Specifications and replacement parts

Operating Ambient Temperature

Thermostat: 

32 to 120° F (0 to 48.9° C)

Portable Comfort Control: 

32 to 120° F (0 to 48.9° C)

Wireless Outdoor Sensor: 

-40 to 140° F (-40 to 60° C)

Wireless Indoor Sensor: 

0 to 120° F (-17.8 to 48.9° C)

   

 -For Optimal Battery Life: 35 to 114° F (1.7 to 45.6° C)

Equipment Interface Module:

 -40 to 165° F (-40 to 73.9° C)

Return Air Sensor: 

0 to 200° F (-17.8 to 93.3° C)

Discharge Air Sensor: 

0 to 200° F (-17.8 to 93.3° C)

RedLINK Internet Gateway: 

32 to 120° F (0 to 48.9° C)

Operating Relative Humidity

Thermostat: 

5% to 90% (non-condensing)

Portable Comfort Control: 

5% to 90% (non-condensing)

Wireless Outdoor Sensor:

 0% to 100% (condensing)

Wireless Indoor Sensor: 

5% to 90% (non-condensing)

Equipment Interface Module: 

5% to 95% (non-condensing)

RedLINK Internet Gateway: 

5% to 95% (non-condensing)

Physical Dimensions 

(height, width, depth)

Thermostat: 

4-1/2 x 3-1/2 x 7/8 inches (115 mm x 88 mm x 22 mm)

Equipment Interface Module: 

9-5/16 x 4-13/16 x 1-19/32 inches (91 x 147 x 42 mm)

Wireless Outdoor Sensor: 

5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm)

Wireless Indoor Sensor: 

2-7/8 x 1-7/8 x 15/16 inches (74 x 48 x 24 mm)

Portable Comfort Control: 

6-1/4 x 3-1/8 x 1-5/8 inches (158 x 80 x 38 mm)

RedLINK Internet Gateway: 

6 x 4-7/8 x 2-1/2 inches (152 x 124 x 64 mm)

RedLINK Communication

Frequency: 

900 Mhz frequency range

Re-Sync Time: 

RedLINK devices re-establish communication within 6 minutes after AC power resumes.

Electrical

 

ratings

Terminal

Voltage (50/60 Hz)

Max. Current Rating

W - OB

18 to 30 VAC and 750 mVDC

1.00A

Y

 (cooling)

18 to 30 VAC

1.00A

G

 (fan)

18 to 30 VAC

0.50A

W2 - Aux 1

 (heating)

18 to 30 VAC 

0.60A

W3 - Aux 2

18 to 30 VAC 

0.60A

Y2

 (cooling)

18 to 30 VAC

0.60A

A-L/A

 (output)

18 to 30 VAC

1.00A

U1

30 VAC max.

0.50A

U2

30 VAC max.

0.50A

U3

30 VAC max.

0.50A

Accessories and replacement parts

Accessories / Replacement Parts

Part Number

Equipment Interface Module

THM5421R1021

Wireless Adapter for TrueZone, TrueSteam, or extend wireless range of EIM

THM4000R1000

RedLINK Internet Gateway

THM6000R1002

Wireless Entry/Exit Remote

REM1000R1003

Wireless Vent and Filter Boost Remote

HVC20A1000

Portable Comfort Control

REM5000R1001

Wireless Outdoor Sensor

C7089R1013

Wireless Indoor Sensor

C7189R1004

Wireless Outdoor Sensor 10k ohm NTC

C7089U1006

Wired Wall-mount Indoor Sensor 10k ohm NTC

C7189U1005

Wired Flush-mount Indoor Sensor 20k ohm NTC

C7772A1004, C7772A1012

Wired Wall-mount Indoor Sensor 20k ohm NTC

TR21

Wired Wall-mount Indoor Sensor 10k ohm NTC

TR21-A

Supply or Return Air Sensor 10k ohm NTC

C7735A1000

Supply or Return Air Sensor 20k ohm NTC

C7041

Supply or Return Air Sensor 20k ohm NTC

C7770A1006

Occupancy Sensor for Remote Setback

WSK-24

Cover Plate (covers marks left by old thermostats)

THP2400A1027W, THP2400A1027G, 
THP2400A1027B

69-2739_A.indd   15

11/1/2012   2:33:34 PM

Содержание Prestige THX9421R02

Страница 1: ...Q with Equipment Interface Module Installation Guide TM TM TM OR 2 Wires for Power 2 Wires for Power RedLINK to Equipment Interface Module RedLINK to TrueZONE Wireless Adapter 69 2739_A indd 1 11 1 2012 2 33 23 PM ...

Страница 2: ...utdoor sensor USB port Use USB device to load settings and dealer information Reference to key features Password is date code Getting started Follow these basic steps to install this thermostat link it with the equipment interface module EIM and wireless accessories and set installer options 1 Installing the Equipment Interface Module EIM 2 Installing the thermostat 3 Powering optional RedLINK acc...

Страница 3: ...ked in the kit 1 Installing the equipment interface module EIM Terminal Designations Conventional System Heat Pump Terminal Description Terminal Description C Common wire from 24 VAC transformer C Common wire from 24 VAC transformer R Power wire from 24 VAC transformer R Power wire from 24 VAC transformer RH Heating power RH Heating power RC Cooling power RC Cooling power W Heat Stage 1 O B Change...

Страница 4: ...00R1000 Wireless Adapter for extended wireless range See wiring diagrams on pages 4 5 See wiring diagram below for wiring Dry Contact Devices to display alerts U1 U2 and U3 are normally open dry contacts when set up for a stage of heating or cooling You must install a field jumper if the stage of heating or cooling is powered by the system trans former Do NOT install a field jumper if the stage of...

Страница 5: ...N WITH LOW SPEED FAN 24 VAC 120 VAC 1 2 Typical hookup of powered humidifier Typical hookup of non powered humidifier Typical hookup of powered ventilation Typical hookup of powered dehumidifier whole house dehumidifer Typical hookup of variable speed blower for dehumidification in low speed Typical hookup of non powered ventilation Any combination of universal relays U1 U2 U3 can be used They are...

Страница 6: ...to the R and C terminals at the EIM or to a separate 24 volt transformer not provided 2 3b Push excess wire back into the wall opening 2 4 Insert coin cell battery Place coin cell battery in thermostat as shown with side up NOTE Coin cell battery saves time and date during a power loss 2 Installing the thermostat R C 1324 Thermostat back view Thermostat back view Wallplate back view Wallplate Wall...

Страница 7: ...p 4 5 3 2 Connect gateway to internet and connect to power 3 2a Connect RedLINK Internet Gateway to router or modem with Ethernet cable RJ45 3 2b Connect gateway s power cord to an electrical outlet that is not controlled by a wall switch 3 Powering optional RedLINK accessories Thermostat Wallplate 2 5 Mount thermostat on wallplate Align thermostat to wallplate and snap into place R C 3 2a 3 2b 69...

Страница 8: ...e exit the listening mode at the other system and then try again Green Flashing In Listening Mode system is ready to add RedLINK devices Green Steady RedLINK devices are communicating Red RedLINK device s are NOT communicating Check EIM and RedLINK devices 4 2b While the Connected light is flashing green on the EIM press Next on the thermostat After a short delay the screen will display Device Con...

Страница 9: ...n on each new RedLINK accessory 4 4b After a short delay up to 20 seconds check the thermostat to confirm the connection of each RedLINK accessory 4 4c Touch Done at the thermostat after all new RedLINK accessories are connected NOTE The thermostat displays a countdown timer while in listening mode If it detects no activity for 15 minutes it exits listening mode Done 4 5 Finish the initial setup F...

Страница 10: ... Installer Setup To perform Installer Test To view Data Logs Finding your password You can find the Date Code on the back of the thermostat or 1 Touch Menu 2 Select Dealer Information Dealer Informa on OK 1324 1324 Thermostat back view Password Date Code 69 2739_A indd 10 11 1 2012 2 33 31 PM ...

Страница 11: ...CT button on each new RedLINK accessory 5b After a short delay up to 20 seconds check thermostat to confirm the connection of each RedLINK accessory 5c Touch Done at the thermostat after all new RedLINK accessories are connected NOTE Thermostat displays a countdown timer while in listening mode If it detects no activity for 15 minutes it exits listening mode Linking RedLINK accessories to the ther...

Страница 12: ...ons 3 Enter password date code and touch Done 4 Select Create Setup or Installer Test 5 Follow prompts on the screen to select the desired setup options or to perform an equipment test Installer Op ons Done Mounting an outdoor sensor 1 Mount the sensor on a vertical exterior wall at least 6 inches below any overhang Choose a location protected from direct sunlight 2 Place sensor securely in bracke...

Страница 13: ...ple sensors are selected the thermostat will respond to an average of temperatures detected at each sensor Humidification control If optional remote indoor sensors are installed you can choose which sensor you want to use for humidification control You can use a different sensor for dehumidification Dehumidification control If optional remote indoor sensors are installed you can choose which senso...

Страница 14: ...t thermostat information on the USB device select Save to USB When you replace a thermostat you must reset the RedLINK accessories before connecting them to the new thermostat Follow the instructions below At the Portable Comfort Control Press and hold the blank space or arrow in the lower right corner of the screen until the display changes hold for about 4 seconds Press REMOVE then YES to discon...

Страница 15: ...0 Mhz frequency range Re Sync Time RedLINK devices re establish communication within 6 minutes after AC power resumes Electrical ratings Terminal Voltage 50 60 Hz Max Current Rating W OB 18 to 30 VAC and 750 mVDC 1 00A Y cooling 18 to 30 VAC 1 00A G fan 18 to 30 VAC 0 50A W2 Aux 1 heating 18 to 30 VAC 0 60A W3 Aux 2 18 to 30 VAC 0 60A Y2 cooling 18 to 30 VAC 0 60A A L A output 18 to 30 VAC 1 00A U...

Страница 16: ...URY NOTICE If this product is replacing a control that contains mercury in a sealed tube do not place the old control in the trash Contact the Thermostat Recycling Corporation at www thermostat recycle org or 800 238 8192 for information on how and where to properly and safely dispose of your old thermostat Must be installed by a trained experience technician Read these instructions carefully Fail...

Отзывы: