P7635 DIFFERENTIAL AIR PRESSURE SENSORS

31-00147—01

2

Zero Adjustment 

The Zero adjustment should only be performed with no 
pressure applied. 

Small positive or negative pressure offsets can be 
removed using the Zero push button. Make sure that there 
is no pressure at the HI and LO pressure fittings. 
Additionally, a small piece of tubing can be connected 
between the HI and LO brass fittings to neutralize any 
external pressure effects. Press and hold the Zero button 
for 5 seconds. The P7635 will enter zero mode AFTER 
push button is released. 

SPECIFICATIONS

Supply Voltage

250 Ohm Load: 

16-36 VDC / 24VAC ± 10%, 50/60 Hz

0-5 VDC: 

12-36 VDC / 24VAC ± 10%, 50/60 Hz

500 Ohm Load: 

21-36 VDC / 24VAC ± 10%, 50/60 Hz

0-10 VDC: 

16-36 VDC / 24VAC ± 10%, 50/60 Hz

Supply Current mA [Power Consumption]

4-20 mA Output: 

23 mA minimum [0.83 VA]

VDC Output Signals: 

5 mA maximum [0.18 VA]

Output Signals

4-20 mA: 

 2-Wire Loop Powered (Output limited to 20.5 

mA Max.)

4-20 mA: 

3-Wire, VAC Powered (Output limited to 20.5 mA 

Max.)

0-5 VDC or 0-10 VDC: 

3-Wire, VAC, or VDC Powered (Out-

put limited to 5.25 and 10.25 VDC)

Sensor Accuracy: 

± 0.5 % FSO (Standard)

NOTE:

Accuracy includes linearity, hysteresis, and 
repeatability.

Operating Temperature Range: 

32 to 185°F (0 to 85°C)

Compensated Temperature Range: 

32 to 122°F (0 to 

50°C)

Humidity: 

10 to 95% RH, non-condensing

Thermal Effects: 

± 0.056% FSO/ºF (± 0.10% FSO/ºC)

NOTE:

Shift is relative to 77ºF (25ºC)

Warm Up Time: 

15 minutes

Response Time (T95): 

8 seconds

Output Update Range: 

1 Second intervals

Zero Function: 

Pushbutton Zero Function (Recom-

mended after 15 minutes warm up)

Proof Pressure [Burst Pressure]

Ranges < 1” wc (248.84 Pa): 

Proof: 270” wc (67.2 kPa)

[Burst: 415” wc (103.3 kPa)]

Ranges > 1” wc (0.2488 kPa) to < 10” wc (2.488 kPa): 

Proof: 350” wc (87.12 kPa)
[Burst: 550” wc (136.9 kPa)]

Media Types: 

Dry air or inert non-conductive gases

Din Rail Mounting: 

35 mm (U.S. Patent No. 7,416,421)

Wire Connections [Wire Size]: 

3 Position de-pluggable 

screw terminal block
[14 AWG (1.628 mm2) to 24 AWG (0.5105 mm2)]

Terminal Block Torque Rating: 

4.43 to 5.31 in-lbs. 

(0.5 to 0.6 Nm)

Tubing Size Accepted:

0.250” (6.35 mm) O.D. x 0.170” (4.318 mm) I.D.
Push-On Flexible Poly Tubing

Enclosure Material [Flame Rating]: 

Polycarbonate [UL 

94V-0]

Approvals: 

CE, RoHS2, WEEE

WEEE Directive

At the end of their useful life packaging and product 
should be disposed of via a suitable recycling center. Do 
not dispose of with household waste. Do not burn.

Содержание P7635

Страница 1: ...s not have an effect on the pressure sensor If mounting the unit horizontally a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor WIRING Shielded cable with 16 to 22AWG conductors is recommended Use the Wiring Connections table below to determine the proper wiring for your application Insert the wire into the depluggable terminal block sockets an...

Страница 2: ...acy 0 5 FSO Standard NOTE Accuracy includes linearity hysteresis and repeatability Operating Temperature Range 32 to 185 F 0 to 85 C Compensated Temperature Range 32 to 122 F 0 to 50 C Humidity 10 to 95 RH non condensing Thermal Effects 0 056 FSO ºF 0 10 FSO ºC NOTE Shift is relative to 77ºF 25ºC Warm Up Time 15 minutes Response Time T95 8 seconds Output Update Range 1 Second intervals Zero Functi...

Страница 3: ...A P7635D05M 0 to 0 5 in wc Uni 0 5 4 20mA P7635D1M 0 to 1 in wc Uni 0 5 4 20mA P7635D2M 0 to 2 in wc Uni 0 5 4 20mA P7635D5M 0 to 5 in wc Uni 0 5 4 20mA P7635D10M 0 to 10 in wc Uni 0 5 4 20mA P7635B01M 0 1 to 0 1 in wc bi 0 5 4 20mA P7635B025M 0 25 to 0 25 in wc bi 0 5 4 20mA P7635B05M 0 5 to 0 5 in wc bi 0 5 4 20mA P7635B1M 1 to 1 in wc bi 0 5 4 20mA P7635D2V 0 to 2 in wc Uni 0 5 0 10Vdc ...

Страница 4: ...he following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the device Le présent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de broui...

Отзывы: