ADS-14221, PPT2 User Manual
October, 2016
11 of 85
Table 1.0 – Command List, Grouped by Function
See previous page for descriptions of the table headings.
Command
Code
Action
Directing
Command
Sequence of
Response with
(90-99)
Addresses
Input or
Output
Type
Requires
Write
Enable
Terminates
Continuous
Commands
Can Write
to
EEPROM?
Can Write
to DAC?
Command Description
Pressure Readings
P1
No Before
(5) Out No No No No
Pressure, Single, ASCII Format
P2
No
(3)
After Out
No
Yes
(8)
No No
Pressure, Continuous, ASCII Format
P3
No Before
(5) Out No No No No
Pressure, Single, Binary Format
P4
No
(3)
After Out
No
Yes
(8)
No No
Pressure, Continuous, Binary Format
Pressure Units
DU
Yes Before Both
Yes
(6)
No Yes
(9)
No
Display Units Control
U=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
User Supplied Display Units
Pressure Sensor Temperature Readings
T1
No Before
(5) Out No No No No
Sensor Temperature, Single, °C
T2
No
(3)
After Out
No
Yes
(8)
No No
Sensor Temperature, Continuous, °C
Transducer Information
ID
Yes Before Both
Yes
(6)
No Yes
(9)
No
Identification Number
M=
Yes After
(4) Out No No No No
Maximum Full Scale Pressure
P=
No After
(4) Out
No No No No
Production Date
S=
No After
(4) Out
No No No No
PPT2 serial number
V=
No After
(4) Out
No No No No
PPT2 Firmware Version
Pressure Reading Modifiers
I=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
Integration Time
IC
Yes Before Both
Yes
(6)
No Yes
(9)
No
Idle Count Parameter
CM
Yes Before Both
Yes
(6)
No Yes
(9
No
Compatibility Mode (new command)
DS
Yes Before Both
Yes
(6)
No Yes
(9)
No
Deadband and Sensitivity Control
Pressure Window Customization, Calibration, and Control
F=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
Customized Full Scale Pressure
Range
T=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
Set Tare Value
TC
Yes Before Both
Yes
(6)
No Yes
(9)
No
Tare Control Switch
X=
Yes After
(4)
Both
Yes
(6)
No Yes
(9)
No
Slope 1, User Compensation Control
Y=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
Slope 2, User Compensation Control
Z=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
Offset, User Compensation Control
Analog Customization, Calibration, and Control
AN
Yes Before Both
Yes
(6)
No Yes
(9)
No
Analog Range Setting
DX
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
DAC Slope Compensation Control
(new command)
DZ
Yes After
(4) Both
Yes
(6)
No Yes
(9)
No
DAC Offset Compensation Control
(new command)
H=
Yes After
(4) Both
Yes
(6)
No Yes
(9)
Yes
(11)
Highest Analog Voltage