AUTOMATIC IGNITION CONTROLLER

R4560

INSTRUCTION SHEET

EN1R--9102 9402R1--NE

Description
The R4560 is a solid state automatic
direct burner ignition as well as
intermittent ignition controller with
excellent performance and high
reliability standard.

Application
The R4560 provides automatic
sequence control for:

-

Power burners up to 350 kW in
accordance with DIN 4788 part 2
and 3 including flame supervision
and non volatile lockout for
intermittent operation.

-

Power burners in accordance with
European safety standards EN 298.

-

Warm air heaters in accordance with
DIN 4794 part 3 (-- 20

E

C).

FEATURES

-

Integral reset alarm push button

-

Accurate safety timer.

-

Individual timers for safety and
prepurge timing.

-

Supply voltage range 220 ... 240 V.

-

Full operating sequence after flame
loss.

-

Optional internal medium power
50 Hz spark igniter with 20 cm cable
and 2,8 x 0,8 mm spade terminal for
extended wiring.

-

Connection for external high power
igniter (S720)

-

Lockout in case of air proving switch
detects no air.

-

Lockout in case of flame simulation
before start or during prepurge.

-

Sequence status diagnostic
indicators by 4 LED’s.

S

u

bj

ec

t

to

c

ha

ng

e

w

it

ho

u

t

n

o

ti

ce

.

P

ri

n

ted

in

th

e

N

e

the

rl

an

ds

.

Содержание R4560

Страница 1: ...nce with European safety standards EN 298 Warm air heaters in accordance with DIN 4794 part 3 20 EC FEATURES Integral reset alarm push button Accurate safety timer Individual timers for safety and prepurge timing Supply voltage range 220 240 V Full operating sequence after flame loss Optional internal medium power 50 Hz spark igniter with 20 cm cable and 2 8 x 0 8 mm spade terminal for extended wi...

Страница 2: ...t7 Ts Tp 5 s max t4 Fig 3 Intermittent pilot ignition Fig 4 Direct burner ignition P y P y MV1 MV2 MV1 MV2 Thermostat Gas valve Ignition Flame rod Fan Limiter Reset switch Alarm Air proving switch y G Gas pressure switch y P 91 5 62 39 35 63 5 20 20 21 50 15 65 3 3 3 Retaining screw Conduit knockout Reset button Subbase 15 Fig 5 Dimensions Sequence status LED s see fig 6 y G y Flame established V1...

Страница 3: ...ered separa tely High voltage ignition cable with length of 50 cm order number 45 900 411 001 Subbase ordernumber Q632A 1124 SYSTEM OPERATION Automatic ignition controller for po wer burners see fig 3 and 4 When thermostat calls for heat fan is energized if air proven switch is in the no air position When sufficient air flow is proven by the air proving switch a prepurge period Tp elapses before t...

Страница 4: ... controller seems to operate normally but does not detect ignition flame check for right polarity of power supply line neutral Checking flame current The minimum value should be 1 µA To check flame current connect a DC micro Ampèremeter between flame sensing wire and flame sensing rod see fig 1 and 2 If flame current is insufficient check that proportion of flame touching the grounded portion of t...