Honeywell R4795A Скачать руководство пользователя страница 13

13

60-2285—7

R4795A

TROUBLESHOOTING • SERVICE

(3) Remove any flame simulating condition such

as false light.

(4) Note that any change made in the detector or its

sighting requires a pilot turndown test.

3. If using an R7290 Ultraviolet Amplifier, replace the

amplifier and recheck the flame relay dropout time. If
the flame relay dropout timing is still excessive, re-
place the detector and check its wiring.

4. If trouble persists, replace the R4795.

H. Miscellaneous problems

1. Repeated lockouts or control failures: The most com-

mon causes of repeated failures of the control or flame
detector, or repeated lockouts are:
a. High ambient temperatures over 125

°

F (52

°

C).

Subtract 10

°

F (6

°

C) for alarm contacts and 10

°

F

(6

°

C) for 50 Hz operation. -40

°

F (-40

°

C) models

have a maximum ambient of +115

°

F (46

°

C) at

60 Hz, +105

°

F (40

°

C) at 50 Hz.

b. Supply voltage variation greater than plus 10 to

minus 15 percent.

c. Marginal flame signal.
d. Faulty flame detector.

2. Ignition interference (flame rod installations only)

What it is.  Ignition interference is a false signal

from a spark ignition source superimposed on the
basic flame signal. It is normally associated with a
marginal flame reading, and usually caused by a mar-
ginal flame ground.

How detected. The arc gap circuit in the rectifica-

tion amplifier (Fig. 10) protects the R4795 from igni-
tion interference; however, it also prevents operations
when ignition interference is present above the arcing
level of the device. If a shutdown is caused by ignition
interference, the arc gap protector glows.

Continuous interference below the arcing level can

be detected by reading the flame current with the pilot
and ignition on; then with only the pilot on. Any sub-
stantial  difference indicates the presence of ignition
interference.

Intermittent ignition interference may be due to

very turbulent air in the ignition electrode area. For
arc-over elsewhere, examine the electrodes for spac-
ing and for unusual dirt conditions or dust accumula-
tions between the ignition leads and flame leads.

How eliminated (tabulated in order of importance).
1. Provide adequate flame grounding area.
2. Be sure the ignition electrode and the flame rod

are on opposite sides of the grounding area.

3. Check for the correct spacings on the ignition

electrode. Spacing should be 1/16 in. (1.6 mm)
to 3/32 in. (2.4 mm) for 6,000V systems; 1/8 in.
(3.2 mm) to 3/16 in. (4.8 mm) for 10,000V
systems.

4. Eliminate any marginal spacings at other areas

along the lead routes. Replace any deteriorated
leads.

Service

GENERAL

1. Only qualified personnel should attempt to service

heating equipment or controls.

2. Perform all checks required in the Checkout section

when replacing the R4795, or when relighting or restoring
power to the system after shutdown.

3. Captive mounting screws carry current; always dis-

connect power before loosening or tightening the mounting
screws.

4. On each service call, check the controller for the ap-

proximately correct calibration and differential; assure it is
mounted securely (see Controller installation instructions).

5. Never use oil on any part of the R4795.
6. When cleaning the burner, clean the flame detector.
7. DO NOT MANUALLY PUSH IN THE R4795

RELAYS. This may damage the relays and it is an unsafe
practice because it overrides the protective features of the
relays. Clean relay contacts only as instructed following.

PERIODIC MAINTENANCE

The specific maintenance schedule setup will depend on

several factors including type of equipment being controlled,

operating conditions (dirt and heat especially), and the cost of
a nuisance shutdown. Include the following in any program:

Annually replace the vacuum tubes in the C7012 Flame

Detector (if used).

Perform a flame failure check and pilot turndown test

whenever the burner is serviced, and at least annually.

Inspect and clean the detector and any viewing windows

as often as required by soot accumulation and heat
conditions at the detector.

Do a flame current check at least monthly, and more often

where a shutdown may be costly.

Clean contacts only when required by failure to operate

properly.

CONTACT CLEANING

CAUTION

Open the master switch before removing cover or
cleaning contacts. Line voltage is present on most
contacts when power is on.

Содержание R4795A

Страница 1: ...repurge if the flame goes out while burner is running If pilot flame is not re established safetyswitchtripsandlocksoutsystem A tripped safety switch must be manually reset to restore operation Push to resetsafetyswitchisdust resistantenclosed Optional spdt alarm contacts operate external alarm on safety switch lockout Ignition interference circuit rectification amplifier only protects electronic ...

Страница 2: ...t contacts Male quick connect terminals female quick connects included See Terminal Ratings 40 F 40 C models have isolated spdt alarm contacts Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number 3 Flame failure response tim...

Страница 3: ...tion Design Certified File no 21 6 F and F1 ACCESSORIES W136A Test Meter includes 117053 Meter Connector Plug Flame Simulator 203659 Ultraviolet 121708 Rectification 123514B Ultraviolet 117053 Meter Connector Plug FSP1535 Tester for operational check Q624 Solid State Spark Generator 118702E Remote Reset Cover 120 Vac 60 Hz 202471C Reset Cover for R4795A ADDITIONAL CONTROLS Order all additional con...

Страница 4: ...ng tubes can result in failure of the sensingtubetoproperlydiscriminatebetweenflame conditions For systems using R4795A with R7290 Amplifiers use C7027 C7035 and C7044 Flame Detectors only on burners that cycle On and Off at least once every 24 hours Appli ances with burners that remain on for 24 hours continuously or longer should use the C7012E Flame Detector with the R7247C Amplifier or the C70...

Страница 5: ...TS BURNER MOTOR AIR FLOW SWITCH TO FLAME DETECTOR FLAME ROD OR UV DETECTOR FLAME AMPLIFIER 1K4 3K2 2K2 2K3 MAIN FUEL VALVE S IGNITION PILOT VALVE CONTROLLER LIMIT S R4795A 8 7 6 F G 5 4 3 1 2 2 3 Fig 3 Wiring hookup of oil system with interrupted ignition M8683 L1 HOT L2 1 1 2 3 4 5 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR INTERMITTENT IGNITION CONNECT IGNITION...

Страница 6: ...R FLAME DETECTOR 6 8 7 6 T T F G 2 1 3 4 5 AIR FLOW SWITCH SODERLESS CONNECTION 120V 120V M8684 R4795C Replacement In most cases the R4795A can directly replace the R4795C For standing pilot applications where the pilot flame was detected during the off cycle install a relay as shown in Fig 5 Flame Detector Wiring See Fig 6 Alarm Contacts Models with alarm contacts have three male quick con nect t...

Страница 7: ...wandremovethecover seeFig 8 Position the R4795 over the Q270 Subbase Start all ten mounting screws and tighten uniformly These screws com plete electrical circuits terminal 1 excepted and hold the R4795 to the subbase L1 HOT L2 1 1 2 2 IF A LINE VOLTAGE ALARM IS USED THE R4795 MUST BE MOUNTED IN A SUITABLE ENCLOSURE POWER SUPPLY MUST MATCH THE ELECTRICAL RATINGS OF THE ALARM PROVIDE DISCONNECT MEA...

Страница 8: ... SAFETY SWITCH RESET BUTTON CAPTIVE MOUNTING SCREWS 10 2K 3K M8680 ST71A PLUG IN PURGE TIMER PURGE TIMER CONNECTORS PLUG IN AMPLIFIER OPTIONAL ALARM TERMINALS AMPLIFIER CONNECTORS TEST JACK ARC GAP IGNITION INTERFERENCE PROTECTION R7289 RECTIFICATION AMPLIFIER ONLY PRELIMINARY INSPECTION Make certain that 1 Wiringconnectionsarecorrectandallterminalscrews are tight Use a meter to check the continui...

Страница 9: ...ge c As the control attempts to restart the pilot turn the pilot back up slowly just until relay 2K pulls back in You will have 15 seconds to complete this step before lockout occurs d Again turn the pilot down slightly but not enough so theflamerelaydropsout Iftherelaydropsout simply allow the control to complete the purge period and then turn the pilot back up to pull in the flame relay as in st...

Страница 10: ...so spark is produced between the electrode and ground 3 Checktheflamerelay2K Therelayshouldnotpullin The flame signal current should not be more than one fourth microampere 4 If relay 2K does pull in resight the detector farther out from the spark or away from possible reflection It may be necessary to construct a barrier to block the ignition spark from the detector view Continue adjustments unti...

Страница 11: ...e 1K relay will not pull in The result will be a continuous purge safe failure Hot Refractory Hold in Photocell Installations If hot refractory holds in the flame relay at the end of the running cycle startup is prevented until the hot refractory no longer holds in the flame relay Troubleshooting The first step in troubleshooting the R4795A is to deter mine the location of the system trouble Reset...

Страница 12: ... is pulled in check for flame simulating condition 4 If the flame relay is not pulled in clean the 2K relay contacts 5 Replace the purge timer with one of the same timing If problem still continues replace the R4795 D Relay 1K pulls in but the pilot does not light ignition doesnotoccur orexpandingpilotvalvedoesnotopen 1 Make sure that all manual fuel valves are open 2 Check voltage between termina...

Страница 13: ... Howeliminated tabulatedinorderofimportance 1 Provide adequate flame grounding area 2 Be sure the ignition electrode and the flame rod are on opposite sides of the grounding area 3 Check for the correct spacings on the ignition electrode Spacing should be 1 16 in 1 6 mm to 3 32 in 2 4 mm for 6 000V systems 1 8 in 3 2 mm to 3 16 in 4 8 mm for 10 000V systems 4 Eliminate any marginal spacings at oth...

Страница 14: ...e reasons 1 Some had solvents that could deteriorate plastic parts and wire insulation 2 Some leave an oily residue that will collect dust and dirt The residue will also break down to form various carbonaceousproducts Eitherresultwillcauseearlycontact failure Do not use an abrasive sand paper stock file etc or a burnishing tool to clean contacts Its use can cause early contact failure for these re...

Страница 15: ...15 60 2285 7 ...

Страница 16: ... Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in Mexico www honeywell com bbc ...

Отзывы: