Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES

Fig. 1. Typical location of thermostat or remote-mounted sensor.

Install the remote-mounted sensor(s) about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.

Do not mount the sensor(s) where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

If more than one remote sensor are required, they must be
arranged in a temperature averaging network consisting of

two, three, four, five or nine sensors. See Fig. 2 through 6.

IMPORTANT

To avoid electrical interference, which can cause
erratic performance, keep wiring runs as short as
possible and do not run thermostat wires
adjacent to the line voltage electrical distribution
systems. Use shielded cable (Belden type 8762
or equivalent for 2-wire and Belden type 8772 or
equivalent for 3-wire). The cable shield must be
grounded only at the controlled equipment case.

Fig. 2. Two T7047G Sensors providing

temperature averaging network for

T7300/Q7300 Thermostat/Subbase.

Fig. 3. Two T7047C Sensors and one T7047G Sensor

providing temperature averaging network for

T7300/Q7300 Thermostat/Subbase.

Fig. 4. Four T7047C Sensors providing

temperature averaging network for

T7300/Q7300 Thermostat/Subbase.

5 FEET

(1.5 METERS)

YES

NO

NO

NO

M4823A

M4838

T

T

SUBBASE

T

T

T7047G

T7047G

T

T

M4839

T

T

SUBBASE

T

T

T7047C

T

T

T7047C

T

T

T7047G

M4840

T

T

T

T

SUBBASE

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

Содержание Q7300A

Страница 1: ...le for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Subbase without Remote Mounted Temperature Sensor Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it ca...

Страница 2: ... IMPORTANT To avoid electrical interference which can cause erratic performance keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems Use shielded cable Belden type 8762 or equivalent for 2 wire and Belden type 8772 or equivalent for 3 wire The cable shield must be grounded only at the controlled equipment case Fig 2 Two ...

Страница 3: ...g screws Fig 7 Mounting the subbase WIRING SUBBASE All wiring must comply with local electrical codes and ordinances Follow equipment manufacturer wiring instructions when available Refer to Fig 9 through 17 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal ...

Страница 4: ...POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LED...

Страница 5: ...TH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X T...

Страница 6: ...CONTACTOR 1 C4 C3 C5 CA1 T CA2 CA4 CA3 CA5 T T TRANSFORMER E HEAT RELAY 2 HEAT CHANGEOVER VALVE X3 X1 X4 EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE A2 A1 AS AS DISCHARGE AIR SENSOR ECONOMIZER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS USE A1 AND A2 WHEN THE CONTACTS ARE NORMALLY CL...

Страница 7: ... X2 L EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE EM MODE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS USE ECONOMIZ...

Страница 8: ...ABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN CONTAC...

Отзывы: