Programming
P/N 151204
4-17
4.3
Programming Options
Table 4-4 list all the programming options and the items that can be modified within those
programming option menus.
Note:
Programming options that have a # in the Programming Options column have multiple programmable
components. See Section 4.1.2 for additional information.
Table 4-4: Programming Options
Programming
Option
Menu Item
Choices
Default
Comments
Zone (1-30) #
Options
Zone # Location
Programmable through SKSS downloading
software. To program through On-board or remote
annunciator:
1. Press * to activate.
2. Press Up or Down arrow to move through
character set.
3. Press Left or Right arrow to move cursor to
desired character location.
4. Repeat steps 2 and 3 until location name is
entered.
5. Press Enter when the desired location name is
complete.
Zone # Type
Not Used
Fire
Waterflow
Supervisory
Undefined
Heat
Cold
Water
AC Delay
Will generate an AC Trouble for either an open or
shorted input. The report to the receiver will be
delayed until the AC Delay timer expires. (See
Section 4.2.10 for AC Delay Time programming.)
Ext. Reset
A shorted input will reset active alarms. This type
of zone is local only. No troubles will be reported
to the central station receiver.
Ext. Silence
A shorted input will silence alarms and troubles.
This type of zone is local only. No troubles will be
reported to the central station receiver.
Zone # Local
No
Zone will report when activated.
Yes
Local Zone, will not report when activated.
Zone # Disable
No
Zone cannot be bypassed.
Yes
Zone can be bypassed.
Zone # Response
1 Sec
4 sec
16 sec
40 sec
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...