Cable length
Flame sensing: 1000 mm max.
Ignition: 500 mm max.
Ignition
Spark voltage:
>
15 kV at 40 pF load
Repetition rate: S4567A 1001: 40 Hz
S4567B 1017: 33 Hz
Spark energy: S4567A 1001: 9
←
As
S4567B 1017: 3
←
As
Max. spark gap: 3.5 mm
Remark
Integrated flame (S4567B 1017 only), alarm and reset opto
couplers with safe separation.
SYSTEM OPERATION
S4567A 1001 and S4567B 1017 (see fig. 3.)
When there is a call for heat a self check time (T
c
) plus waiting
period (T
w
) elapse before built--in igniter and gas valve(s) are
switched on.
The ignition spark ignites gas and resulting flame is detected
by the flame rod.
Ignition is switched off after extended ignition time and flame
establishment.
If flame is not established within the safety time (T
s
), the
ignition control locks out.
If the flame is lost during normal run, the ignition control
repeats start sequence.
Lock- out reset
The ignition control can be reset by depressing the external
reset button.
If a first reset is not succesful, wait at least 15 seconds before
attempting another one.
NOTE 1.: When first starting, the control can be in the
lock--out condition; depress the reset button to free
the controls.
After a manual reset an extended waiting time will
occur.
NOTE 2.: If during normal use the reset button is pressed, the
gas valves drop off and the ignition control starts a
new sequence after releasing the reset button.
Side connection
4
5
L
3
3
1
RS
6
2
LM
N
10K
1K
+
--
5 V
LM -- Limiter
RS -- Reset switch
GV -- Gas valve
GV
Fig. 1. Connection diagram S4567A 1001