COOLING 

CAUTION 

If outside air or heat exchange medium (water) is 
below 10

A

C (50

A

F), do not operate cooling. 

Move the system switch on the Q539 to COOL and the 

fan switch to AUTO. Move the cooling setpoint dial to about 
6

A

C (10

A

F) below room temperature. Cooling equipment 

should start and the fan should run. Change the setpoint to 
about 6

A

C (10

A

F) above the room temperature. The cooling 

equipment and fan should shut off. 

FAN 

Move the subbase switch to OFF and the fan switch to 

ON. The fan should run continuously. Move the fan switch 
to AUTO. In this position, fan operation is controlled by the 
heating or cooling system control circuit. 

Operate the entire system one complete cycle with 

switches in each position before leaving installation. Turn 
thermostat dial to the desired setting and set the system and 
fan switches. 

Automation and Control Solutions 

Honeywell 

Honeywell Limited—Honeywell Limitée 

1985 Douglas Drive North 

35 Dynamic Drive 

Golden Valley, MN 55422 

Scarborough, Ontario 

M1V 4Z9 

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers. 

www.honeywell.com/yourhome

95-6486–9  G.H.  Rev. 8-02 

Содержание Q539

Страница 1: ...l Z Q539H low voltage fan switch for control of fan relay in AUTO position for both heating and cooling control a Cooling transformer in systems with separate heating and cooling circuits b Heating transformer in systems with isolated heating and cooling circuits c Circuit only completed between R and B with system switch in HEAT position d Circuit only completed between R and O with system switch...

Страница 2: ...er instructions for Q539 wiring diagrams If not available refer to Fig 1 through 5 4 Push excess wire back through the hole and plug any opening with insulation to prevent drafts that can affect performance 5 Loosely fasten the thermostat subbase to the wall with ascrewthroughtheleftmountinghole Adjustthesubbaseso it is approximately level and start the second screw through the right mounting slot...

Страница 3: ... HOT M8833 Fig 5 Typical hookup for Q539J in heating cooling applications Fan relay operates automatically on heat or cool with fan in AUTO position Q539J T87F INTERNAL SCHEMATIC HEAT OFF COOL HEAT OFF COOL AUTO FAN ON W B R G P T87F TEMP FALL R1 ADJUST ABLE HEAT ANTICIPATOR FILTER LIGHT X Y CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION COMPRESSOR RELAY COOLING DAMPER MOTOR FAN RELAY O L1 HOT ...

Страница 4: ...ch to ON The fan should run continuously Move the fan switch to AUTO In this position fan operation is controlled by the heating or cooling system control circuit Operate the entire system one complete cycle with switches in each position before leaving installation Turn thermostat dial to the desired setting and set the system and fan switches Automation and Control Solutions Honeywell Honeywell ...

Отзывы: