R7140G,L,M BURNER CONTROL MODULES
66-1153—2
8
Mounting R7140 Relay Module
Installing the Programmer (Fig. 3)
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power before installation to prevent
electrical shock. More than one disconnect may be
involved.
1.
Open the master switch.
2.
Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of
the subbase so it does not interfere with the contacts.
3.
Grasp the programmer chassis and engage the chassis
hinge brackets with the pivot pins at the bottom of the
subbase.
4.
Swing the chassis inward until the spring connectors
engage the knifeblade contacts. Push in until the
contacts are fully engaged.
5.
Tighten the chassis retaining screw securely.
6.
Close the master switch to restore power.
Removing the Programmer
1.
Open the master switch.
2.
Loosen the chassis retaining screw.
3.
Pull outward on the top of the chassis.
4.
Disengage the chassis hinge brackets from the subbase
pivot pins.
Fig. 3. Mounting the programmer on the subbase.
Fig. 4. Operating sequence, R7140G1000/R7140G2008.
CHASSIS
RETAINING
SCREW
SPRING
CONNECTORS
KNIFE-BLADE
CONTACTS (20)
WIRING
SUBBASE
PIVOT PIN (2)
HINGE
BRACKET (2)
PROGRAMMER
CHASSIS
M22605
R7140G
POWER
OPERATING
CONTROLS
AND
INTERLOCKS
BURNER
FLAME
SIGNAL
FIRING
RATE
MOTOR
INITIATE
(INITIAL
POWERUP
ONLY)
POWER
STANDBY
PREPURGE
HOLD
DRIVE TO
LOW FIRE
POWER
PILOT
FLAME
MAIN
POWER
PFEP
10 SEC.
(4 SEC. IF
JR1 CLIPPED
PILOT
FLAME
MAIN
POWER
MFEP
PILOT
FLAME
MAIN
RUN
POWER
POSTPURGE
POWER
STANDBY
00
00
10
25
00
15
20
MOTOR ACTION
BURNER/BLOWER MOTOR
IGN.
15 SEC. INTERRUPTED PILOT VALVE
LIMITS AND BURNER CONTROLLER CLOSED
RUNNING INTERLOCKS CLOSED
PII CLOSED
LOW FIRE SW.
SAFE START CHECK
FLAME PROVING
10 SEC. IGN./PILOT 5
18
8
5 SEC.
6
TO
3
TO
16
TO
8
13
TO
10
11
TO
10
11
TO
M23319
INTERLOCK. CHECK
14
11
TO
14
11
TO
4
16
L1
MAIN VALVE
7
TIMED
PREPURGE
POWER
FLAME
MAIN
PILOT
ALARM
POWER
FLAME
MAIN
PILOT
ALARM
ALARM
ALARM
ALARM
00
IC
SSC
LED
DISPLAY
R7140G SWITCHING
1 TERMINAL 6 HAS THE FOLLOWING OPTIONS:
AS RECEIVED - INTERMITTENT PILOT
JR2 CLIPPED - 15 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)
JR2 CLIPPED PLUS TERMINALS 8 - 15 JUMPERED - 30 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)
1
16
2
2
PII MEANS PRE-IGNITION INTERLOCK.
3
FOR R7140G1000:
L1 TO 4
4 TO 3
3
3