2

APPLICATION FEATURES

1. Information system

The information system is microprocessor based and re-
ports on all aspects of burner control box operation and
flame supervision. It informs continuously about the actual
programming sequence the unit is just performing. Besides
monitoring of the programming sequence it also allows to
identify errors during start-up of operation without any
additional testing devices. The automatically performed
diagnosis is a valuable tool which facilitates service/
maintenance work and therefore saves costs. The analyses
of the error cause can be done directly on stage or if not
possible afterwards as the lock out reason is stored in a non-
volatile lock out mode memory.
The information system communicates with the outside
world using a LED (the used Flash-Code is similar to the
Morse-Code). The messages are optically transmitted by a
appropriately flashing LED. Using an additional terminal
(optional), the messages can be recorded and displayed in
easy readable form.

1.1 Programming sequence display

The built-in microprocessor controls not only the pro-
gramming sequence but the information system too. The
individual phases of the programming sequence are
displayed as Flash-Code.
The following messages can be distinguished:

Message

Flash-Code

waiting for

❘   ❘  

.

air proving switch

pre-purge

❘   ❘   ❘

  .

tv1
pre-ignition

❘   ❘   ❘   ❘

  .

tvz

safety time

❚   ❘

  .

ts

delay 2nd stage

❚   ❘   ❘

  .

tv2
running

  _

low mains voltage

❘   ❚   ❚

  _

Description

= short pulse

= long pulse

. = short pause
_ = long pause

1.2 Lock-out diagnoses

In case of a failure the LED is permanently illuminated. Every
10 seconds the illumination is interrupted by a flash code,
which indicates the cause of the error. Therefore the following
sequence is performed which is repeated as long as the unit
is not reset.

Sequence:

illuminated phase

 dark phase

Flash-Code  dark phase

❘   ❚   ❚   ❚   ❚

for 10 sec

 for 0.6 sec

 for 1.2 sec

Error diagnosis

Error message

Flash-Code

Possible fault

lock out

❘   ❚   ❚   ❚   ❚

within lock out safety time

safety time

no flame establishment

stray light

❘    ❘   ❚   ❚   ❚

stray light
during monitored phase,
detector may be faulty

air proving switch

❚   ❚   ❘    ❘   ❘

air proving switch

in closed position

contact welded

air proving switch

❘    ❘    ❘   ❚   ❚

air proving switch does not

time-out

close within specified time

air proving switch

❘    ❘    ❘    ❘   ❚

air proving switch opens

opened

during start or operation

loss of flame

❚   ❚   ❚   ❚   ❘

loss of flame during
operation

Flash-Code for manual lock out
anual/external

❘   ❘   ❚   ❚   ❚  

_

  ❚   ❚   ❚   ❚   ❚

lock out
(see also 3. lock out and reset)

2. Flame detection

The following types of flame detectors are suitable:
– Ionisation probe, temperature resistant material, well

insulated (material and insulation same as for ignition
electrode).

– Infrared-flicker detector type IRD 1020 with mounting

flange M 93 or the UV solid state flame sensor UVD 971.

Flame detection using an ionisation probe is only possible
in conjunction with mains supplies which provides a neu-
tral earth connection.
Connecting the IRD 1020 or UVD 971 the correct wiring
has to be observed.

2.1 Stray light monitoring

The stray light check is performed at the end of the pre-
purge time for thr duration as mentioned in the technical
datas.

DMG 971

Содержание satronic DMG 971

Страница 1: ...nd allows together with a variety of cable entry points utmost flexibility of electrical wiring The DMG 971 is funstionally compatible to MMI 811 and MMI 811 1 Please note Is the DMG 971 to be used to replace the MMI 811 or 811 1 care has to be taken to make sure the air proving switch LW is wired between terminals 4 and 7 and not like on the MMI between 5 and 7 DMG 971 Gas Burner Safety Control F...

Страница 2: ...lse short pause _ long pause 1 2 Lock out diagnoses In case of a failure the LED is permanently illuminated Every 10 seconds the illumination is interrupted by a flash code whichindicatesthecauseoftheerror Thereforethefollowing sequence is performed which is repeated as long as the unit is not reset Sequence illuminated phase dark phase Flash Code dark phase for 10 sec for 0 6 sec for 1 2 sec Erro...

Страница 3: ...t mode If the voltage rises again the controlboxperformsautomaticallyastart upassoonasthe mains voltage is 187 Veff 5 Safety The design and control sequence of the DMG 971 controls will comply with the currently applicable standards and regulations see also TECHNICAL DATA 6 Mounting and electrical wiring Wiring base 3 earth terminals with additional terminal for burner earthing 3 neutral terminals...

Страница 4: ...d lockout appears if the air proving switch LW contact is still in it s closed position e g welded contacts Has the air proving switch LW changed to it s open position in the meantime e g by a run down motor a normal start sequence follows 3 Fault finding The built in information system facilitates the trouble shoot ing in the case of problems occurring during start up or during operation A list o...

Страница 5: ...t stage V2 Solenoid valve 2nd stage LW Air proving switch SA External lock out signal tlw max reaction time for air proving switch tv1 Supervised pre purge time tvz Pre ignition time tz Ignition time total ts Safety time tv2 Delay 2nd stage M Ph N HS ST GW RT EV IS Z V1 V2 SA LW 1 2 3 4 5 6 7 8 9 C A B SV tvz tz ts tv2 tw tv1 tlw rv1 rs 2 6 5 7 4 3 C 9 B 8 1 A rz rv2 Flame amplifier Reset µC Reset...

Страница 6: ...2 Support for IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type 3 core cable 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice VARIATION IRD right HOLDER M 93 FOR IRD left axial 35 3 14 4 5 26 15 1 4...

Отзывы: