background image

Basic Accessories 

4 Basic Accessories 

 

 

 

Mounting Plate SC110 

 

 

 

Movable Mounting Kit SC111 

 

 

 

 

 

 

Keyhole Protection Kit SC112 

 

 

Spacer for Keyhole Protection Kit SC118 

 

 

 

Test Transmitter SC113 

 

External Test Transmitter SC115 

 

 

 

 

 

 

Recess Mounting Box SC116 

 

 

 

 

 

Floor Mounting Box SC117 

 

 

 

 

 

 

Armored Cable Kit (8 wires) SC114 

 

 

 

 

 

- 6 - 

Содержание SC100

Страница 1: ...the best use of the product please read the User Guide carefully before using the product Keep the User Guide at an easily accessible place and make it available to the next user 2010 Honeywell International Inc All rights reserved http www security honeywell com Document 800 04996 Rev A ...

Страница 2: ......

Страница 3: ...in the structure itself which may cause nuisance alarms Bells Human activity Do not apply the detectors close to the bells Or apply a piece of tape on the bell to suppress the overtones generated in the frequency range of the detectors Apply carpet or vibration damping material on vaults and under safes placed on concrete or marble floors Regular maintenance and inspection at least annually by the...

Страница 4: ......

Страница 5: ...F IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the product s it sells may not be compromised or circumvented that the product s will prevent ...

Страница 6: ......

Страница 7: ...inets 10 Document Cabinets 10 Gates 11 Hatches and Chests 11 6 Installation 12 Mounting the Detector 12 Opening the Detector 12 Mounting on Steel 12 Mounting on Stainless Steel or Hardened Steel 13 Mounting on Concrete 14 Mounting the Accessories 15 The Movable Mounting Kit SC111 15 The Keyhole Protection Kit SC112 15 The Spacer for Keyhole Protection Kit SC118 16 The Armored Cable Kit SC114 16 Th...

Страница 8: ...ening the Detector 12 Figure 6 2 Drill Plan 12 Figure 6 3 Mounting Plate SC110 13 Figure 6 4 Movable Mounting Kit SC111 Components 15 Figure 6 5 Keyhole Protection Kit SC112 Components 15 Figure 6 6 Spacer for Keyhole Protection Kit SC118 Components 16 Figure 6 7 Armored Cable Kit SC114 Components 16 Figure 6 8 Test Transmitter SC113 Components 16 Figure 6 9 External Test Transmitter SC115 Compone...

Страница 9: ...Honeywell iii Tables Table 2 1 Application Settings 2 Table 9 1 Remote Test 23 ...

Страница 10: ......

Страница 11: ...bration Detector SC100 and related accessories Chapter 7 Settings shows how to configure sensitivities and other settings on Seismic Vibration Detector SC100 base Chapter 8 Connecting the Detector introduces how to wire and connect Seismic Vibration Detector SC100 to the protected zone Chapter 9 Test introduces the tests of the Seismic Vibration Detector SC100 Chapter 10 Technical Specifications i...

Страница 12: ...r SC100 is designed to detect any known attack tool on Vaults Vault Doors Strong Room Vaults Modular Vaults ATMs Night Deposit Safes Free Standing Safes Gates Hatches Chests Other objects with a solid structure According to the vibration characteristics of the application constructions sensitivity required in each sensor and the natural vibrations and ambient noise level in the premises the detect...

Страница 13: ... detection of all known attack tools on Vault Doors Safes ATMs and so on Flat frequency non resonant response sensor for genuine frequency analysis Built in diagnostic tool used to set detector sensitivity in relation to existing noise level DIP switch sensitivity settings adapt to various applications Integrated EOL resistors compatible with various control panels High detection capability due to...

Страница 14: ...ecognize low to medium amplitude signals with long duration like those caused by a thermic lance oxy arc or acetylene torch The medium level detection mode is designed to detect medium to high amplitude and medium to long or intermittent duration signals as caused by mechanical demolition such as hydraulic jack hammer chisel and electric power tools The high level detection mode is designed to det...

Страница 15: ...lector transistor output going into conductive mode upon alarm condition The transistor is protected against overload with a series resistor of 1 38k ohm Note No protection against sabotage attempts with external magnetic fields is needed due to solid state alarm relay Power Supply Block The input circuits are very well protected against electrical interference and high energy electrical surges by...

Страница 16: ... Plate SC110 Movable Mounting Kit SC111 Keyhole Protection Kit SC112 Spacer for Keyhole Protection Kit SC118 Test Transmitter SC113 External Test Transmitter SC115 Recess Mounting Box SC116 Floor Mounting Box SC117 Armored Cable Kit 8 wires SC114 6 ...

Страница 17: ...ctors On each wall On the floor On the ceiling inside the vault On or inside the vault door Figure 5 1 Planning Vaults Protection The Mounting Plate SC110 the Recess Mounting Box SC116 and the Floor Mounting Box SC117 can be used to mount the detectors in the vaults It is recommend mounting detectors at least about 1 80m high to keep clear from lockers The sensitivity of the detectors can be set t...

Страница 18: ...stalling the detectors in an existing vault Module Vaults must be bolted and welded together to get a reasonable detection range One maximum module width is 1000mm and length is 6500mm can be covered on the other side of a welded corner Detector mounted on the centre of one module can cover 5 adjacent modules at most Figure 5 3 Detector mounted on the center of one modular vault Detector mounted o...

Страница 19: ...e to the dispenser opening On or inside the door Figure 5 6 Planning Night Safe Deposit Box Protection On or inside the door Close to the dispenser opening Rubber Pad Reduce the noise created by the falling cash boxes when deposited The Movable Mounting Kit SC111 or the Keyhole Protection Kit SC112 and the Armored Cable Kit SC114 can be used when mounting detectors on the safes Free Standing Safes...

Страница 20: ... the Outside of the Safe Detectors are better protected when mounted inside and detectors mounted outside will have a deterring effect The Movable Mounting Kit SC111 and the Keyhole Protection Kit SC112 have the advantage of forcing the staff to handle the alarm installation properly It prevents the staff forgetting to remove keys or properly closing the safe doors as well as blocking the keyhole ...

Страница 21: ...nd mounting the detector on the upper part of the frame into which the vertical rods are welded A weather protection box which can purchase from an electric wholesaler should be used to protect the detector from moisture The detector shall be in direct metallic contact with the gate by using screws or welded mounting plate Hatches and Chests For protection of Hatches and Chests normally one detect...

Страница 22: ...at and smooth steel surface both Drill Plan see Figure 6 2 Drill Plan and Detector Base see Figure 2 1 Detector Description can be used to mark the mounting holes Figure 6 2 Drill Plan Note Please remove the drill plan after mounting holes have been drilled C A A B Detector SC100 mounting hole C Test Transmitter SC113 mounting hole Note The drill plan shall be removed after all of the mounting hol...

Страница 23: ... and should be welded on the mounting surface first Figure 6 3 Mounting Plate SC110 UPSIDE F G C D E A B This orientation is used for mounting on concrete A B Detector SC100 mounting holes C D Test Transmitter SC113 locating hole E Mounting Plate SC110 mounting hole F G Welding Slots UPSIDE DOWN F G C D E A B This orientation is used for mounting on stainless steel or hardened steel Refer to the s...

Страница 24: ...the Mounting Plate SC110 and the anchor if the M6 anchor cannot reach the solid concrete 4 Attach the Mounting Plate SC110 into the outline marked and then through the center hole insert M6 50mm screw into M6 anchor in the wall 5 Tighten M6 50mm screw but do not fix the Mounting Plate SC110 on the concrete surface and make sure the mounting plate does not expand either Note The Mounting Plate SC11...

Страница 25: ... on which Detector SC100 is positioned during non armed time and one Night position plate mounted on the protected surface on which Detector SC100 is positioned during armed time The figure below shows the components of the Movable Mounting Kit SC111 For more information please refer to Movable Mounting Kit SC111 User Guide Figure 6 4 Movable Mounting Kit SC111 Components Mounting Plate Day Positi...

Страница 26: ... for checking the proper mounting wiring and function of the detector and it should be mounted inside of the detector about how to mount the Test Transmitter SC113 please refer to Mounting the Detector on page 12 Figure 6 8 Test Transmitter SC113 Components The External Test Transmitter SC115 The SC115 External Test Transmitter is a range test transmitter developed to generate a simulated attack s...

Страница 27: ...Plate Mounting Box The Floor Mounting Box SC117 The Floor Mounting Box SC117 is designed to provide an easy way to recess the detector in the floor and protect the detector from external destruction The figure below shows the components of the Floor Mounting Box SC117 For more information please refer to The Floor Mounting Box SC117 User Guide Figure 6 11 Floor Mounting Box SC117 Components Floor ...

Страница 28: ...lts ON Noise indicator ON Glow OFF ON Low sensitivity setting Gnoisy ON ON Noisy environment sensitivity setting Factory default settings are shown in grey Note Any change of DIP switch 3 will cause an alarm Any change of DIP switch 3 must be followed by a power off sequence of 5 seconds The Noise LED will light or flash intensively if the noise level external or internal is too high Reduce the se...

Страница 29: ...block only one EOL value can be set Other EOL resistor values can be used by removing all jumpers on the EOL jumper field and wire new resistors directly on the terminal block J19 J20 Settings No Jumper Jumper J19 Terminal 8 Spare Terminal Terminal 8 Alarm O C Output J20 Connect SC111 SC112 to the loop Normal Close Factory default settings are shown in grey J1 Setting J1 is used for remote test an...

Страница 30: ... the terminal block Note The open collector alarm output terminal 8 will be active low during alarm 5 Connect the detector to the panel according to the actual applications See Figure 8 2 for connecting the detector to a zone configured as Dual End of Line and Figure 8 3 for connecting the detector to a zone configured as Single End of Line Figure 8 2 Alarm and tamper configured to one loop RTI RS...

Страница 31: ... whole test the items below may be used Additional detectors Electric drill and a 6 mm carbide tipped drill bit The Test Transmitter SC113 and External Test Transmitter SC115 Follow the steps below to perform the field test 1 Locate any irregularity in the construction Note The mortar between bricks and blocks should be considered as irregularities 2 Install a detector at one side of the suspected...

Страница 32: ...eptable If the noise led is flickering or is lighting steadily try to find the noise source and remove it Note Always try to remove the source of ambient noise before reducing the detection range Switch off noise LED tool by setting DIP switch 4 in OFF position Set the sensitivity of the detector to an appropriate value Close the detector cover and check for closed loop condition of the tamper loo...

Страница 33: ...erminal 10 on the terminal block to start the test A successful remote test will be acknowledged by an alarm from the detector within 1 second 2 3 Complete test with Test Transmitter SC113 including mounting check Connect Test Transmitter SC113 to J1 red cable to pin 2 and black cable to pin 3 Apply an active low 0 volt to terminal 10 on the terminal block to start the test A successful remote tes...

Страница 34: ...en Collector Active low during alarm Ri 1 38 kΩ Alarm Hold Time Approx 2 5 sec Sabotage Protection Pry off and Cover Switch 30 VDC 100 mA Low Supply Voltage Alarm 6 5 VDC Temperature Alarm 85 C 5 C Internal Functional Alarm Stainless steel drill shield Sabotage and fault functions will cause the alarm relay to drop Inputs Remote test of detector mounting and detector function or Remote test of det...

Страница 35: ......

Страница 36: ...ty de Honeywell Security Group Via della Resistenza 53 59 20090 Buccinasco Italia Tel 39 0 248 880 51 www honeywell com Per ulteriori informazioni Fax 39 0 248 880 55 33 Email info hsce italia honeywell com www honeywell com security it Honeywell Security Group Ampèrestraat 41 1446 TR Purmerend Nederland Tel 31 0 299 410200 www honeywell com Voor meer informatie Fax 31 0 299 410201 Email intrusion...

Отзывы: