MODELS P531, P532 AND P532UI OPERATING MANUAL
RS-232 (P531 front panel port only)
Baud
19200
Parity
None
Protocol
Modbus(RTU) fixed address of 64
Flame
Maximum flame detector response time
5 second
Minimum flame detector self-checking rate
1 second
Maximum flame failure “lock-out” time
2 to 4 seconds (adjustable)
Maximum flame failure response time
2 to 4 seconds (adjustable)
Signal for presence of flame
Flame on set point (adjustable)
Signal for absence of flame
Flame off set point (adjustable)
No large Maximum flame signal will cause lost flame indication.
Compatibility
Viewing head #3
S702, S706, S802 or S806 (and -PH and –HF versions)
Viewing head #1 or #2
S550x, S552x, S556x (and –PF versions)
Fuses
No user serviceable components are inside.
Self-resetting fuses are provided internally on the following connections:
+24 PWR DC input voltage supply (DC units only)
+24 BATT Battery input voltage supply
These require cooling off period (of no load) to reset.
Cleaning
Turn power off before cleaning.
Only wipe Panel front with a soft cloth (dry or slightly dampened with water).
Cable
Connection from the Signal processor to the viewing heads shall use approved cable:
Cable can be Instrument Tray cable with CIC C22.2 No. 239 certification C330
Or must be run inside of Conduit (with properly sealed ends).
Environmental
Ambient Temperature
-40° C to 60° C (FM) or 0° C to 52° C (CSA)
Humidity
non-condensing
Maximum 80% for temperatures below 31° C Decreasing to
50% maximum at 40° C and above
Vibration
+1 g at 10 to 150 Hz
Rev.0405