41
SERIES 3000 MKII TECHNICAL MANUAL
S3KMKIIMAN_MAN0878_Issue 6_01/2014
21.3 Main unit UL/CSA hazardous area nameplate
21.4 Main unit ATEX/IECEx hazardous area nameplate
Honeywell Series 3000 MkII
Honeywell Analytics Ltd. Poole, Dorset, UK BH17 0RZ
Gas Detector for use in Haz. Loc. as to Fire, Electrical Shock
and Explosion Hazards Only. Associated Apparatus - Read
manual and install as per Control Dwg 3000E3160.
Suitable for use in and provides intrinsically safe circuit.
Cl. I, Div. 1 & 2, Grps. B, C & D; Cl. II, Div. 1, Grps E, F & G; Cl. II
Div. 2, Grps. F & G; Cl. I, Zone 1, Grp. IIB + H2 Haz. Loc. Temp code T4
32VDC MAX Class 2; Pmax =0.6W; Um=250V Tamb. -40°C to +55°C.
Entity Parameters
: Uo=5.88V;Io=0.124A;Po=0.183W;Lo=1mH;Co=10uF
5N80
WARNING:
To Reduce The Risk Of Ignition Of Hazardous
Atmospheres, Disconnect The Equipment From The Supply
Circuit Before Opening Enclosure. Keep Tightly Closed When
in Operation. Conduit Runs Must Have a Seal Fitting
Connected Within 18 in Of The Enclosure.
WARNING:
Substitution Of Components May Impair
Intrinsic Safety
Avertissment
: La Substitutution
De Composants Peut Compromettre La Securite Intrinseque.
[Exia]
Model No: S3KXX2 S/N :
Made in Korea
Honeywell Series 3000 MkII
Honeywell Analytics Ltd. Poole, Dorset, UK BH17 0RZ
Read Manual prior to use.
Temp. Code T4 32Volts DC. Class 2, Pmax=0.6W, Um=250V
Tamb.-20
℃
To +55
℃
0344
Entity Parameters
Uo=5.88V;Io=0.124A;Po=0.183W;
Lo=1mH; Co=10uF
Model No : S3KXX2 S/N :
II 2 (1) GD Ex d [ia IIC Ga] IIB + H2 T4 Gb
Ex t [ia IIIC Da] IIIB T135
℃
Db
DEMKO 07 ATEX 0709149X
IECEx UL 11.0011X
Ex d [ia IIC Ga] IIB + H2 T4 Gb
Ex t [ia IIIC Da] IIIB T135
℃
Db
Made in Korea