INSTRUCTION SHEET
S4560
AUTOMATIC IGNITION CONTROL
MU1R--9086 0009R9--NE
APPLICATION
The S4560 provides automatic ignition and control for burners
in accordance with EN 298.
SPECIFICATIONS
Model
S4560: 220 ... 240 V, 50 Hz.
Suffix A: For atmospheric burners. Non volatile lock out in
accordance with EN 298.
Suffix B: As suffix A except a built in flame indication relay for
modulating applications.
Suffix C: For fan assisted applications. Non volatile lock out in
accordance with EN 298.
Suffix D: As suffix C except a built in flame indication relay for
modulating applications.
Suffix E: As suffix A except lock--out after flame lost during
normal operation.
Suffix P: As suffix A except volatile lock out, reset by
interrupting heat demand.
Suffix Q: As suffix B except volatile lock out, reset by
interrupting heat demand.
Suffix R: As suffix C except volatile lock out,reset by
interrupting heat demand.
Suffix T: As suffix D except volatile lock out, reset by
interrupting heat demand.
Dimensions
See fig. 9.
Ambient temperature
0 ... 60
_
C
Relative humidity
90% max. at 40
_
C (non condensing)
Supply voltage
Line voltage, 220 V (--15%) ... 240 V (+10%), 50 Hz (
¦
2 Hz)
Power consumption
10 VA max.
Electrical rating
Valve(s) output: 1 A max cos
♥
>
0.6
Fan output (Suffix C, D, R and T): 1 A max cos
♥
>
0.6
Alarm output: 1 A max cos
♥
>
0.6
Flame indication relay: 1 A max cos
♥
>
0.6
External ignition transformer: 1 A max cos
♥
>
0.6
All outputs together: 3 A max.
Electrical connection
High tension spark: 2.8 x 0.5 mm spade terminal.
Flame rod and ground: 6.3 x 0.8 or 4.8 x 0.8 mm spade
terminal (depending on O.S. number).
Multiple connector: Molex 3001 series
Timing (depending on O.S. number)
Waiting time (T
w
)/Prepurge time (T
p
): 0 ... 24 s
Safety time (T
s
): 0 ... 250 s
Stabilization time (T
stab
): 0 ... 15 s
Flame sensing
Flame sensing is based on the rectification principle.
Minimum flame current: 0.7
←
A
Response time ”ON”: < 200 ms (at 2
←
A flame current)
Response time ”OFF”: < 1 s
Maximum cable length: 1 m
Not protected against electrical shock.
Ignition
Integral electronic spark generator
Spark voltage: 12 kV at 40 pF load
Repetition rate: 12 Hz
Maximum cable length: 1 m
Not protected against electrical shock.