4.2.4 J1 Remote Test Settings 

13. Attach the detector base on Mounting Plate SC110 and 

then use the two M4

×

8mm screws provided to fix it. 

 

 

14. Wire and configure the detector (see 

“4. Wirings and 

Settings”

), and then use the top screw to fix the 

detector cover properly.

 

 

 

 

 

Position Function 

Method 

Result 

 

No test 

Connect jumper to J1 pin 1 only. 

 

1-2 

 

Electronics test 

Connect jumper to J1 pin 1 and 2; 
Apply 0 volt to terminal 10 on the terminal 
block (see

 Figure 6

) to start the test. 

A successful remote test will be 
acknowledged by an alarm from 
the detector within 1 second. 

2-3 

 

Complete test 
including mounting 
check 

Connect Test Transmitter SC113 to J1 (black 
cable to pin 2 and red cable to pin 3); 
Apply 0 volt to terminal 10 on the terminal 
block (see 

Figure 6

) to start the test. 

A successful remote test 
including mounting check will be 
acknowledged by an alarm from 
the detector within 1 second. 

4.  Wirings and Settings 

Wirings and settings are configured on detector base. All function modules on the detector base are shown as below.  

Figure 5 Detector Base 

 

* Factory default settings are shown in grey. 

J1 

5. Maintenance 

DIP Switches 

Noise LED 

Check the detector mounting and functions regularly (once a year at least). 

Tamper Switch 

Note:

 Connect Terminal9 to low level (<0.6VDC), the sensitivity of detector will be reduced to about 1/8 of original level. 

J19 

EOL Jumpers 

J20 

6. Technical Specifications 

Terminal Block 

Power Requirements

 

Supply Voltage 

8 ~ 16 VDC, nominal 12 VDC 

Current Consumption (quiescent) 

Typical 3 mA @ 12 VDC 

Current Consumption (alarm) 

Typical 2 mA @ 12 VDC 

Voltage Ripple 

100Hz, 

10% of nominal voltage 

Step Change 

Unom +/- 25% 

Slow Change of Supply Voltage 

Unom +/- 25% 

Warm-up Time 

< 5 sec 

Sensitivity 

Adjustable Sensitivity 

4 levels by DIP Switches 

Reduced Sensitivity (Maintenance, Service) Input 

Active low (terminal 9) 

 0.6 VDC 

Detection Radius (Thermal Tools) on Concrete K350 

5 m 

Detection Radius (Thermal Tools) on Steel 

5 m 

Alarm Outputs

 

Solid State Relay SPDT (Change Over) 

30 VDC / 100 mA / typical Ri=25 

 

Transistor Open Collector 

Active low during alarm / Ri=1.38 k

 

Alarm Hold Time 

Approx. 2.5 sec 

Sabotage Protection

 

Pry-off and Cover Switch

 

30 VDC / 100 mA 

Low Supply Voltage Alarm * 

< 6.5 VDC 

Temperature Alarm * 

+85°C ± 5°C 

Internal Functional Alarm* 

Stainless steel drill shield 

* Sabotage and fault functions will cause the alarm relay to drop. 

Inputs

 

Remote test of detector mounting and detector function or 
Remote test of detector electronics only. 

Active low 

 0.6 VDC, test duration < 1 sec 

Reduced Sensitivity (maintenance, service) Input 

Active low 

 0.6 VDC, duration  = as long as active low 

Sensitivity reduction to 12.5 % 

Installation Tool 

A noise and alarm indicator is incorporated to support sensitivity setting. 

Environmental Conditions

 

Maximum Humidity 

95% RH (non-condensing) 

Operation Temperature 

-40°C ~ +70°C 

Storage Temperature 

-50°C ~ +70°C 

Environmental Class (VdS) 

III 

Housing Protection Category 

IP43 IK04 

Housing

 

Dimensions (H x W x D) 

80 mm x 60 mm x 21 mm 

Chassis and Cover 

Die-cast metal 

Color 

RAL7035 (light grey) 

Weight 0.228kg 

4.1 Wirings 

4.1.1 Terminal Block Wiring 

The wirings should be connected to the terminal block first, and then should be connected to the panel. 

Figure 6 Terminal Block Wiring 

 

Note:

 The open collector alarm output 

(terminal 8) will be active low during alarm. 

4.1.2 Panel Wiring 

According to the different terminal block wirings, there are two ways to connect the detector to the panel. 

Alarm and tamper configured to one loop 

Alarm and tamper configured to two loops 

RTI

RSI

S/OC

T2

T1

C

NC

V+

NO

0V

Z1

COM

Tamper

RT

Alarm

J20

RA

 

Connected to a zone configured as Dual-End-of-Line 

RTI

RSI

S/OC

T2

T1

C

NC

V+

NO

0V

Tamper

RT

Alarm

J20

Z1

COM

Z2

 

Connected to a zone configured as Single-End-of-Line 

Detector 

Detector 

Note: 

When this wiring 

diagram is used, RT still 
can be used for tamper 
loop, but the jumper on 
RA needs be removed 
and the external EOL 
resistor has to be 
connected to alarm 
loop. 

External EOL  
Resistor 

Panel 

Panel 

4.2 Settings 

4.2.1 DIP Switch Settings 

 

ON 
OFF 

Sensitivity Settings 

Application Settings 

Noise LED 

 1 

 

 

 

G

high

 

off 

off  High sensitivity setting 

off 

ATMs/ Night deposit safes 

off 

Noise indicator OFF 

G

normal

 

on 

off  Normal sensitivity setting 

on 

Safes / Vaults 

on 

Noise indicator ON 

G

low

 

off 

on  Low sensitivity setting 

 

 

 

 

G

noisy

 

on 

on  Noisy environment sensitivity setting 

 

 

 

 

 

7. Certifications and Approvals 

8. Ordering Information 

SC100 Seismic Vibration Detector meets approvals as 
below: 

  NF&A2P Type 3 

  IMQ Type 3 (Pending) 

 UL 

(Pending) 

 ULC 

(Pending) 

 CE 

 CCC 

  VdS G 110004 class C 

Mounting Plate 
Movable Mounting Kit 
Keyhole Protection Kit 
Test Transmitter 
1.8m Armored Cable Kit (8 wires) 
External Test Transmitter 
Recess Mounting Box 
Floor Mounting Box 
Spacer for Keyhole Protection Kit 

SC110 
SC111 
SC112 
SC113 
SC114 
SC115 
SC116 
SC117 
SC118

 

* Factory default settings are shown in grey.

 

Notes:

 

1.  Any change of DIP switch 3 will cause an alarm. 
2.  Any change of DIP switch 3 must be followed by a power-off sequence of 5 seconds. 
3.  The Noise LED will light or flash intensively if the noise level (external or internal) is too high. Reduce the sensitivity with DIP switch 

1 and 2 until the Noise LED turns off. 

4.  When scratching the surface of the protected object lightly, the Noise LED will turn on as a confirmation of detection. 
5.  In case of alarm, the Noise LED will flash with 5 Hz, appx. 2.5 seconds. 
6.  Turning off the Noise LED by DIP switch 4 will reduce current consumption. 

9. Shipping List 

4.2.2 EOL Jumper Settings 

Description

 

Quantity

 

SC100 Seismic Vibration Detector 

Screw M4x8mm 

Cable Strap 

Drill Plan 

Two-way Jumper Link 

Installation Guide 

Jumper Position 

EOL 

Value 

1-2 

1K 

2-3 2.2K 
4-5 4.7K 

TAMPER 

(RT) 

5-6 5.6K 
1-2 

1K 

2-3 2.2K 
4-5 4.7K 

ALARM 

(RA) 

5-6 5.6K 

 

* Factory default settings are shown in grey.

 

Notice for Installation Guide 

Pictures in the manual are for reference only. Please see the actual items. 
The products will be updated and the information shall not be distributed. 
Please read the book before operation and keep it properly for future use. 
The manual has been reviewed and the accuracy is guaranteed. If there is any uncertainty or controversy, please refer to the final explanation of 
Honeywell. Honeywell does not take any responsibility for any consequences caused by misunderstanding of the manual or improper operations.

 

Notes:

  

1.  Refer to Control Panel manual for proper EOL selection. 
2.  For each block, only one EOL value can be set. 
3.  Other EOL resistor values can be used by removing all jumpers on the EOL jumper field and wire new resistors directly on the 

terminal block. 

 

4.2.3 J19/J20 Settings 

 

No Jumper 

Jumper 

J19 

Terminal 8 = Not Used 

Terminal 8 = Alarm O/C Output 

J20 

Connect SC111/SC112 to the loop 

Normal Close 

Honeywell 

 

           * Factory default settings are shown in grey. 

© 2010 Honeywell International Inc. 

www.honeywell.com/security

 

Document 800-04805 Rev. C 

Отзывы: