P7650A/B/U

31-00138—02

4

5.

For applications using conduit, remove the cable 
gland nut on the bottom of the unit. Thread a stan-
dard 1/2-inch NPT female threaded coupler onto 
the body of the cable gland. Connect the opposite 
end of the coupler to the conduit.   

Fig. 6. 

6.

Set DIP switches to desired settings.

Table 1. 

*Velocity mode is unidirectional regardless of DIP switch 
setting.

Table 2. DIP Switch Settings.  

7.

Set rotary switch to the desired setting. Align the 
arrow (not the slot) on the rotary switch to the 
desired full-scale range. LCD models momentarily 
indicate the selected range.

Rotary Switch Settings

Table 3. 0-1 Inch Range Models, Field Selectable 

(WC/FPM or Pa/MS). 

Table 4. 0-10 Inch Range Models, Field Selectable 

(WC/FPM or Pa/MS).   

DIP Switch

Setting

DIP Switch 1: Scale

ON = Pascal/MPS

OFF = In. WC/FPM

DIP Switch 2: Mode

ON = Velocity

OFF = Pressure

DIP Switch 3: Direction*

ON = Unidirectional

OFF = Bidirectional

DIP Switch 4: Response

ON = Slow

OFF = Fast

DIP Switch 5: Output

ON = 4-20 mA

OFF = Voltage

DIP Switch 6: 
Volt Scale

ON = 0-5 Vdc

OFF = 0-10 Vdc

DIP Switch 7

Unused

DIP Switch 8

Unused

1/2-INCH NPT FEMALE 

THREADED COUPLER

M37460

Scale

Mode

Direction Response

ON

Pascal/MPS

Velocity

Uni

Slow

OFF

In. WC/FPM

Pressure

Bi

Fast

1

2

3

4

Output

Volt Scale

Unused

Unused

ON

mA

5V

Unused

Unused

OFF

Volt 10V

Unused

Unused

5

6

7

8

WC / FPM

Pa / MS

0

0 to 0.1 in. WC

0

0 to 25 Pa

1

0 to 0.25 in. WC

1

0 to 50 Pa

2

0 to 0.5 in. WC

2

0 to 100 Pa

3

0 to 1 in. WC

3

0 to 250 Pa

4

0 to 500 FPM

4

0 to 2.5 ms

5

0 to 1000 FPM

5

0 to 5 ms

6

0 to 2000 FPM

6

0 to 10 ms

7

0 to 3000 FPM

7

0 to 15 ms

WC / FPM

Pa / MS

0

0 to 1 in. WC

0

0 to 250 Pa

1

0 to 2.5 in. WC

1

0 to 500 Pa

2

0 to 5 in. WC

2

0 to 1000 Pa

3

0 to 10 in. WC

3

0 to 2500 Pa

4

0 to 3000 FPM

4

0 to 15 ms

5

0 to 4000 FPM

5

0 to 20 ms

6

0 to 5000 FPM

6

0 to 25 ms

7

0 to 6000 FPM

7

0 to 30 ms

Содержание P7650A Series

Страница 1: ...ller is responsible for conformance to all applicable codes If this product is used in a manner not specified by the manufacturer the protection provided by the product may be impaired No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material PRODUCT IDENTIFICATION New Part Number Mounting Selectable w c Pressure Range Uni or Bi Directional Veloc...

Страница 2: ...asured value Temperature Effect 1 250 Pa models 0 05 C 10 2 5 kPa models 0 01 C Relative to 25 C 0 to 50 C 32 to 122 F Zero Drift 1 year 1 250 Pa models 2 0 max 10 2 5 kPa models 0 5 max Zero Adjust Pushbutton auto zero and digital input 2 pos terminal block Operating Environment 0 to 60 C 32 to 140 F Altitude of Operation 0 to 3000 m Pollution Degree 2 Humidity Range 100 RH non condensing Mountin...

Страница 3: ...g configuration a Connect the right side tube to the rear brass barb marked as on the underside of the device housing b Connect the left side tube to the probe in the back of the device housing Panel mount tubing configuration a Connect the right side tube to the rear brass barb marked as on the underside of the device housing b Connect the left side tube to the front brass barb marked as on the u...

Страница 4: ...witch 2 Mode ON Velocity OFF Pressure DIP Switch 3 Direction ON Unidirectional OFF Bidirectional DIP Switch 4 Response ON Slow OFF Fast DIP Switch 5 Output ON 4 20 mA OFF Voltage DIP Switch 6 Volt Scale ON 0 5 Vdc OFF 0 10 Vdc DIP Switch 7 Unused DIP Switch 8 Unused 1 2 INCH NPT FEMALE THREADED COUPLER M37460 Scale Mode Direction Response ON Pascal MPS Velocity Uni Slow OFF In WC FPM Pressure Bi F...

Страница 5: ...st accuracy after an initial warm up period During the first few minutes of operation readings at zero pressure and the lowest pressure ranges appear erroneous Following this initial warm up period the P7650A B U device maintains its specified accuracy and stability The LCD momentarily indicates range SET when a selection is made Pressure is normally indicated on the display Units are in inches wa...

Страница 6: ...rference that may cause undesired operation IC REGULATIONS RSS GEN This device complies with Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the device Le présent appareil est conforme aux CNR d Industrie Can...

Страница 7: ...P7650A B U 7 31 00138 02 ...

Страница 8: ...05 18 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature ...

Отзывы: