Honeywell Silent Knight IDP-Monitor-2 Скачать руководство пользователя страница 1

Mounting

Mounts directly to 4˝ square electrical boxes (see Figure 
2A). The box must have a minimum depth of 21/8˝. 
Surface mounted electrical boxes (SMB500) are available 
from Silent Knight.

Wiring

NOTE:

  All wiring must conform to applicable local 

codes, ordinances, and regulations. This module is in-
tended for power limited wiring only.
1.  Install module wiring in accordance with the job draw-

ings and appropriate wiring diagrams.

2.  Set the address on the module per job drawings.
 

Note: Monitor module L (using terminals 6 and 7) re-
sponds at the address set on the code switches. Monitor 
module H (using terminals 8 and 9) will automatically 
respond at the next higher address. For example, if the 
code switches are set to 76, module L will respond at 
address 76 and module H will respond at address 77. 
Use caution to avoid duplicate addressing of modules 
on the system.

3.  Secure module to electrical box (supplied by installer), 

as shown in Figure 2A.

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

K200-13-00 

I56-2730-002

IDP-Monitor-2 

Dual Monitor Module

INSTALLATION AND MAINTENANCE 

INSTRUCTIONS

Before Installing

This information is included as a quick reference instal-
lation guide. Refer to the control panel installation man-
ual for detailed system information. If the modules will 
be installed in an existing operational system, inform the 
operator and local authority that the system will be tem-
porarily out of service. Disconnect power to the control 
panel before installing the modules.

NOTICE:

 This manual should be left with the owner/

user of this equipment.

General Description

The Dual Monitor Module is intended for use in intel-
ligent, two wire systems. It provides two independent 
2-wire initiating device circuits (IDC), at two separate, 
consecutive addresses. It is capable of monitoring nor-
mally open contact fire alarm and supervisory devices, or 
either normally open or normally closed security devices. 
The module has a single panel controlled red LED.

Compatibility Requirements

To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel 
(list available from Silent Knight).

Figure 2A.

Module mounting:

Figure 2B: 

Specifications

Normal Operating Voltage:  15 to 32 VDC
Maximum Current Draw: 

5.7 mA (LED on)

Average Operating Current:  750µA (LED flashing)
EOL Resistance: 

47K Ohms

Max. IDC wiring resistance:  1,500 Ohms
Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4

1

/

2

˝ H x 4˝ W x 1

1

/

4

˝ D  

 

(Mounts to a 4˝ square by  

 

2

1

/

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

Figure 1. Controls and Indicators:

C0157-00

C0156-00

C0218-01

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

0

1

2

3

4

8

7

6

5

9

ON

ES

AD

DR

ES

S

TE

NS

1 0

2

3

4

5

6

7

8 9

1 0

2

3

4

5

6

7

8 9

Отзывы: