NOTICE:
This manual should be left with the owner/
user of this equipment.
GENERAL DESCRIPTION
The IDP-Control-6 Six Circuit Supervised Control
Module is intended for use in an intelligent alarm sys-
tem. Each module is intended for switching applications
involving AC, or DC which require wiring supervision. A
common SLC input is used for all modules. Each module
has its own address. A pair of rotary code switches is
used to set the address of the first module from 01 to 94.
The remaining modules are automatically assigned to the
next five higher addresses. Provisions are included for
disabling a maximum of three unused modules to release
the addresses to be used elsewhere. Each module also
has panel controlled green LED indicators. The panel can
cause the LEDs to blink, latch on, or latch off. In order
to synchronize strobes, horn/strobes, and speaker/strobes,
a SYNC-1 accessory card (sold separately) must be used
with the IDP-Control-6. See the SYNC-1 installation
manual for details on how to install.
BEFORE INSTALLING
If the modules will be installed in an existing operational
system, inform the operator and local authority that the
system will be temporarily out of service. Disconnect the
power to the control panel before installing the modules.
This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the
body. The housing cabinet should be metallic and suit-
ably grounded.
K200-17-00
1
I56-2734-003
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
IDP-Control-6 Six Circuit
Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current:
2.25 mA
Alarm Current:
35 mA (assumes all six relays have
been switched and all six LEDs
solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
–10°C to 55°C
Humidity:
10 to 85% Non-condensing
Dimensions:
6.8˝ H x 5.8˝ W x 1.25˝ D
Accessories:
IDP-ACB Cabinet and chassis
Wire Gauge:
12-18 AWG
Max. NAC Circuit
Wiring Resistance:
40 Ohms
Power Rating Per Circuit: 63 W @ 70.7 VAC; 50 W @ 25 VAC
Table 1:
CURRENT RATING
MAXIMUM VOLTAGE
LOAD DESCRIPTION
APPLICATION
3 A
30 VDC
Resistive
Non-coded
2 A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-coded
.9 A
125 VDC
Resistive
Non-coded
.5 A
30 VDC
Inductive (L/R=5ms)
Coded
1 A
30 VDC
Inductive (L/R=2ms)
Coded
.3 A
125 VAC
Inductive (PF=.35)
Non-coded
1.5 A
25 VAC
Inductive (PF = .35)
Non-coded
.7 A
70.7 VAC
Inductive (PF=.35)
Non-coded
2 A
25 VAC
Inductive (PF=.35)
Non-coded
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed)
state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communi-
cate with the panel before connecting circuits controlled by the module.
(7) 1
×
4 Terminal
Blocks
(2) 1
1
/
4
˝ (32mm)
Stand offs
(15) Large Shunts
(4) Machine Screws
(5) Short Power
Supply Jumpers (2) Small Shunts
(2) Nuts
(2) EOL Relay
Connector
Assemblies
(6) 47k Ohm
End of Line
Resistors
(1) Long Power Supply Jumper
C0202-01
Included: