Restore Code
3 203 101 - 3 203 104
Fire Alarm 1-30
FA1 - FA30
A1 - A0
Alarm Code
1 110 001 - 1 110 030
Fire Bypass
FB1-FB30
T1 - T0
Trouble Code
1 571 001 - 1 571 030
Fire Alarm Restore 1-30
FH1 - FH30
AR1 - AR0
Alarm Restore Code
3 110 001 - 3 110 030
Fire Test Begin
FI1 - FI10
Test 0
Test Code
1 604 000
Fire Trouble Restore 1-30
FJ1 - FJ30
R1 - R0
Restore Code
3 373 001 - 3 373 030
Fire Test End
FK0
Test 0
Test Code
1 604 000
Fire Restore/Clean-Me Restore
FR1-FR30
R1 - R0
Restore Code
3 110 001 - 3 110 030
Note: These reports are sent for Notification Appliance Circuits that are programmed for releasing operation.
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...