IRD 1010

Flame monitoring device for yellow- or blue-
burning oil flames

INTRODUCTION

The IRD 1010 is employed to monitor the flame of an oil
burner. This flame monitoring device should be connected
to a Satronic oil burner control box. Monitoring is based on
the infra-red flicker principle, in other words, the flickering
infra-red light of the flame is detected. The steady radiation
from, for example, the glowing refractory layer on the inside
of the boiler, has no effect on the detector.  The IRD 1010
replaces the models IRD 910, 911 and 911 vi. If exchanging
the units, care must be taken to connect them correctly (see
page 3).

TYPES AVAILABLE (also see page 4, Variants)

Item no.

Designation

16501

Flicker detector IRD 1010 right

16502

Flicker detector IRD 1010 end-on

16503

Flicker detector IRD 1010 left

The infra-red flicker detector is suitable for use with the
following control boxes:

IRD 1010

DKO 970, 972, 974, 976
DKW 974, 976
DMO 976
TF 801, 802.1, 804
TF 830.1, 832.1, 834.1, 834E.1, 834.2, 836
TF 844, TF 974, 976
MMD 900, 900.1,
TTO 872, 876
MMO 872, 876
TMO 720-4

CONSTRUCTIONAL FEATURES

The infra-red sensor and the pre-amplifier are hermetically
sealed in glass and along with the electronics form an
integrated unit in the flame detector. Wiring is by way of a
plug connection. The sensitivity control and two LED’s for
indication of the flame signal are situated on the rear of the
flicker detector.

Infra-red flicker detector

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)

Nominal current input

approx. 4 mA

Power consumption

1 VA

Ambient temperature

-20

°

 C to +60

°

 C

Insulation standard

IP 41

Mounting attitude

any

Weight

40 g

Flame viewing attitude

side-on or end-on according
to type

Spectral response

800 - 1100 nm

(with daylight filter)

maximum 950 nm

Frequency range

15 Hz.... 250 Hz (-12 dB)

Sensitivity adjustment
range

approx. 1 : 20 (26 dB)

Switch-on delay

< 3.5 sec.

(after connecting
operating voltage)
Response time

< 0.1 sec.

Cut-out time

< 1 sec.

Содержание Satronic IRD 1010

Страница 1: ...ector is suitable for use with the following control boxes IRD 1010 DKO 970 972 974 976 DKW 974 976 DMO 976 TF 801 802 1 804 TF 830 1 832 1 834 1 834E 1 834 2 836 TF 844 TF 974 976 MMD 900 900 1 TTO 872 876 MMO 872 876 TMO 720 4 CONSTRUCTIONAL FEATURES The infra red sensor and the pre amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame det...

Страница 2: ...reduced In addition care should be taken that the detector is not subjected to unusually harsh vibration and receives no hard knocks COMMISSIONING AND MAINTENANCE During commissioning and after servicing the flame monitoringsystemshouldbecheckedforfaultlessoperation as follows 1 Check that the detector is connected properly Wrong connectionsarearisktosafety andcouldcausedamage to the detector unit...

Страница 3: ...ibletodetector directlyorreflection Correct by preventing direct sight of ignition spark d Interference from ignition cable lay cables some distance apart or possibly screen the detector 2 NoindicationfromLED safterestablishmentofflame a Incorrect or faulty wiring b Sensitivity set too low c Detector positioned wrongly receives no light d Detector or viewing window dirty e Defective detector IRD 1...

Страница 4: ... flange Holder M74 59074 Connectioncable Plug type 3 core cable 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice 35 3 ø20 48 4 5 26 4 7 ø 14 FLICKER DETECTOR IRD 1010 Light entrance from right Item no 16501 104 29 50 44 ø13 5 21 8 Satronic IRD 1010 S...

Отзывы: