background image

 

 

- 2 -

 

Battery Installation and Replacement 

To replace the battery: 

1.

 

Remove the detector from its mounting base by twisting the 
detector counterclockwise. Remove the battery, and dispose 
properly. 

2.

 

To ensure proper power-down sequence, wait a minimum of 20 
seconds before installing new battery. 

3.

 

Install a new 3-volt CR123A Lithium battery in the battery 
compartment. Follow the polarity diagram inside the 
compartment. 

4.

 

Reinstall the smoke detector onto the mounting base by 
turning the detector clockwise. 

5.

 

Test the detector as described in the TESTING SIGNAL 
STRENGTH section of this manual. The green LED should 
blink about once every 10 seconds to indicate normal operation. 
If the battery is not installed correctly, the smoke detector will 
not operate and the battery may be damaged. If the detector 
does not appear to be sending a signal during any of the tests, 
check for correct battery installation and for a fully charged 
battery. 

Test Switch

Green LED

Red LED

 

Figure 1. 5808W3 Wireless Smoke/Heat Detector 

Programming 

The smoke detector must be enrolled in the control panel before it 
can operate in the system. The 5808W3 smoke/heat protection zone 
must be enrolled as Loop 1 and “Input Type” 3 (supervised RF). 

If programmed, this smoke detector is capable of monitoring the 
additional conditions of Maintenance (transmitted as Loop 2), and 
Low Temperature (transmitted as Loop 3). Tamper is transmitted 
as Loop 4, but does not require programming.  To take advantage of 
the value added features of Maintenance and Low Temperature, 
you must program each loop as a separate zone in the 5800 series 
wireless compatible panel. 

1.

 

Enter the control’s Zone Programming mode. 

2.

 

Enter the zone number to be programmed. 

3.

 

Enter the applicable zone type when prompted.  Program 

 

Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16),  

 

Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble 
zone (type 19), and  

 

Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone 
(type 8). 

NOTE

: Loop 2 High/Low Maintenance is supported only on 

commercial control panels such as the Vista-128FBP. 

4.

 

When prompted, enter Input Type 03 (3 on some controls) 
– Supervised RF Transmitter. 

5.

 

When prompted for the serial number, transmit from the 
detector by activating the tamper switch.  To do this, hold 
the base of the detector in one hand, and rotate the 

detector counter-clockwise on the base until it snaps open. 

 

Then return to clockwise position until the detector snaps 
into place.  

6.

 

When the serial number is displayed, transmit from the 
detector a second time by activating the tamper switch 
again as described in Step 5.  The current loop number (4) 
will begin to flash. 

7.

 

Manually change the loop number to the desired loop 
number for the zone (according to the application). 

8.

 

When programming for this zone is complete, program 
other zones for the transmitter as necessary (except for 
Tamper Loop 4, which does not require programming).  

 

WARNING:  The fire protection zone enrolled must 
always be Loop 1.  Otherwise, fire annunciations will 
not be reported by the control. 

9.

 

Exit Programming mode when programming is complete, 
and test the detector. Refer to the Testing Section. 

See the control unit’s installation instructions for further 
details.  

Mounting 

First, determine the best location for the smoke detector, one that 
provides a strong wireless transmission path and proper smoke 
detection. 

A GOOD TRANSMISSION PATH MUST BE 

ESTABLISHED FROM THE PROPOSED MOUNTING 
LOCATION BEFORE PERMANENTLY INSTALLING THE 
DETECTOR.

 To check, perform the test described in the TESTING 

SIGNAL STRENGTH section of this manual. Prior to mounting the 
detector to the mounting base, you must “enroll” the detector’s 
serial number into the system (see the PROGRAMMING section).  
To mount the detector, perform the following steps: 

1.

 

Once a suitable location has been determined, install the 
mounting base on the ceiling or on the wall (if local ordinances 
permit). Use the two screws and anchors provided. 

2.

 

Turn the detector in a clockwise direction in the mounting base 
until it clicks into place. 

3.

 

Test the detector immediately after completing the installation 
(as described in the TESTING section of this manual) and 
refer to the control system’s instructions for additional 
information concerning the use of wireless smoke detectors. 

Tamper
Release Tab

Direct Mount Holes

Tamper Resistant Tab

(Cut off small tab to activate

tamper resist feature)

 

Figure 2. Detector Mounting Base 

 

 

Figure 3. Mount Detector Across Ceiling Panel Support 

!

 

DO NOT attach the detector to removable ceiling panels. 
Attach the detector across panel support as shown in 
Figure 3.

 

Содержание Photoelectronic Smoke/Temperature Detector 5808W3

Страница 1: ...detector has reset a RESTORE message is transmitted to the control panel and the transmitter s zone number can be cleared from the panel The built in Drift Compensation algorithm automatically maintains the sensitivity of the detector Once the detector reaches its limit of compensation it transmits a maintenance signal to the panel The mounting base installation is simplified by the incorporation ...

Страница 2: ...e detector by activating the tamper switch To do this hold the base of the detector in one hand and rotate the detector counter clockwise on the base until it snaps open Then return to clockwise position until the detector snaps into place 6 When the serial number is displayed transmit from the detector a second time by activating the tamper switch again as described in Step 5 The current loop num...

Страница 3: ...Heat Method Hair dryer of 1000 1500 watts Direct the heat toward either side thermistor Be sure to hold the heat source about 12 inches from the detector to avoid damage to the plastic The detector will reset only after it has time to cool Smoke detection testing is recommended for verifying system protection capability A detector that fails to activate with any of these tests should first be clea...

Страница 4: ...otify the central station when the system is back in service REMOVABLE DETECTOR COVER SCREEN SENSING CHAMBER TOP HALF DETECTOR HOUSING Figure 5 Removing Screen Sensing Chamber Specifications Power Source One 3 volt CR123A Lithium Battery included Replace with Duracell DL123A Sanyo CR123A Panasonic CR123A or ADEMCO 466 Height 2 3 inches 58 mm Diameter 5 3 inches 135 mm with mounting base Weight 8 5...

Отзывы: