Operation

Automatic Transfer Switch Owner’s Manual

15

Section 4: Operation

Functional Tests and Adjustments

Following transfer switch installation and interconnection,
inspect the entire installation carefully. A competent,
qualified electrician should inspect it. The installation
should comply strictly with all applicable codes,
standards, and regulations. When absolutely certain the
installation is proper and correct, complete a functional
test of the system. 

IMPORTANT: Before proceeding with functional tests,
read and make sure all instructions and information in
this section is understood. Also read the information and
instructions of labels and decals affixed to the switch.
Note any options or accessories that might be installed
and review their operation.

Manual Operation

See 

Figure 4-1

. A manual handle (B) is shipped with the

transfer switch manual. Manual operation must be
checked BEFORE the transfer switch is operated
electrically. To check manual operation, proceed as
follows:

1.

Verify the generator is in the OFF mode.

2.

Turn OFF both utility (service disconnect circuit
breaker) and emergency (generator main line
circuit breaker) power supplies to the transfer
switch.

3.

Note position of transfer mechanism main contacts
(A) by observing the movable contact carrier arm.
This can be viewed through the long narrow slot in
the inside cover. The top of the movable contact
carrier arm is yellow to be easily identified.

Manual operation handle in the UP position - LOAD
terminals (T1, T2) are connected to utility terminals
(N1, N2).

Manual operation handle in the DOWN position -
LOAD terminals (T1, T2) are connected to
EMERGENCY terminals (E1, E2).

Close to Utility Source Side

Before proceeding, verify the position of the switch by
observing the position of manual operation handle in

Figure 4-1

. If the handle is UP, the contacts are closed in

the utility (normal) position, no further action is required.
If the handle is DOWN, proceed with Step 1.

1.

With the handle inserted into the movable contact
carrier arm, move handle UP. Be sure to hold on to
the handle as it will move quickly after the center of
travel.

2.

Remove manual operating handle from movable
contact carrier arm. Return handle to storage
bracket.

Figure 4-1. Manual Operation

(000121)

CAUTION

Equipment damage. Perform functional tests in the 
exact order they are presented in the manual. 
Failure to do so could result in equipment damage.

 

(000132)

DANGER

Electrocution. Do not manually transfer under load. 
Disconnect transfer switch from all power sources 
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.

(000122)

CAUTION

Equipment damage. Do not use excessive force while 
manually operating the transfer switch. Doing so could 
result in equipment damage.

 

004399

A

B

Содержание RXSK100A3

Страница 1: ... Service Circuit Breaker RXSM200A3 Service Entrance Rated with Utility Service Circuit Breaker RXSK200A3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW HONEYWELLGENERATORS COM 855 436 4636 Para español visita http www honeywellgenerators com service support owner support Pour le français visiter http www honeywellgenerators com service support owner support SAV...

Страница 2: ...halates and lead which are known to the State of California to cause cancer and birth defects or other reproductive harm To minimize exposure avoid breathing exhaust do not idle the engine except as necessary service your equipment in a well ventilated area and wear gloves or wash your hands frequently when servicing your equipment For more information go to www P65Warnings ca gov ...

Страница 3: ...Fault Current Label 13 Section 4 Operation Functional Tests and Adjustments 15 Manual Operation 15 Close to Utility Source Side 15 Close to Generator Source Side 16 Return to Utility Source Side 16 Voltage Checks 16 Utility Voltage Checks 16 Generator Voltage Checks 16 Generator Tests Under Load 16 Checking Automatic Operation 17 Installation Summary 17 Shutting Generator Down While Under Load Or ...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank ...

Страница 5: ... might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating technique that the manufacturer does not specifically recommend verify that it is safe for others Also make sure the procedure work method or operating technique utilized does not render the equipment unsafe Safety Symbols and ...

Страница 6: ...f the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will result in death or serious injury Automatic start up Disconnect utility power and render unit inoperable before working on unit Failure to do so will result in death or serious injury 000191 DANGER 000119 Equipment ma...

Страница 7: ...before working on utility connections of the transfer switch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will result in death or serious injury 000188 DANGER Electrocution Do not wear jewelry while working on this equipment Doing so will result in death or serious injury 000213 DANGER Electrocution Only author...

Страница 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...

Страница 9: ...h a single phase system when the single phase neutral line is to be connected to a neutral lug and is not to be switched Solderless screw type terminal lugs are standard The conductor size range is as follows This transfer switch is suitable for control of motors electric discharge lamps tungsten filament and electric heating equipment where the sum of motor full load ampere ratings and the ampere...

Страница 10: ...tion against falling rain and sleet are undamaged by the formation of ice on the enclosure Safe Use of Transfer Switch Before installing operating or servicing this equipment read the Safety Rules carefully Comply strictly with all Safety Rules to prevent accidents and or damage to the equipment The manufacturer recommends that a copy of the Safety Rules be posted near the transfer switch Also be ...

Страница 11: ...tal of eight loads Use Priorities A C 1 4 on the SACM as the top priorities then up to four SMMs as Priorities 5 8 Use only select A C priorities on the SACM as the top priorities then use additional SMMs as the remaining priorities A SMM can share a priority with an A C priority on the SACM provided the generator is sized to handle the combined surge load from both appliances Sharing priorities c...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...

Страница 13: ...the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a rigid supporting structure To prevent switch distortion level all mounting points If necessary use washers behind mounting holes to level the unit Open Enclosure See Figure 3 1 First remove outer cover A 1 Remove thumb screw B 2 Slide slot C over retention tab 3 Lower co...

Страница 14: ...d on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applicable codes standards and regulations Knockouts into the transfer switch can be made in the field as needed for entry of power cables and conduit Conduit entry shall maintain the proper wire bending spaces required by Tables 312 6 A and B in the NEC Conduits should be arranged to prov...

Страница 15: ...n insulation rating equal to at least the maximum circuit voltage applied to any conductor within the equipment cable or conduit See NEC 300 3 C 1 Connecting SACM See Figure 3 3 The SACM can control an air conditioner 24 VAC directly Control of Air Conditioner Load 1 Route the thermostat cable from the furnace thermostat to the outdoor air conditioner unit to the transfer switch 2 Connect the wire...

Страница 16: ...t 2 D Air Conditioner 2 E Thermostat 3 F Air Conditioner 3 G Thermostat 4 H Air Conditioner 4 T1 fused Battery Charge N1 fused Utility Sense N2 fused Utility Sense 0 DC Ground 194 12 VDC 23 Transfer Control J 240 VAC 6 3A Fuses A B G H C D E F T1 1 1 1 1 2 2 2 2 T1 N1 N2 0 DC GROUND 194 12 VDC N1 N2 T1 23TRANSFER J T1 N2 0 194 23 N1 006244 ...

Страница 17: ...aining the unit Owner s Manual and transfer switch manual operating handle The 2017 NEC requires that the short circuit current rating of the transfer equipment based on the type of overcurrent protective device protecting the transfer equipment be field marked on the exterior of the transfer equipment For NEC compliance verify the required short circuit current rating of the transfer switch befor...

Страница 18: ...Installation 14 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...

Страница 19: ...s can be viewed through the long narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in the UP position LOAD terminals T1 T2 are connected to utility terminals N1 N2 Manual operation handle in the DOWN position LOAD terminals T1 T2 are connected to EMERGENCY terminals E1 E2 Close to Utility Source Side Before proceedi...

Страница 20: ...B1 to its ON or CLOSED position 4 With an accurate AC voltmeter and frequency meter check the no load voltage and frequency Measure across ATS terminal lugs E1 to E2 E1 to NEUTRAL and E2 to NEUTRAL 5 When certain that generator supply voltage is correct and compatible with transfer switch ratings turn OFF the generator supply to the transfer switch 6 Set the generator main circuit breaker CB1 to O...

Страница 21: ...and start when the utility source power is turned OFF after a five second delay factory default setting After starting the transfer switch should connect load circuits to the standby side after a five 5 second warm up delay Let the system operate through its entire automatic sequence of operation NOTE Timer durations may differ between generators and settings With the generator running and loads p...

Страница 22: ...utility supply to the ATS 2 Verify managed loads are powered and all LEDs illuminate on SACM 3 Press the TEST button on the SACM 4 Verify that all of the connected loads to be shed become disabled 5 After five 5 minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status LED A C 2 is ON 7 After another 15 seconds verify Load A C 3 is...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 Section 5 Drawings and Diagrams Installation Drawings No 0G6832 A 100A SE non SE 150 200A non SE ...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual No 10000012171 A 150 200A SE ...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 Interconnection Drawings No 10000009574 Part 1 of 2 Liquid Cooled Generator ...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual No 10000009574 Part 2 of 2 Liquid Cooled Generator ...

Страница 27: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 23 No 10000009620 SE and non SE Rated ATS 1 of 2 Air Cooled Generator ...

Страница 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual No 10000009620 SE and non SE Rated ATS 2 of 2 Air Cooled Generator ...

Страница 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank ...

Страница 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...

Страница 31: ......

Страница 32: ... Specifications subject to change without notice The Honeywell trademark is used under license from Honeywell International Inc Honeywell International Inc makes no representation or warranties with respect to this product This product is manufactured by Generac Power Systems Inc Waukesha WI 53189 USA Part Number 10000009532 Revision B 03 05 2018 ...

Отзывы: