# ISU ISU Name

ISU Options (defaults in bold)

Notes

370

Heat 1 CPH 

(Heating cycle 

rate stage 1)

1 - 12 CPH

This ISU is only displayed when Heat Stages is set to 1 stage or more stages. Cycle rate limits 

the maximum number of times the system can cycle in a 1 hour period measured at a 50% 

load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times 

per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions 

are less than or greater than a 50% load. The recommended (default) cycle rate settings are 

below for each heating equipment type: 

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil 

Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat 

= 3 CPH; Steam = 1 CPH.

371

Heat 2 CPH 

(Heating cycle 

rate stage 2)

1 - 12 CPH

This ISU is only displayed when Heat Stages is set to 2 stages. The recommended (default) 

cycle rate settings are below for each heating equipment type: 

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil 

Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat 

= 3 CPH; Steam = 1 CPH.

375

Aux Heat CPH 

(Heating cycle 

rate Auxiliary 

Heat)

1 - 12 CPH

This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed when 

Auxiliary Heat is configured. The recommended cycle rate settings are below for each heating 

equipment type: 

Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil 

Forced Air = 5 CPH; Electric Forced Air = 9 CPH.

425

Smart Response

On, 

Off

Smart Response is a comfort setting. Heating or cooling equipment will turn on earlier, ensur-

ing the indoor temperature will match the setpoint at the scheduled time.

429

Max Cool 

Temperature

from Min. Cool Temp. to 99 °F or to 37.0 °C 

(90 °F 

or 32 °C)

The user cannot set the cooling temperature above this level.

430

Min Cool 

Temperature

from 50 °F or 10.0 °C to Max. Cool Temp. 

(50 °F 

or 10 °C)

The user cannot set the cooling temperature below this level.

431

Max Heat 

Temperature

from Min. Heat Temp. to 90 °F or to 32.0 °C 

(90 °F 

or 32 °C)

The user cannot set the heating temperature above this level.

432

Min Heat 

Temperature

from 40 °F or 4.4 °C to Max. Heat Temp. 

(50 °F 

or 10 °C)

The user cannot set the heating temperature below this level.

702

Air Filters

0

 - 2

This ISU refers to the number of air filters in the system.

711

Air Filter 1 

Reminder

Off 

10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 

30, 45, 60, 75 Days 

3, 4, 5, 6, 9, 12, 15 Months

Choose either calendar or equipment run time-based reminder.

712

Air Filter 2 

Reminder

Off 

10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 

30, 45, 60, 75 Days 

3, 4, 5, 6, 9, 12, 15 Months

Choose either calendar or equipment run time-based reminder.

810

Hum Pad 

Reminder

Off 

6, 12 Calendar Months

921

Dehum Filter 

Reminder

Off 

30, 60 Calendar Days   

3 - 12 Calendar Months (in 1 month increments)

1018

Vent Filter 

Reminder

Off, 

3, 6, 9, 12 months

1100

UV Devices

0

 - 2

Some systems may have two UV devices, one for the A-Coil and another for Air Treatment. A 

replacement reminder can be setup for each one separately.

1105

UV Bulb 1 

Reminder

Off, 

6, 12, 24 months

1106

UV Bulb 2 

Reminder

Off, 

6, 12, 24 months

1401

Idle Brightness

0= Off, 

0 - 5

Adjust brightness of an inactive backlight (idle screen) from default 0 (backlight off) to 5 

(maximum  

brightness).

1410

Clock Format

12 hour, 

24 hour

1415

Daylight Saving

On, 

Off

Set to Off in areas that do not follow Daylight Saving Time.

Содержание RCHT8610WF

Страница 1: ...fence technology it senses your return and helps make you comfortable upon arrival You can always manually change your preset Home and Away temperature either on the thermostat or on the Honeywell Home app 2 Smart scheduling Use a combination of geofencing and time scheduling to fit your busy active lifestyle 3 Time Based scheduling Program your thermostat for one week each day each day is a diffe...

Страница 2: ...your old thermostat 2 Check that your system is off Change the temperature on your old thermostat If you don t hear the system turn on within 5 minutes the power is off Note If you have a digital thermo stat that has a blank display skip this step 1 Turn power OFF To protect yourself and your equipment Turn off the power at the breaker box or switch that controls your heating cooling system 3 Remo...

Страница 3: ... mostat in step 13 Connect the other end of the unused wire to the C terminal on your heating cooling system or the zone panel if your home uses more than one thermostat to control temperature Be sure any other wire s connected to the C terminal stay securely connected when you re tighten the terminal Not all heating cooling equipment use the C label for the 24 VAC common wire If your heating cool...

Страница 4: ...Rh or Rc into R terminal 2 Insert your Rc wire into Rc terminal 3 Insert your R or Rh wire into R Terminal 17 Turn your power ON Turn on the power at the breaker box or switch that controls the heating cooling system OFF ON ON OFF ON ON 90 o 16 Attach your thermostat Align the thermostat onto the UWP and firmly snap it into place 18 Return to the thermostat Return to the thermostat Confirm the scr...

Страница 5: ...desired indoor temperature 4 Finish Setup Touch until you see Finish Setup Touch Select or touch text area Select No Yes Back No Yes Back 5 Setup Wi Fi At the end of setup process you will be prompted to SETUP WIFI If your Wi Fi is still not working you have to manually set the time and date Select No on the SETUP WIFI screen 6 Set time and date Set daylight saving time if you are in an area that ...

Страница 6: ...ome screen In auto mode the thermostat can control either heating or cool ing to maintain the desired indoor temperature 303 Auto Differential 0 F to 5 F or 0 0 C to 2 5 C Differential is the minimum number of degrees rise or fall required during off cycle to switch from the last active mode heat or cool to the opposite mode when the thermostat is in auto changeover Differential is NOT deadband Th...

Страница 7: ...tting Heating or cooling equipment will turn on earlier ensur ing the indoor temperature will match the setpoint at the scheduled time 429 Max Cool Temperature fromMin CoolTemp to99 Forto37 0 C 90 F or 32 C The user cannot set the cooling temperature above this level 430 Min Cool Temperature from 50 F or 10 0 C to Max Cool Temp 50 F or 10 C The user cannot set the cooling temperature below this le...

Страница 8: ... s manual for additional information There is an alert that says Wi Fi Signal Lost What does that mean The Wi Fi signal to the thermostat has been lost Wait for the thermostat to reconnect or select a new network within the Honeywell Home app configuration menu If the thermostat is unable to reconnect you will need to troubleshoot the router to determine the cause Why is the thermostat showing up ...

Страница 9: ...e T5 Smart supports Apple HomeKit When prompted by the Honeywell Home app scan the code on the back cover of the guide included with your T5 Smart thermostat 2 Year Limited Warranty For Warranty information go to honeywellhome com ...

Страница 10: ...10 ...

Страница 11: ...11 ...

Страница 12: ...N 55422 www resideo com 33 00474 01 M S 4 19 Printed in United States 2019 Resideo Technologies Inc This product is manufactured by Resideo Technologies Inc Golden Valley MN 1 800 633 3991 The Honeywell Home trademark is used under license from Honeywell International Inc All rights reserved 33 00474 01 ...

Отзывы: