
0
7 8
6
5
4
3
2
1
9
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
SILENT KNIGHT CONTROL PANELS ONLY
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
47 K EOL
RESISTOR
ELR-47K
MODULE
47 K EOL
RESISTOR
ELR-47K
H
L
9
8
7
6
5
4
3
2
1
0
TENS
ONES
ADDRESS
LOOP
0
2
4
6
8
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
K200-13-00
2
I56-2730-002
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
C0809-01
7550 Meridian Circle
Maple Grove, MN 55369-4927
763-493-6455; 800-328-0103
Fax: 763-493-6475
http://www.silentknight.com
© 2006 Silent Knight
2/06