Honeywell RM7895 Series Скачать руководство пользователя страница 23

RM7890, RM7895 100 Vac

17 . 

If used, remove the bypass jumpers from the low fuel pres-

sure limit and subbase.

18 . 

If a second stage is used, make sure the automatic second 

stage fuel valve(s) opened, and check the lightoff as fol-

lows (otherwise proceed to step 19):

a . 

Open the manual second stage fuel valve(s).

b . 

Restart the system by raising the setpoint of the operat-

ing controller.

c . 

When the first stage burner flame is established, watch 

for the automatic second stage fuel valve(s) top open. 

Observe that the second stage lights off properly.

d . 

Make burner adjustments for flame stability and input 

rating.

e . 

Shut down the system by lowering the setpoint of the 

operating controller. Make sure the burner flame goes 

out and that all automatic fuel valve(s) close.

19 . 

Restart the system by closing the burner switch and/or 

raising the setpoint of the operating controller. Observe 

that the burner flame is established during PILOT IGN, 

within the normal lightoff time specified by the equipment 

manufacturer.

20 . 

Measure the flame signal. Continue to check for the proper 

signal, see Table 10, through the RUN period. Any pulsat-

ing or unsteady readings will require further attention.

21 . 

Make sure all readings are within the required ranges be-

fore proceeding.

NOTE:  Upon completing these tests, open the master switch 

and remove all test jumpers from the subbase termi-

nals, limits/controls or switches .

22 . 

Return the system to normal operation.

Pilot Turndown Test  (All Installations  

Using a Pilot)

Perform this check on all installations that use a pilot. The 

purpose of this test is to verify that the main burner can be lit 

by the smallest pilot flame that will hold in the flame amplifier 

and energize the FLAME LED. If using AMPLI-CHECK™ and 

one megohm per volt meter, the flame signal will fluctuate ev-

ery time the amplifier does a self check.

NOTE:  Low fuel pressure limits, if used, could be open . If so, 

bypass them with jumpers during this test .

1 . 

Open the master switch.

2 . 

Close the manual main fuel shutoff valve(s).

3 . 

Connect a manometer (or pressure gauge) to measure pilot 

gas pressure during the turndown test.

4 . 

Open the manual pilot shutoff valve(s).

5 . 

Close the master switch and start the system with a call for 

heat by raising the setpoint of the operating controller. The 

primary sequence should start and PILOT IGNITION for 

the RM7890 (PREPURGE for the RM7895) should begin. 

6 . 

After the sequence has entered the normal burner run pe-

riod, turn the pilot gas pressure down very slowly, reading 

the manometer (or gauge) as the pressure drops. Stop im-

mediately when the FLAME LED goes out. Note the pres-

sure at this point.

NOTE:  If there is no flame present for the selected Flame 

Failure Response Test (FFRT), the relay module will 

lock out .

a . 

If the Flame Failure Action jumper (see Table 6 or 7, JR2) 

is not clipped: allow the RM7890 to recycle to PILOT IG-

NITION or the RM7895 to recycle through PREPURGE. 

If the Flame Failure Action jumper is clipped: push the 

reset pushbutton and allow the RM7890D to recycle to 

PILOT IGNITION or the RM7895E,F to recycle through 

PREPURGE.

b . 

As the control attempts to relight the pilot, increase the 

pilot pressure immediately until the FLAME LED comes 

on, and then turn it down slowly to obtain a pressure 

reading just above the dropout point or until the flame 

signal increases to approximately 1.25 Vdc. This step 

must be completed within 4 or 10 seconds, depending 

on the selected PFEP, or lockout occurs.

c . 

Turn the pilot back down slightly but not enough to 

cause the FLAME LED to go out. (Keep the pilot gas 

pressure just above the reading noted in step 6 above.)

NOTE:  Step d requires two people, one to open the manual 

main fuel valve(s) and one to watch for ignition .

d . 

With the sequence in the normal burner run mode, make 

sure the automatic fuel valve(s) is open. Smoothly open 

the manual main fuel shutoff valve(s) and watch for 

main burner lightoff.

e . 

If the main flame is not established within five seconds 

or the normal lightoff period specified by the burn-

er manufacturer, close the manual main fuel shutoff 

valve(s) and open the master switch. Then return to step 

6a. If the burner flame is established in the normal ligh-

toff period, proceed to step 10. 

7 . 

Recycle the burner and let the sequence advance to the 

PILOT IGN period for the RM7890; advance to the PRE-

PURGE period for the RM7895.

8 . 

Increase the pilot flame size by increasing its fuel flow until 

a smooth main flame is accomplished.

9 . 

Reposition the flame rod until the pilot flame signal volt-

age is approximately 1.25 to 1.50 Vdc.

10 . 

When the main burner lights reliably with the pilot at turn-

down, disconnect the manometer (or pressure gauge) and 

turn up the pilot gas flow to the level recommended by the 

equipment manufacturer.

11 . 

If used, remove the bypass jumpers from the subbase ter-

minals, limits/control or switches.

12 . 

Run the system through another cycle to check for normal 

operation.

13 . 

Return the system to normal operation.

Ignition Interference Test (All Flame Rods)

Test to be sure that a false signal from a spark ignition system 

is not superimposed on the flame signal.
Ignition interference can subtract from (decrease) or add to 

(increase) the flame signal. If it decreases the flame signal 

enough, it causes a safety shutdown. If it increases the flame 

signal, it can cause the FLAME LED to come on when the true 

flame signal is below the minimum acceptable value.
Start the burner and measure the flame signal with both igni-

tion and pilot (or main burner) on, and then with only the pilot 

(or main burner) on. Any significant difference (greater than 

0.5 Vdc) indicates ignition interference.

 

23 

32-00216-01

Содержание RM7895 Series

Страница 1: ...ument provides installation and static checkout in structions Other applicable publications are Table 1 Other applicable publications Form number Description 65 0249 S7810M Modbus Module 65 0084 Q7800A B 22 Terminal Wiring Subbase Product Data 65 0090 S7800A 2 line VFD Keyboard Display Module Product Data 65 0091 S7810A Data ControlBus Module Product Data 65 0095 S7820 Remote Reset Module Product ...

Страница 2: ...d optional Keyboard Display Module Status of configuration jumpers SPECIFICATIONS Electrical Ratings See Table 2 Voltage and Frequency 100 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 15A maximum type SC or equivalent Environmental Ratings Ambient Temperature Operating 40 F to 140 F 40 C to 60 C Storage 60 F to 150 F 51 C to 6...

Страница 3: ...M7895 Alarm 100 Vac 1A pilot duty 4 RM7890 Alarm 100 Vac 1A pilot duty 4 RM7895 Burner Motor 100 Vac 9 8AFL 58 8ALR inrush 5 RM7890 Unused 5 RM7895 Line Voltage Supply L1 100 Vac 10 15 50 60 Hz 10 b 6 RM7890 Burner Controller and Limits 100 Vac 8A Run 43A inrush b 6 RM7895 Burner Controller and Limits 100 Vac 1 mA 7 RM7890 Unused 7 RM7895 Airflow Interlock 100 Vac 8A run 43A inrush 8 Pilot Valve I...

Страница 4: ...ch Combination A B C D F 4 5A ignition 50 VA Pilot Duty plus 4 5A ignition 180 VA ignition plus motor valves with 660 VA inrush 360 VA open 250 VA hold 2A Pilot Duty 65 VA Pilot Duty plus Motor valves with 3850 VA inrush 700 VA open 250 VA hold Fig 1 Mounting dimensions of RM7890 RM7895 Relay Module and Q7800A Subbase in in mm Fig 2 Mounting dimensions of RM7890 RM7895 Relay Module and Q7800B Subb...

Страница 5: ... Dynamic Self Check R7886A Mb 3 0 sec Gas oil coal Ultraviolet Adjustable Sensitivity C7076 Optical White Dynamic Ampli Check R7851B 0 8 or 3 0 sec Gas oil coal Optical UV Visible Light C7927 C7962 Dynamic Self Check R7851Cb 3 0 sec Gas oil coal Optical UV only C7961 a Flame Failure Response Time FFRT depends on selection of amplifier b Circuitry tests all electronic components in flame detection ...

Страница 6: ...Internal system fault occurred c Main valve terminal is energized when it should be off d No flame present at end of PFEP e Airflow lockout feature is enabled and the airflow switch opens RM7895 f Purge card is not installed or was removed RM7895 only g Purge card is faulty RM7895 only 6 RUN PERIOD a Ignition terminal is energized when it should be off b Internal system fault occurred c Main valve...

Страница 7: ...r information during normal operation or when a safety shutdown or hold occurs First out Annunciation reports the cause of safety shutdown or identifies the cause of a failure to start or continue the burner control sequence with text and numbered code using the optional KDM It monitors all field input circuits including the flame signal amplifier Self Diagnostics add to the First Out Annunciation...

Страница 8: ...c trical separation using insulation at least equivalent to double or reinforced insulation This can be accomplished by either 1 Optically isolating the communication and or remote reset lines from the control cabinet 2 Providing physical separation from the communication and or remote reset lines using electrical conduit and a 204718A Remote Display Cover Assembly or other suitable enclosure that...

Страница 9: ...t the subbase using four no 6 screws not provided NOTE You might receive and error code 101 via KDM check the screws securing the relay to the subbase to check if they are not tight enough re tighten to insure there is no gap between the relay and the subbase Fig 4 Internal block diagram of the RM7890 see Fig 6 for detailed wiring instructions 9 32 00216 01 ...

Страница 10: ... refer to the Specifi cations for the 2 line VFD KDM 65 0090 the 4 line LCD KDM 32 00110 Network Data ControlBus Module 65 0091 or Extension Cable Assembly 65 0131 3 Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage More than one disconnect may be required 4 All wiring must comply with all applicable electrical codes...

Страница 11: ...r equivalent Remote Reset Module 22 AWG two wire twisted pair insulated for low voltage Modbus Module 22 AWG two wire twisted pair with ground Belden 8723 shielded cable or equivalent 13 Vdc full wave rectified transformer power input 18 AWG wire insulated for voltages and temperatures for given application TTW60C THW75C THHN90C The KDM and for remote mounting or communications Data ControlBus Mod...

Страница 12: ...path are free of nonconductive coatings and protected against corrosion on mating surfaces Signal ground KDM Data ControlBus Module Modbus Module Connect the shield at both ends of the daisy chain to earth ground 7 Recommended wire routing a For flame detector leadwires 1 Do not run high voltage ignition transformer wires in the same conduit with the flame detection wiring 2 Do not run scanner wir...

Страница 13: ...dule dust cover flame amplifier flame amplifier signal voltage probes electrical signal volt age probes and electrical connections a Allow an additional two inches 51 mm below the relay module for the flame amplifier mounting b Allow an optional three inch 76 mm minimum to both sides of the relay module for electrical signal voltage probes 3 Make sure subbase wiring does not project beyond the ter...

Страница 14: ...etector to the wiring subbase Capacitance increas es with leadwire length reducing the signal strength The maximum permissible leadwire length depends on the type of flame detector leadwire and conduit The ultimate limiting factor in the flame detector leadwire is the flame signal See Table 10 Fig 8 Electrical panel installation Fig 9 Wall or burner installation Fig 10 Dust cover mounting Fig 11 S...

Страница 15: ... sequence if the relay module verifies voltage fluctuations of 10 15 or fre quency fluctuations of 10 during any part of the operating sequence The INITIATE sequence lasts for ten seconds un less the voltage or frequency tolerances are not met When the tolerances are not met a hold condition is initiated and displayed on the optional KDM for at least five seconds When the tolerances are met the IN...

Страница 16: ...nds into PREPURGE or within the specified purge card timing oth erwise a recycle to the beginning of PREPURGE or lockout occurs depending on how the airflow switch selectable jumper is configured Ignition Trials Pilot Flame Establishing Period PFEP 1 The pilot valve and ignition transformer terminals 8 and 10 are energized The relay module has an intermittent pi lot valve terminal 8 2 Flame must b...

Страница 17: ...lightning and high current protection Equipment Recommended 1 Voltmeter one megohm volt minimum sensitivity set on the 0 to 300 Vac scale 2 Two jumper wires no 14 wire insulated 12 in 305 mm long with insulated alligator clips at both ends An ammeter can replace one of the jumper wires when checking operation of terminals 8 9 or 10 Verify amp draw to the device nameplate General Instructions 1 Per...

Страница 18: ...Ignition spark if ignition transformer is connected to terminal 8 Automatic pilot valve opens if connected to terminal 8 Refer to wiring diagram of system being tested 1 Watch for spark or listen for buzz a Ignition electrodes are clean b Ignition transformer is okay 2 List for click or feel head of valve for acti vation a Actuator if used b Pilot valve 5 3 to 9a Automatic fuel valve s opens If us...

Страница 19: ...or spark or listen for buzz a Ignition electrodes are clean b Ignition transformer is okay 2 List for click or feel head of valve for acti vation a Actuator if used b Pilot valve 6 5 to 9a Automatic fuel valve s opens If using direct spark ignition check the first stage fuel valve s instead of the pilot valve 3 Same as test number 5 If using direct spark ignition check the first stage fuel valve s...

Страница 20: ...a pilot 6 Hot refractory hold in test all installations 7 Ignition interference test all installations using flame rods 8 Flame signal with hot combustion chamber all installa tions 9 Safety shutdown tests all installations See Fig 14 for location of component parts and see Fig 5 or 6 or Q7800 Specifications form 65 0084 for terminal locations Preliminary Inspection When performing the following i...

Страница 21: ...ream from the burner inlet or disconnect power from the auto matic main fuel valve s 4 Close the master switch and start the system with a call for heat by raising the setpoint of the operating controller see Fig 15 or the relay module sequence The sequence should start the ten second INITIATE sequence 5 Let the sequence advance through STANDBY and SAFE START CHECK PREPURGE in the RM7895 Ignition ...

Страница 22: ...l operation 23 Make sure all readings are in the required ranges before proceeding NOTE Upon completing these tests open the master switch and remove all test jumpers from the subbase termi nals limits controls or switches Initial Lightoff Check for Direct Spark Ignition DSI Use this check for gas and oil burners that do not use a pilot immediately following the preliminary inspection Refer to the...

Страница 23: ... relay module will lock out a If the Flame Failure Action jumper see Table 6 or 7 JR2 is not clipped allow the RM7890 to recycle to PILOT IG NITION or the RM7895 to recycle through PREPURGE If the Flame Failure Action jumper is clipped push the reset pushbutton and allow the RM7890D to recycle to PILOT IGNITION or the RM7895E F to recycle through PREPURGE b As the control attempts to relight the p...

Страница 24: ...pi lot cannot ignite e Safety shutdown will occur 5 Observe loss of flame during RUN if Flame Failure Action configuration jumper JR2 is selected for Lockout see Ta bles 6 and 7 a Open the main fuel manual shutoff valve s and open the manual pilot shutoff valve s b Depress the reset pushbutton c Start the system Startup should be normal and the main burner should light normally d After the sequenc...

Страница 25: ...the actual status of the terminal If voltage is detected at the terminal 1 is displayed but if volt age is not present at the terminal 0 is displayed Historical Information Index The relay module has nonvolatile memory that allows it to retain historical information for the six most recent lockouts Each of the six lockout files retains the cycle when the fault occurred the hour of operation when t...

Страница 26: ...roper value INITIATE HOLD Low Line Voltage The LED indicates the burner status POWER and that low line voltage has occurred The burner sequence will not advance into STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner switch or if the operating controller ...

Страница 27: ...output will be de energized after the reset pushbutton is released SAFETY AND SECURITY Physical device protection Device shall be accessible to authorized personnel only In stallation on publicly accessible places is not recommended as this could lead to unwanted and potentially unsafe chang es to device wiring configuration etc It is recommended to lock the device in an enclosed cabinet with acce...

Страница 28: ...nd Maxon To learn more about our products visit ThermalSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell Process Solutions Honeywell Thermal Solutions HTS 1250 West Sam Houston Parkway South Houston TX 77042 ThermalSolutions honeywell com U S Registered Trademark 2019 Honeywell International Inc 32 00216 01 Edition 08 19 Printed in United States ...

Отзывы: