RM7890A,B,C/EC7890A,B 7800 SERIES RELAY MODULES

66-1089—11

10

PRINCIPAL TECHNICAL FEATURES

The RM/EC7890 provides all customary flame safeguard 

functions as well as significant advancements in safety, 

annunciation, and system diagnostics. 

Safety Shutdown (Lockout) Occurs if:

1.

INITIATE PERIOD

a. AC line power errors occurred, see Operation. 

b. Configuration jumpers have been changed (after 

200 hours). 

c. Four minute INITIATE period has been exceeded. 

2.

STANDBY PERIOD

a. Flame signal is present after 240 seconds.

b. Ignition/intermittent pilot valve terminal is energized.

c. Internal system fault occurred.

d. Main valve terminal is energized.

e. Three second (two seconds for EC7890A1037, 

RM7890A1064 and RM7890B1055) Flame Failure 

Response Time (FFRT) Amplifier is installed and 

configuration jumper is selected for relight (see 

Table 3).

3.

SAFE START CHECK (EXCEPT RM7890C)

a. Ignition/intermittent pilot valve terminal is energized.

b. Internal system fault occurred.

c. Main valve terminal is energized.

4.

PILOT FLAME ESTABLISHING PERIOD (PFEP)

a. Ignition/intermittent pilot valve terminal is not 

energized.

b. Internal system fault occurred.

c. Main valve terminal is energized.

d. No flame present at end of PFEP.

5.

RUN PERIOD

a. Ignition terminal is energized.

b. Internal system fault occurred.

c. Main valve terminal is not energized.

d. No flame present and configuration jumper is 

selected for lockout.

e. Pilot valve terminal is not energized.

OPERATION

Sequence of Operation

The RM/EC7890 has the operating sequences listed below; 

see Fig. 2. The RM/EC7890 LED provide positive visual 

indication of the program sequence: POWER, PILOT, FLAME, 

MAIN and ALARM.

Initiate

The RM/EC7890 enters the INITIATE sequence when the 

relay module is powered. The RM/EC7890 can also enter the 

INITIATE sequence if the relay module verifies voltage 

fluctuations of +10/-15% or frequency fluctuations of ±10% 

during any part of the operating sequence. The INITIATE 

sequence lasts for ten seconds unless the voltage or 

frequency tolerances are not met. When the tolerances are 

not met, a hold condition is initiated and is displayed on the 

optional KDM for at least five seconds. When the tolerances 

are met, the INITIATE sequence restarts. If the condition is not 

corrected and the hold condition exists for four minutes, the 

RM/EC7890 locks out. Causes for hold conditions in the 

INITIATE sequence:

a. AC line dropout detection.

b. AC line noise that can prevent a sufficient reading of 

the line voltage inputs. 

c. Brownouts caused by a low line voltage.

NOTE: If a 3.0 second flame failure response amplifier is 

installed and configuration jumper JR2 is intact, the 

RM/EC7890 locks out. JR2 must be clipped.

Standby

The RM/EC7890 is ready to start an operating sequence 

when the operating control input (terminal 6) recognizes a call 

for heat. The burner switch, limits, operating limit control and 

all microcomputer monitored circuits must be in the correct 

state for the RM/EC7890 to continue into the Safe Start 

Check. 

Normal Start-Up Safe Start Check
(Except RM7890C)

The RM/EC7890 verifies that a flame or flame simulating 

condition does not exist and proceeds into the Ignition Trial. If 

a flame or flame simulating condition is present, the 

RM/EC7890 remains in the STANDBY period. RM7890C 

checks its internal components for flame simulating 

conditions.

Ignition Trials 

a. Pilot Flame Establishing Period (PFEP):

(1) The pilot valve and ignition transformer, termi-

nals 8 and 10, are energized. The RM/EC7890 

has an intermittent pilot valve, terminal 8. 

RM7890C closes internal relay contact in the “F” 

lead.

(2) Flame must be proven by the end of the four- or 

ten-second PFEP (30 seconds for 

RM7890A1031) or a safety shutdown occurs.

(3) Once flame is proven, the ignition, terminal 10, is 

de-energized and the main valve, terminal 9, is 

energized. 

(a)The RM7890B1030 finishes the 4- or 10-sec-

ond PFEP before the main valve is energized.

(b)The RM7890A1064, RM7890B1055/

EC7890A1037 with JR1 intact completes 10 

second PFEP, shutting off ignition (Terminal 

10) at 6 seconds. When the JR1 clipped these 

devices complete a 4 second PFEP, shutting 

off ignition (terminal 10) at 2 seconds.

Run

The RM/EC7890 is now in RUN and remains in RUN until the 

controller input, terminal 6, opens, indicating that the demand 

is satisfied or a limit has opened.

maxon.su

Содержание rm7890b

Страница 1: ...ng Instructions 65 0109 Flame Amplifiers for the 7800 SERIES Product Data 65 0131 221818A C Extension Cable Assembly Product Data 65 0229 7800 SERIES Relay Modules Checkout and Troubleshooting 65 0249 S7810M ModBus Module SPECIFICATIONS Electrical Ratings See Table 3 Voltage and Frequency RM7890 120 Vac 10 15 50 60 Hz 10 EC7890 220 240 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum To...

Страница 2: ...equency energy and if not installed and used in accordance with the instructions can cause interference with radio communications It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residen...

Страница 3: ...Interlock b Flame Detector leadwires The maximum flame sensor leadwire length is limited by the flame signal strength c Remote Reset leadwires The maximum length of wire is 1000 feet 305 meters to a Remote Reset pushbutton d Data ControlBus Module The maximum Data ControlBus Module cable length depends on the number of system modules connected the noise conditions and the cable used The maximum le...

Страница 4: ...e control panel of the equipment Earth ground must be capable of conducting enough current to blow the 15A fuse or breaker in the event of an internal short circuit 2 Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a leadwire is required use 14 AWG copper wire 3 Make sure that mechanically tightened joints along the ground path are free of nonconduct...

Страница 5: ... EC7890 to fail the dielectric test or possibly destroy the internal lightning and high current protection Equipment Recommended 1 Voltmeter 1M ohm volt minimum sensitivity set on the 0 to 300 Vac scale 2 Two jumper wires No 14 wire insulated 12 in 304 8 mm long with insulated alligator clips at both ends Note that an ammeter can be used in place of a jumper to confirm current draw of loads igniti...

Страница 6: ...nition transformer is okay 4 3 8 1 Ignition spark if ignition transformer is connected to terminal 8 2 Automatic pilot valve opens if connected to terminal 8 or main valve if DSI application NOTE Refer to wiring diagram of system being tested 1 Watch for spark or listen for buzz a Ignition electrodes are clean b Ignition transformer is okay 2 Listen for click or feel head of valve for activation a...

Страница 7: ...LINE VOLT INPUTS FIELD WIRING INTERNAL WIRING IGNITION PILOT MAIN VALVE 1K RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS LIMITS CONTROLLER 1K1 2K2 FLAME SIGNAL TEST NUMBERS IN CIRCLES ARE RELAY MODULE TERMINAL NUMBERS PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 120 VAC 50 60 HZ RM7890 220 240 VAC 50 60 HZ EC7890 POWER SUPPLY EC7890 REQUIRES A 220 240 VAC TO 120 VAC 10VA STEPDOWN T...

Страница 8: ... THE Q7800 SUBBASE THE R4222N1002 OR R4222V1002 RELAY IS ACCEPTABLE TO USE IN THIS TYPE OF APPLICATION USE THE N O PILOT DUTY CONTACTS MASTER SWITCH L1 HOT L2 Q7800 4 POWER 00 LED DISPLAY OPERATING CONTROLLER AND LIMITS BURNER START FLAME SIGNAL INITIATE ALARM POWER STANDBY POWER POWER PILOT FLAME MAIN PFEP 4 OR 10 SEC PILOT FLAME MAIN POWER RUN STANDBY 4 10 IGNITION INTERMITTENT PILOT MAIN VALVE ...

Страница 9: ... electrical signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT Install the RM EC7890 with a plug in motion rather than a hinge action 4 Mount the RM EC7890 by aligning the four L shaped corner guides and knife blade termin...

Страница 10: ...a hold condition is initiated and is displayed on the optional KDM for at least five seconds When the tolerances are met the INITIATE sequence restarts If the condition is not corrected and the hold condition exists for four minutes the RM EC7890 locks out Causes for hold conditions in the INITIATE sequence a AC line dropout detection b AC line noise that can prevent a sufficient reading of the li...

Страница 11: ...0 seconds for RM7890A1031 c Not applicable for RM7890C Standing Pilot d The Relight feature JR2 intact requires a 0 8 second FFRT Flame Amplifier The EC RM7890 locks out and indi cates a Fault 46 if a 3 second FFRT is used and jumper JR2 is not clipped and removed e Clipping and removing a site configurable jumper after 200 hours of operation results in a hard lockout code 110 f For RM7890A1064 RM...

Страница 12: ...eywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 66 1089 11 M S Rev 08 10 Printed in U S A m a x o n s u ...

Отзывы: